![Frico ACC1000WL Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/frico/acc1000wl/acc1000wl_manual_2332174015.webp)
15
AC Corinte
Technical specifications |
Thermozone AC Corinte E with electrical heat
Type
Output
steps
[kW]
Airflow
[m
3
/h]
∆
t
*2
[°C]
Sound
level
*3
[dB(A)]
Voltage
motor
[V]
Voltage
heat
[V]
Amperage
motor
[A]
Amperage
heat
[A]
Height/
Length
[mm]
Weight
[kg]
ACC1000E
*1
0/6/9
950/1900
29/14
44/61
230V~
400V3~
2,2
8,7/13,0
1000
47
ACC1500E
0/8/12
1350/2600
27/14
45/62
230V~
400V3~
2,9
11,5/17,3
1500
63
ACC2000E
0/12/18
1980/3800
28/14
47/64
230V~
400V3~
4,3
17,3/26,0
2000
95
ACC2500E
0/12/18
2340/4500
23/12
48/65
230V~
400V3~
5,1
17,3/26,0
2500
110
ACC3000E
0/16/24
2660/5100
27/14
48/65
230V~
400V3~
5,8
23,1/34,6
3000
126
*
1
) ACC1000E is available only for horizontal mounting.
*
2
)
∆
t = temperature rise of passing air at maximum heat output and lowest/highest airflow.
*
3
) Conditions: Distance to the unit: 5 metres. Directional factor: 2. Equivalent absorption area: 200 m
2
.
Technical specifications |
Thermozone AC Corinte WL with water heat, coil for low tempered water <80/60 °C
Type
Output
*2
[kW]
Airflow
[m
3
/h]
∆
t
*2,3
[°C]
Water
volume
[l]
Sound level
*4
[dB(A)]
Voltage
motor
[V]
Amperage
[A]
Height/
Length
[mm]
Weight
[kg]
ACC1000WL
*1
19
950/1900
42/35
2,0
44/61
230V~
2,1
1000
47
ACC1500WL
29
1350/2600
41/34
3,2
45/62
230V~
2,9
1500
63
ACC2000WL
42
1980/3800
40/33
4,3
47/64
230V~
4,3
2000
95
ACC2500WL
52
2340/4500
41/34
5,4
48/65
230V~
5,0
2500
110
ACC3000WL
60
2660/5100
38/31
6,6
48/65
230V~
5,7
3000
126
Technical specifications |
Thermozone AC Corinte WH with water heat, coil for high tempered water >80/60 °C
Type
Output
*2
[kW]
Airflow
[m
3
/h]
∆
t
*2,3
[°C]
Water
volume
[l]
Sound
level
*4
[dB(A)]
Voltage
motor
[V]
Amperage
[A]
Height/
Length
[mm]
Weight
[kg]
ACC1000WH
*1
11
950/1900
26/20
1,1
44/61
230V~
2,1
1000
47
ACC1500WH
17
1350/2600
26/20
1,9
45/62
230V~
2,9
1500
63
ACC2000WH
24
1980/3800
25/19
2,5
47/64
230V~
4,3
2000
95
ACC2500WH
30
2340/4500
25/23
3,3
48/65
230V~
5,0
2500
110
ACC3000WH
35
2660/5100
23/17
3,9
48/65
230V~
5,7
3000
126
*1) ACC1000W is available only for horizontal mounting.
*2) Applicable at water temperature 80/60 °C, air temperature in +15 °C.
*3)
∆
t = temperature rise of passing air at maximum heat output and lowest/highest airflow.
*4) Conditions: Distance to the unit: 5 metres. Directional factor: 2. Equivalent absorption area: 200 m
2
.
Protection class AC Corinte E/W (IP20).
CE compliant.
Содержание ACC1000WL
Страница 1: ...6 14 DE 3 xx PL Thermozone AC Corinte...
Страница 3: ...3 AC Corinte Dimensions and connections 50 120 Horizontal ACC E W Details of ACC W...
Страница 5: ...Wiring diagrams AC Corinte Electric regulations options Level 1 5 AC Corinte...
Страница 6: ...Wiring diagrams AC Corinte Electric regulations options Level 2 6 AC Corinte...
Страница 7: ...Wiring diagrams AC Corinte Electric regulations options Level 3 7 AC Corinte...
Страница 8: ...Wiring diagrams AC Corinte Water regulations options Level 1 8 AC Corinte...
Страница 9: ...Wiring diagrams AC Corinte Water regulations options Level 2 9 AC Corinte...
Страница 10: ...Wiring diagrams AC Corinte Water regulations options Level 3 10 AC Corinte...