AR3200C

27

GB

 

 

[kW]

 

 

[V]

 

 

[mm

2

]

0

230V~

1,5

AR3210CE03

3

230V~

2,5

AR3210CE05

5

230V~/400V3N~  6/1,5

AR3210CE08

8

400V3N~ 

2,5

AR3215CE08

8

400V3N~ 

2,5

AR3215CE12

12

400V3N~ 

4

AR3220CE10

10

400V3N~ 

2,5

AR3220CE16

16

400V3N~ 

6

*) Dimensioning of external wiring shall comply 
with applicable regulations and local deviations 
may occur. 

Type 

Output  Voltage 

Minimum 

area*

Control 

Start-up (E) 

When the unit is used for the first time or 
after a long period of disuse, smoke or odour 
may result from dust or dirt that has collected 
on the element. This is completely normal 
and disappears after a short time. 
  

Connecting the water coil (W) 

The installation must be carried out by an 
authorised installer. 

The water coil has copper tubes with 

aluminium fins and is suitable for connection 
to a closed water heating system. The heating 
coil must not be connected to a mains 
pressure water system or an open water 
system. 

Note that the unit shall be preceded by a 

regulating valve, see Frico valve kit.  

    The connections to the heating coil must 
be equipped with shut off valves to allow 
problem free removal. Water coil is equipped 
with a drain and a vent valve. The water coil 
is connected via connections with dimensions 
DN15 (1/2’’), outside thread, inside the unit. 
Knockouts are placed on the top and the side 
of the unit.  
    NOTE: Care must be taken when 
connecting the pipes. Use a wrench or similar 
to hold the air curtain connections to prevent 
straining of the pipes and subsequent water 
leakage during connection to water supply 
pipe-work. 

Adjustment of the air curtain and air flow 

The direction and speed of the air flow should 
be adjusted considering the load on the 
opening. Pressure forces affect the air stream 
and make it bend inwards into the premises 
(when the premises are heated and the 
outdoor air is cold).

The air stream should therefore be directed 

outwards to withstand the load. Generally 
speaking, the higher the load, the greater the 
angle that is needed.

  

Basic setting fan speed 

The fan speed when the door is open is set 
using the control. Note that the air flow 
direction and fan speed may need fine 
adjustment depending on the loading of the 
door.
  

Filter (W) 

The water coil is protected against dirt and 
blockage by an internal air filter which covers 
the coil face. 

Service, repairs and maintenance  

For all service, repair and maintenance first 
carry out the following:  
1. Disconnect the power supply. 
2. The service hatch is opened by loosening the 

snap fixings located on the bottom of the unit 
(turn 90°). The hatch must be held when the 
snap fixings are loosened. See fig. 3a and 3b. 

3. After service, repairs and maintenance close 

the service hatch and make sure that the snap 
fixings lock properly. 

Unit without heating or with water heating 

The electrical connection is made on the 
front or on the top of the unit. Control 
(230V~) should be connected to a terminal 
block in the terminal box.  

Unit with electrical heating 

The electrical connection is made on the front 
or on the top of the unit. Control (230V~) and 
power supply for heat (400V3~) should be 
connected to a terminal block in the terminal 
box.  

The cable glands used must meet the 

protection class requirements. The largest 
cable diameter for the terminal block is 16 
mm². 
See wiring diagrams. 
 

Содержание AR3210C

Страница 1: ...AR3200C 19 SE 26 GB Original instructions 32 FR 46 DE 54 ES 39 NO 62 IT 70 NL 78 PL 85 RU...

Страница 2: ...leitungsseiten bestehen haupts chlich aus Bildern F r die bersetzung der verwendetenTexte in englischer Sprache siehe die entsprechenden Sprachseiten DE Las p ginas introductorias contienen b sicament...

Страница 3: ...AR3200C 3 1028 1538 2028 1078 1588 2078 475 525 90 70 256 90 135 51 29 20 29...

Страница 4: ...AR3200C 4 244 134 933 805 156 525 66 805 1315 157 Mounting on threaded bars outside the unit AR3220C AR3210C AR3215C Front view Side view...

Страница 5: ...AR3200C 5 Fig 1b Mounting on threaded bars outside the unit Mounting on threaded bars outside the unit Fig 1a Mounting brackets on delivery AR3220C...

Страница 6: ...R3200C 6 Mounting on threaded bars inside the unit Fig 2a Mounting brackets on delivery 124 392 E A 932 W 848 E A 851 W 935 121 124 850 1360 54 88 Top view Side view AR3220C AR3210C AR3215C W 84 121 8...

Страница 7: ...Fig 2c Location of the mounting brackets on the inside of the unit AR3220C 6x AR3210C AR3215C 4x Fig 2d In order to mount the brackets remove the service hatch outlet grille and covering plates AR322...

Страница 8: ...AR3200C 8 Fig 3a Snap fixings 2 1 1 2 90 AR Service hatch Fig 3b Open the unit Fig 4 Terminal box and control panel inside unit...

Страница 9: ...C PA34CB20 AR3220C PA34VD15 AR3210C AR3215C PA34VD20 AR3220C PAMLK AR3200C FHDN15 AR3200C W PA2DR AR3200C PAMLK AR3200C 9 PA34TR PA2DR PA34CB PA34VD FHDN15 VOT15 DN15 VOT20 DN20 VOT25 DN25 VKF15LF DN1...

Страница 10: ...tallation type E 3 Sound pressure LpA Conditions Distance to the unit 5 metres Directional factor 2 Equivalent absorption area 200 m At lowest highest airflow 4 t temperature rise of passing air at ma...

Страница 11: ...flow l s Pressure drop kPa AR3210CW max 1500 8 8 35 0 05 2 4 14 1 46 0 17 23 7 min 1000 5 9 30 0 03 1 0 10 9 50 0 13 14 8 AR3215CW max 2600 15 2 33 0 08 8 5 24 5 46 0 30 92 3 min 1700 10 0 28 0 05 3 4...

Страница 12: ...in 2500 14 3 36 0 14 11 2 15 6 36 0 19 18 6 Supply water temperature 55 C Room temperature 18 C Outlet air temperature 35 C 1 Water temperature 55 35 C Room temperature 18 C Type Fan position Airflow...

Страница 13: ...Red IR WATER ALARM HEAT 0 10V 4 3 2 1 AR3210CW AR3215CW AR3220CW Black Brown Blue Run M C Black Blue Brown AR3200CA AR3200CW F1 0 10V F2 F3 N H1H2 N on off 2 1 PE N L PE N L On Only 2 m version Right...

Страница 14: ...ue N L Mid Low c1 b1 Yellow Red White Orange 230V IR WATER ALARM HEAT 0 10V 4 3 2 1 AR3210CE03 AR3210CE05 C INTERNAL SENSOR 0 10V F2 F3 N F1 H1H2 N on off 1 2 N PE L PE N L Over heat cut out C1 On L3...

Страница 15: ...F2 F3 N F1 H1H2 N on off 1 2 N PE L PE N L On K1 high power K2 low power Over heat cut out C K1 K2 L3 L2 N PE L L1 400V3N M Run C Black Brown Blue MidLow N L c1 b1 White Orange Red Yellow Blue Black I...

Страница 16: ...EAT 0 10V WATER ALARM 3 1 2 4 AR3215CE08 Black Right motor Run M Left motor Blue Brown Black M C Yellow Blue Red Black Blue Brown White Orange Run Black Blue Yellow Red White Orange Low L N Mid b1 c1...

Страница 17: ...eat cut out Over heat cut out C K3 K4 C K2 low power K1 high power K1 K2 Low M Run Left motor C Blue Brown Black N Mid L M Right motor Run Black C Blue Brown b1 c1 Blue N Black Low Mid L b1 c1 L1 L3 L...

Страница 18: ...free contact 5A x 3 5A 16A N H1H2 N 1 On Off F1 F2 F3 on off 2 N L PE N L PE 0 10V 0 10V HEAT ALARM WATER INTERNAL SENSOR IR C Black Brown Blue Mid Low N L c1 b1 M Left motor Run M Right motor Run Bl...

Страница 19: ...horizontally with the supply air grille facing downwards as close to the door as possible concealed in the false ceiling The only visible part of the unit is Mounting on threaded bars inside the unit...

Страница 20: ...ment of the air curtain and air flow The direction and speed of the air flow should be adjusted considering the load on the opening Pressure forces affect the air stream and make it bend inwards into...

Страница 21: ...returned to within the motor s operating limits Replacing the water coil W 1 Shut off the water supply to the unit 2 Open the vent valve 3 Open the drain valve 4 When the water coil is empty disconne...

Страница 22: ...rty If there is no heat check the following The functions internal sensor and settings of the built in control system For units with electrical heating also check the fol lowing Power supply to electr...

Страница 23: ...Factory setting dip switches Unit with water heating Dip switch 3 is used for PA2DR optional 2 1 3 Factory setting dip switches Unit without heating or with electrical heating Dip switch 3 is used for...

Страница 24: ...The red LEDs flash and all the buttons are locked 1 Disconnect the electricity with the fully isolated switch 2 Determine the cause of overheating and rectify the fault 3 Connect the unit again Funct...

Страница 25: ...0780 20160212 HH CH Main office Frico AB Tel 46 31 336 86 00 Box 102 SE 433 22 Partille mailbox frico se Sweden www frico se For latest updated information and information about your local contact www...