AR3200C
31
GB
On/off
~20 °C
Fan step 1/2/3
Remote control - on/off, fan steps and heating steps
Heat step
Electric: Half/full power
Water: On/off (1 LED)
Temperature control
If the temperature exceeds 50 °C, the fan
runs at full speed for 2 minutes to vent out
the heat, if the temperature rises above 50
°C again during the following 5 minutes
overheating alarm is deployed. The red LEDs
flash and all the buttons are locked.
1. Disconnect the electricity with the fully
isolated switch.
2. Determine the cause of overheating and
rectify the fault.
3. Connect the unit again.
Functional test
Functional test is started using the remote
control.
Push
and
in 5 seconds
Fan and heatings steps are tested in
10-second intervals which is indicated by
lighted LEDs. When the test is completed, all
LEDs will flash for 30 seconds.
Fan step 1/2/3
On/off
Control panel - Unit without heating
Control panel - Unit with electrical heating or water
heating
1
3
2