Technical specifications 

|     ACCS E with Electrical heat    

3

*

1

) Available only for horizontal mounting. 

*

2

) Lowest/highest airflow of totally 5 fan steps.

*

3

) Conditions: Distance to the unit 5 metres. Directional factor: 2. Equivalent absorption area: 200 m². At lowest/highest airflow.

*

4

t = temperature rise of passing air at maximum heat output and lowest/highest airflow.

*

5

) Applicable at water temperature 80/60 °C, air temperature, in +18 °C.

*

6

) Applicable at water temperature 60/40 °C, air temperature, in +18 °C. 

*

7

) Horizontal mounting

*

8

) Vertical mounting

CE compliant.
Protection class: IP20. 

Type

Outout 
steps 
[kW]

Airflow

*2

 

  
[m

3

/h]

t

*4 

  
[°C]

Sound  
level*

3

 

[dB(A)]

Voltage  
motor 
[V]

Amperage  
motor  
[A] 

Voltage [V] 
Amperage [A] 
(heat)

Length 
 
[mm]

Weight  
 
[kg]

ACCS10E08*¹

2,7/5,4/8,1

950/1900

25/13

44/61

230V~

2,2

400V3~/11,7

1000

50

ACCS15E12*¹

3,9/7,8/11,7

1350/2600

26/13

45/62

230V~

2,9

400V3~/16,9

1500

65

ACCS20E16

5,4/10,8/16,2

1980/3800

24/13

47/64

230V~

4,3

400V3~/23,4

2000

95

ACCS25E20

6,6/13,2/19,8

2340/4500

25/13

48/65

230V~

5,1

400V3~/28,6

2500

110

ACCS30E23

7,8/15,6/23,4

2660/5100

26/14

48/65

230V~

5,8

400V3~/33,8

3000

130

Type

Output*

5

Airflow

*2

t

*4,5

Water 

volume

Sound

Voltage Amperage  Length

Weight

H*

7

 

[kW]

V*

8

 

[kW]

 
[m

3

/h]

H*

7

 

[°C]

V*

8

 

[°C]

H*

7

 

[l]

V*

[l]

level*

3

 

[dB(A)]

motor 
[V]

motor  
[A]

 
[mm]

  
[kg]

ACCS10WH*¹

11,1

-

950/1900

23/17

-

2,0

-

44/61

230V~

2,1

1000

50

ACCS15WH*¹

15,1

-

1350/2600

23/17

-

3,2

-

45/62

230V~

2,9

1500

65

ACCS20WH

22,3

30,3

1980/3800

23/17

30/24 4,3

3,0

47/64

230V~

4,3

2000

95

ACCS25WH

27,1

33,4

2340/4500

23/18

28/22 5,4

3,0

48/65

230V~

5,0

2500

110

ACCS30WH

35,2

51,9

2660/5100

26/21

38/30 6,6

5,6

48/65

230V~

5,7

3000

130

Type

Output*

6

Airflow

*2

t

*4,6

Water 

volume

Sound Voltage Amperage  Length Weight

H*

7

 

[kW]

V*

8

 

[kW]

 
[m

3

/h]

H*

7

 

[°C]

V*

8

 

[°C]

H*

7

 

[l]

V*

[l]

level*

3

 

[dB(A)]

motor 
[V]

motor  
[A]

 
[mm]

  
[kg]

ACCS10WL*¹

9,0

-

950/1900

18/14

-

1,1

-

44/61

230V~

2,1

1000

50

ACCS15WL*¹

16,8

-

1350/2600

24/19

-

1,9

-

45/62

230V~

2,9

1500

65

ACCS20WL

23,5

23,1

1980/3800

23/18 22/18 2,5

4,4

47/64

230V~

4,3

2000

95

ACCS25WL

29,3

25,8

2340/4500

24/19

21/17 3,3

4,4

48/65

230V~

5,0

2500

110

ACCS30WL

34,6

31,1

2660/5100

25/20 22/18 3,9

5,6

48/65

230V~

5,7

3000

130

Technical specifications

  |  ACCS WH with water heat,  coil for high temperature water (

5

80 °C) 

 2

Technical specifications

  |  ACCS WL

,

 with water heat,  coil for high temperature water (

4

80 °C)  2

Содержание AC Corinte ACCS20

Страница 1: ... 22 SE 57 NL 42 ES 32 NO 37 DE 52 IT 28 GB 47 FR 67 RU 62 PL AC Corinte ACCS Original instructions ...

Страница 2: ...Texte in englischer Sprache siehe die entsprechenden Sprachseiten DE Las páginas introductorias contienen básicamente imágenes Consulte la tra ducción de los textos en inglés que las acompañan en las páginas del idioma correspondiente ES De inleidende pagina s bevatten hoofdzakelijk afbeeldingen Voor een vertaling van de gebruikte Engelse teksten zie de pagina s van de resp taal NL Le pagine intro...

Страница 3: ... 105 207 78 115 VL A VR A VL B VR B L 400 314 50 L mm ACCS20 2000 ACCS25 2500 ACCS30 3000 Vertical mounting Upper part of the unit seen from above Connection dimensions inside thread 1 DN25 Bottom part of the unit seen from above ...

Страница 4: ...4 ACCS 50 120 Fig 1 Details of ACCS W Dimensions and connections Fig 2 Securing in the wall or ceiling Note The air curtain must be secured in the wall or ceiling M8 Securing ...

Страница 5: ...5 ACCS Fig 3 Extension hood Accessory 8 x Ø6 for securing at the top 8 x Ø6 for securing in the air curtain screws included 4 x Ø10 for securing at the top ...

Страница 6: ... 220 93 L mm ACCS10 1000 ACCS15 1500 ACCS20 2000 ACCS25 2500 ACCS30 3000 Horizontal mounting Connection dimensions W inside thread 3 4 DN20 206 206 1069 L 3000 206 206 L 1000 1500 L 2 206 L 2000 2500 1069 206 Mounting dimensions ...

Страница 7: ...7 ACCS Fig 5 ACCS Wall bracket Accessory 313 52 264 26 Ø 12 2x 185 40 50 39 Ø12 2x Fig 4 Details of ACCS E ...

Страница 8: ...8 ACCS Fig 7 Minimum distances ACCS E 200 mm ACCS W 180 mm Minimum distance Fig 6 To open To open Vertical and horizontal mounting ...

Страница 9: ...Type ACCWBB ACCWBP ACCWBMP ACCSEH AXP300 FH1025 Accessories ACCW ACCSEH FH1025 AXP300 9 ACCS ...

Страница 10: ...DN20 VOSP25 673 09 46 DN25 VOT15 DN15 VOT20 DN20 VOT25 DN25 VMT15 DN15 VMT20 DN20 VMT25 DN25 VAT 482 98 30 SIReB 673 09 57 SIReAC 673 09 64 SIReAA 673 09 66 SIReRTX 673 09 22 70x33x23 mm SIReUR 673 09 21 114x70x50 mm SIReWTA SIReCJ4 SIReCJ6 SIReCC603 673 09 23 3 m SIReCC605 673 09 24 5 m SIReCC610 673 09 25 10 m SIReCC615 673 09 26 15 m SIReCC403 673 09 27 3 m SIReCC405 673 09 28 5 m SIReCC410 673...

Страница 11: ...ransformer 230V 200V 170V 145V 120V 100V N Black Black Grey Blue Blue White White C2 C1 ROOM Internal sensor Motor protection C C C Transformer 230V 200V 170V 145V 120V 100V N Yellow Orange Red Brown Black Green Blue ACCS15E C C C C ACCS25E ACCS20E C ACCS30E 400V3 230V N N L 11 ACCS ...

Страница 12: ...200V 170V 145V 120V 100V N Black Blue White White Supply 230V C2 C1 ROOM Internal sensor Motor protection Transformer 230V 200V 170V 145V 120V 100V N Yellow Orange Red Brown Black Green Blue ACCS10W C C C ACCS15W C C C C ACCS25W ACCS20W C ACCS30W 230V L N 12 ACCS ...

Страница 13: ...nced see manuals for SIRe 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY SIReB1 SIReRTX optional SIReUB1 230V 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY SIReB1 SIReB1 SIReRTX optional SIReUB1 13 ACCS ...

Страница 14: ...SIReB Basic ACCS W C C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY 230V SIReB1 SD230 SIReRTX optional SIReUB1 14 ACCS ...

Страница 15: ...d see manuals for SIRe C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY 230V 230V 230V SIReB1 SIReB1 SIReB1 SD230 SD230 SD230 SIReRTX optional SIReUB1 15 ACCS ...

Страница 16: ...rop kPA ACCS10WH max 1900 10 9 53 5 0 07 5 6 13 4 39 0 0 16 23 2 min 950 5 4 37 3 0 02 0 9 8 9 45 9 0 11 11 2 ACCS15WH max 2600 14 9 54 7 0 10 2 1 18 3 38 9 0 22 8 3 min 1350 7 7 40 7 0 04 0 4 12 5 45 5 0 15 4 2 ACCS20WH max 3800 21 7 53 4 0 14 5 1 26 9 39 0 0 33 21 6 min 1980 11 3 38 0 0 05 0 9 18 4 45 6 0 23 10 9 ACCS25WH max 4500 25 8 52 0 0 17 4 1 32 9 39 7 0 41 21 0 min 2340 13 4 37 6 0 06 0 ...

Страница 17: ...max 2600 14 9 58 0 0 15 4 2 17 7 38 3 0 39 23 3 min 1350 7 7 42 6 0 05 0 6 12 0 44 3 0 27 11 4 ACCS20WH max 3800 21 7 57 0 0 21 10 1 25 9 38 2 0 58 60 0 min 1980 11 3 41 0 0 07 1 4 17 6 44 4 0 39 29 8 ACCS25WH max 4500 25 8 55 5 0 24 8 0 31 7 38 9 0 71 40 9 min 2340 13 4 40 5 0 08 1 1 21 4 45 1 0 48 28 7 ACCS30WH max 5100 29 2 46 4 0 20 5 8 40 5 41 6 0 89 85 4 min 2660 15 2 34 0 0 08 1 1 26 9 48 0...

Страница 18: ... 0 6 40 6 62 9 0 50 35 6 Supply water temperature 80 C Room temperature 18 C Outlet air temperature 35 C 1 Water temperature 80 60 C Room temperature 18 C Type Fan position Airflow m3 h Output kW Return water temp C Water flow l s Pressure drop kPA Output 2 kW Outlet air temp C Water flow l s Pressure drop kPA ACCS20WH max 3800 21 9 41 1 0 14 5 5 30 3 41 5 0 37 36 3 min 1980 11 4 32 0 0 06 1 1 20 ...

Страница 19: ... 57 4 0 38 19 8 ACCS30WL max 5100 29 2 25 9 0 13 3 9 57 1 51 2 0 70 70 2 min 2660 15 3 22 5 0 06 1 2 36 2 58 4 0 44 31 2 Supply water temperature 70 C Room temperature 18 C Outlet air temperature 35 C 1 Water temperature 70 50 C Room temperature 18 C Type Fan position Airflow m3 h Output kW Return water temp C Water flow l s Pressure drop kPA Output 2 kW Outlet air temp C Water flow l s Pressure d...

Страница 20: ...timized output 2 Nominal output at given supply and return water temperature See www frico se for additional calculations ACCS WL Horizontal mounting Output charts water Supply water temperature 55 C Room temperature 18 C Outlet air temperature 35 C 1 Water temperature 55 35 C Room temperature 18 C Type Fan position Airflow m3 h Output kW Return water temp C Water flow l s Pressure drop kPA Output...

Страница 21: ...S20WL max 3800 21 8 32 7 0 14 3 5 31 1 42 3 0 38 18 9 min 1980 11 3 27 4 0 06 0 9 19 9 47 8 0 24 8 6 ACCS25WL max 4500 25 8 35 1 0 18 5 2 34 7 40 9 0 42 23 0 min 2340 13 4 27 7 0 08 1 2 22 3 46 3 0 27 10 5 ACCS30WL max 5100 29 2 32 2 0 19 7 1 41 7 42 3 0 51 39 7 min 2660 15 3 25 5 0 08 1 8 26 7 47 8 0 33 18 Supply water temperature 60 C Room temperature 18 C Outlet air temperature 35 C 1 Water tem...

Страница 22: ...8 15 6 23 4 2660 5100 26 14 48 65 230V 5 8 400V3 33 8 3000 130 Type Output 5 Airflow 2 t 4 5 Water volume Sound Voltage Amperage Length Weight H 7 kW V 8 kW m3 h H 7 C V 8 C H 7 l V 8 l level 3 dB A motor V motor A mm kg ACCS10WH 11 1 950 1900 23 17 2 0 44 61 230V 2 1 1000 50 ACCS15WH 15 1 1350 2600 23 17 3 2 45 62 230V 2 9 1500 65 ACCS20WH 22 3 30 3 1980 3800 23 17 30 24 4 3 3 0 47 64 230V 4 3 20...

Страница 23: ...in is installed on adjustable feet which makes it possible to compensate for any surface undulations The feet Electrical installation The installation which should be preceded by an omnipolar switch with a contact separation of at least 3 mm should only be wired by a competent electrician and in accordance with the latest edition of IEE wiring regulations The control system is pre installed in the...

Страница 24: ...direction and fan speed may need fine adjustment depending on the loading of the door Filter W The distance between the coil plates in combination with the hole diameter of the intake grille protects against dirt and blockage This normally makes a separate filter unnecessary Service repairs and maintenance For all service repair and maintenance first carry out the following 1 Disconnect the power ...

Страница 25: ...e coil It can be accessed via the service hatch Trouble shooting If the fans are not working or do not blow properly check the following That the intake grille filter is not dirty Functions and settings of the SIRe control system see manual for SIRe If there is no heat check the following Functions and settings of the SIRe control system see manual for SIRe For units with electrical heating also c...

Страница 26: ...ly be run for a short time when it is not being used for extended periods of time Safety For all installations of electrically heated products should a residual current circuit breaker 300 mA for fire protection be used Keep the areas around the air intake and exhaust grilles free from possible obstructions The unit may have hot surfaces during operation and when cooling down The unit must not be ...

Страница 27: ...B Tel 46 31 336 86 00 Box 102 Fax 46 31 26 28 25 SE 433 22 Partille mailbox frico se Sweden www frico se For latest updated information and information about your local contact www frico se Art no 208028 2013 05 24 SÄ HH ...

Отзывы: