FCR-230

2

Economy (Standby):

 “Standby” is shown in the display. The heat-

ing and cooling setpoints are freely adjustable. Factory settings: 
heating=15°C, cooling=30°C.

Off:

 The controller does not heat or cool and the fan stops (unless 

mould protection has been selected or the cool-down function for the 
electric heater is running, in which case the fan will still run).

Window: 

 

 is shown in the display, the controller is off and the fan 

stops (unless mould protection has been selected or the cool-down 
function for the electric heater is running, in which case the fan will 
still run). The window contact is connected to the DI and must be 

configured.

Occupancy detection

Parameter 3 determines if the DI is window contact input or 
occupancy detection input. An occupancy detector can be connected 
to the DI in order to switch between Comfort and Economy mode.

Setpoint

The setpoint is set using the INCREASE and DECREASE buttons. 
Parameter 24 determines what is shown in the display. Refer to the 
parameter list for details.

Setpoint limitation

In parameters 34 and 35, it is possible to set the maximum allowed 
setpoint increase and decrease respectively. 
Example: If P35=5 and P34=3, the setpoint can be changed between 
17°C and 25°C (see the picture below).
The basic setpoint can be changed in parameter 64 (factory 
setting=22°C).

Figure 3: Example of setpoint limitation

Fan control

The fan can be controlled via FCR-230 with the following modes: Low 
speed, Medium speed, High speed, Auto. The current fan speed in 
the Auto mode depends on the heating or cooling demand and the 
settings for each speed. 
When using automatic control, ”AUTO” is shown in the display.
The number of fan speed steps can be selected via parameter 30. 

If the parameter is set to 1, the first fan speed step will be used for fan 

control. 
Via parameter 31, it is possible to set the fan to the lowest speed level 
when Auto mode is selected. If this parameter is set to 1, the fan will run 

in all operating modes except Off and Window (unless mould protection is 

active or the cool-down function for the electric heater is running, in which 
case the fan will run in these modes as well).

Manual control of the fan speed

By pressing the fan button, you change the fan speed according to the 
sequence I

à

II

à

III

à

AUTO. When using manual control, ”MAN” is shown 

in the display. 

If the fan has been configured not to be affected by the heating or cooling 

demand, ”AUTO” will not be shown when pressing the fan button.

Indications

The display has the following indications:
HEAT   Heating control
COOL   Cooling control

       The open window symbol is shown if this function has  

 

been configured and a window is open. 

OFF   The controller does not heat or cool

On/Off button

By pressing the On/Off button, FCR-230 will switch between Off mode 

and Comfort/Economy mode.

Parameter list

When the controller is in Comfort mode or Window mode, different param

-

eter values can be set in a parameter list. 
Hold the INCREASE and DECREASE buttons depressed simultaneously 
for about 5 seconds until the Service symbol is displayed and then press 
the INCREASE button twice.
First the display will show parameter 1. Use the INCREASE and DE-

CREASE buttons to scroll between the parameters and press the On/Off 

button to select the desired parameter. The parameter number will then 
be replaced by the parameter value. The value can be changed using the 
INCREASE and DECREASE buttons. If a button is held depressed the 

value will start scrolling, first slowly and then with increasing speed.

To exit the parameter list and go back to the basic display, press the IN-
CREASE button until “EXIT” is shown (one step before parameter 1) and 

press the On/Off button. You can also exit the parameter list by pressing 

down the INCREASE and DECREASE buttons simultaneously.

Parameters

The following parameters can be changed in the parameter list.

Nº = parameter number
FS = factory setting
NO = normally open
NC = normally closed

Description

FS

1

Control mode:
2=2-pipe system 
3=4-pipe system 

 

4=(Electric heater) N/A

3

2

Change-over mode: 
0=Heating control, 1=Cooling control, 2=Automatic 
change-over depending on analogue temperature 
sensor or digital input

0

3

Operating mode when activating digital input 1, 
terminal 40/41:
0=Economy mode (occupancy detector)

1=Off mode (window contact)

0

4

Mould protection:
0=Not active
1=Active (fan never stops)

0

5

Neutral zone at Comfort mode (NZC). If the neu-
tral zone is 2 K, the heating setpoint is equal to the 
setpoint minus 1 and the cooling setpoint is equal 
to the setpoint plus 1.

0 K

6

Heating setpoint when unoccupied

15°C

7

Cooling setpoint when unoccupied

30°C

8

P-band for the room controller

10 K

9

I-time for the room controller

300 s

10

Not used for this model

11

Switch off timer for Comfort mode

0 min

12

Switch on delay for Comfort mode

0 min

13

Sensor connected to AI1, terminal 42/43:
0=Internal sensor, 1=External room sensor

0

14

Sensor connected to UI1, terminal 43/44:
0=None, 1=Change-over digital, 2=Change-over 
analogue

0

15

Type of digital actuator:
0=Thermal, 1=3-point

0

16-
17

Not used for this model