Area of use

The radiant heaters are primarily used to create
comfortable heating on terraces, balconies,
openair
restaurants etc. They can also be used for
selective heating in storage rooms and workshops.
The Confortinfra is also approved for installation in
bathrooms and shower rooms.
The heater is approved by SEMKO in splash proof
design, IP24. It carries the CE-mark and is in
compliance with the EMC-directive.
Positioning
The heaters must be mounted so that they enclose
the area which is to be heated, see fig. 3. Suitable
distance from the floor is 2—2,5 m. Closer to the
floor is not recommended as the additional heat
may seem unpleasant.

Mounting

• First study fig. 1 and 2. NB! The minimum

distances in fig. 1 must be kept!

• The heaters may only be mounted horizontally!
• The heater must not be mounted so the circuit

breaker can be reached from a bathtub or
shower.

• The heater must not be placed directly under a

wall-outlet!

• The mounting brackets enable mounting in

three different angles for ceiling or wall
mounting. Parallel to the wall/ceiling, 18° or
36° angle.

• Choose the desired angle and fasten the

bracket onto wall or ceiling. The holes are Ø 5
mm, c-c distance is 25 mm.

• Fasten the heaters, snap into the brackets, and

secure it by tightening the securing screws (104
mm long) and the domed nuts (spanner width

mm).

Electrical installation

The electrical installation should be perma-nent
and carried out by a qualified electrician in
conformity with prevailing regulations. The CIR
1XX type must be preceded by an all-pole switch. A
terminal block, which enables connection to other
heaters is situated on the same end of the heater
as the name plate.
Please note that the inlet must be tight. A cable of
EKK or EKLK type or similar must be used.

Minimum cross section area

230V
protected by 10A (up to 2 kW) - min. 1,5mm²
protected by 16A (2—3,5 kW) - min. 2,5 mm²
400V
protected by 10A (up to 4kW) - min. 1,5 mm²
protected by 1 6A (4—6 kW) - min. 2,5 mm²

Maintenance

The heater is on the whole made of rustproof
material and usually does not require any
maintenance. Pollution can in the long run dull
the reflectors somewhat. This however has very
little affect on its function.
If the heater is very dirty it can be cleaned with
compressed air. If the reflector remains dirty it must
be replaced by an authorized repairman. The
reflector must not be polished as this may damage
the protective surface.

GB

Содержание CIR105

Страница 1: ...Comfortinfra CIR SE 5 4 NO GB 8 7 6 FI 9 DE NL 10 FR ...

Страница 2: ...CIR 2 ...

Страница 3: ...CIR 3 ...

Страница 4: ... and fasten the bracket onto wall or ceiling The holes are Ø 5 mm c c distance is 25 mm Fasten the heaters snap into the brackets and secure it by tightening the securing screws 104 mm long and the domed nuts spanner width 7 mm Electrical installation The electrical installation should be perma nent and carried out by a qualified electrician in conformity with prevailing regulations The CIR 1XX ty...

Страница 5: ......

Страница 6: ......

Страница 7: ......

Страница 8: ...overed by this declaration of conformity comply with the EC Electromagnetic Compatibility EMC Directive 89 336 EEC 92 31 EEC EC Low Voltage Directive LVD 73 23 EEC and is are manufactured in accordance with the following stated harmonised standard s or other normative document s EMC EN 55 014 1993 EN 60 555 2 3 1991 EN 55 104 LVD EN 60 335 1 1988 incl Am 2 5 6 51 54 EN 60 335 2 30 1992 incl Am 51 ...

Страница 9: ... 0 2 272 38 39 NORWAY e mail mailbox frico no http www frico no France FRICO FRANCE Tel 33 0 4 72 42 99 42 7 rue de la libération Fax 33 0 4 72 42 99 49 F 69 270 Fontaines sur Saone e mail info frico fr FRANCE Russia FRICO representative office in Russia 1 st Golutvinsky per 3 Tel Fax 7 095 238 63 20 Moscow109180 e mail frico orc ru RUSSIA For latetest updated information see www frico se Artnr 20...

Отзывы: