Soloclim vertical

11

EN

Electrical installation  

Soloclim is equipped with a 1,5 metre long cord with plug 

for connection to an earthed power socket. The power 

supply should be protected by a circuit breaker 1P+N, 

6A, type C. If the cable is damaged it must be replaced 

by a qualified service technician. The installation, which 

should be preceded by an isolator switch with a contact 

Opening the unit Fig.9.  

The unit shold not be opened by any unauthorised 

personnel. Opening the unit is only necessary for adapting 

it to access the terminal block or to clean the filter.  

1.  Switch off the power and disconnect the unit.  
2.  Remove the upper grill by lifting it straight up starting 

with the back edge. 

3. 

Remove the air deflector at the front by lifting it by its 

upper corners. 

4. 

Remove the filter. 

5.  Unscrew the four screws securing the upper front panel 

and remove the panel. Note! The display is protected by 

double-sided tape on the inside of the front. 

Drainage Fig.8.  

The unit is supplied with a drip tray for collecting the 

condensation which should be channelled to a suitable 

place for drainage. The drip tray is fitted with a 0,6 m long 

drainage tube with a safety drain. Size and position are 

shown on the drilling template and fig.8.  

1.  Remove the nozzle from drainage tube, or replace the 

tube with a longer drainage tube. Be careful not to 

squeeze the tube.

2.  The whole tube must be coated with anti-condensation 

insulation indoors and in the wall.

3.  Direct it towards a suitable location for drainage and 

keep a downward slope of minimum 3%.

4.  Insulate junction points.  
If no external drainage is prepared, do not remove the 

nozzle from the drainage tube. It is possible to empty 

the drip tray using the safety drain. When the drip tray is 

full, the unit will stop and error code "OF" appears on the 

display. See trouble shooting.  

 

Collecting condensation in a container Fig.8b.  

If the condensation is channelled to a water tank, or 

similar, it should not be hermetically sealed. Prevent the 

end of the drainage tube from immerse in the water.  

 

Open drain Fig.8b. 

If the condensation is not collected, check that the 

expelled water does not cause any damage or problems 

to people or objects. The water could freeze if the outdoor 

temperatures are below zero, thus creating a hazard. In 

this case, appropriate barriers should be installed in order 

to prevent people from approaching the area. 

6.  Fasten the unit to the upper part of the bracket. 
7. 

Verify that the bracket fits securely into the interlocking 

points on the unit. 

8.  Fix the anchor bracket to the wall.  
For easier connections, a spacer can be used to keep the 

lower part of the unit away from the wall. 

separation of at least 3 mm, should only be wired by a 

competent electrician and in accordance with the latest 

edition of IEE wiring regulations.  

 

Access to the terminal block Fig.9.  

Access to the terminal block is only necessary when 

replacing the wired cable or when using the CP presence 

contact.  

1.  Switch off the power and disconnect the unit.  
2.  Remove grille and front panel (see Opening the unit).  
3.  Unscrew the screws of the terminal block cover and 

remove it.  

It is possible to remove the unit's cable with plug and 

connect the power supply directly to the terminal block.  

4.  Disconnect the power cord from the terminal block. 
5.  Connect the power supply, checking that it has 

a suitable earth connection and dimensionning 

(minimum cable area: 

1,5 mm

2

).  

 

CP presence contact connection Fig.9.  

When the CP contact opens (very low voltage, connected 

to a potential free contact) the unit switches to stand-by 

mode and CP appears on the display. This contact enables 

the connection of an external device such as: prescence 

sensor, window opening contact, remote on/off, activation 

badge. A double insulation cable should be used. See 

wiring diagrams. 

 

Suggestions for saving energy 

• 

Always keep the filters clean. 

•  Keep doors and windows closed in the air conditioned 

room.

•  Do not let direct sunlight enter the room (use curtains, 

blinds or shutters).

•  Avoid using high energy consumption devices in the 

room. 

Maintenance 

The power supply to the unit must be disconnected during 

all service, repair and maintenance work. Wait until the 

unit is cold.  

 

Housing  

To clean the casing, wipe it with a soft, dry cloth. If it is 

very dirty, use a slightly damp cloth and, if necessary, 

a mild detergent. Wipe afterwards with a dry cloth to 

remove moisture.   

 

Filter  

Clean the air filter after a period of continuous use and 

according to the concentration of impurities in the air, 

or when you wish to start-up the unit after a period of 

inactivity.  

1. 

Extract the filter, see Opening the unit. 

2. 

Clean the filter with a vacuum cleaner or by washing it 

in running water.  

3.  Allow it to dry completely before putting it back in the 

unit. 

Содержание 999925

Страница 1: ...Soloclim vertical Original instructions 9 EN 16 SE 24 NO 32 FR 40 DE 48 NL 56 ES 64 PL 72 RU 80 DK 88 FI...

Страница 2: ...tzung der verwendeten Texte in englischer Sprache siehe die entsprechenden Sprachseiten DE Pocz tkowe strony zawieraj g wnie rysunki T umaczenie wykorzystanych tekst w angielskich znajduje si na odpow...

Страница 3: ...5 3V remote control battery H Plastic sheet for wall duct 2 pcs Fig 5 I Energy efficiency label J Inside flanges for air inlet and outlet 2 pcs C D A A I F E B G H A J 10 3 3 Soloclim vertical 1 Touch...

Страница 4: ...duct C 162 mm hole for inlet air duct D 18 mm condensate drain back E 18 mm condensate drain base F Electrical connection G Holes for anchor bracket H Bottom of the unit I Floor Fig 4 Drilling templa...

Страница 5: ...A Chain B Flange C Spring D Outside air grill Fig 5 Air ducts Fig 6 Wall grilles A B C D Plastic sheets for air ducts INSIDE W ALL OUTSIDE W ALL IN OUT IN OUT 5 Soloclim vertical...

Страница 6: ...Wall bracket 2 Interlocking points 3 Anchor brackets Fig 7 Mounting the unit 1 Drainage tube 0 6 m 18 mm outside 13 mm inside 2 Safety drain Fig 8 Drainage Fig 8b 2 1 3 1 2 300 mm 3 6 Soloclim vertica...

Страница 7: ...ded tape 7 Soloclim vertical Accessories Art no Type WxHxD mm 282045 SCKEG162 180x180x20 282046 SCRPK 230x120x170 Wiring diagram GR Grey BR Brown YG Yellow Green BL Blue CP Presence contact N Neutral...

Страница 8: ...COP Voltage V Refrigerant WxHxD mm Weight 2 kg 999925 SCV21DCI 2 04 2 10 2 72 3 10 230V R410a 500x1398x185 57 999926 SCV23DCI 2 35 2 36 2 75 3 15 230V R410a 500x1398x185 57 SCV21DCIN SCV23DCIN Cooling...

Страница 9: ...a gas as the designated refrigerant The refrigerant loop is sealed Only a qualified technician should attempt to service Do not discharge the refrigerant into the atmosphere It is flammable and heavie...

Страница 10: ...lles use water based paints suitable for plastic surfaces to avoid problems with the movement of the fins Wall grilles with fixed fins are available as accessory Mounting the unit Fig 7 The bracket mu...

Страница 11: ...rd In this case appropriate barriers should be installed in order to prevent people from approaching the area 6 Fasten the unit to the upper part of the bracket 7 Verify that the bracket fits securely...

Страница 12: ...er cord pulled from the socket Automatic comfort mode The unit selects cooling or heating mode automatically depending on the set temperature and its fan speed according to the room temperature Settin...

Страница 13: ...y In cooling and dehumidification mode it resets every 30 minutes to prevent the formation of condensation Setting power The unit has five power settings Minimum Medium Maximum Dual Power and Automati...

Страница 14: ...unit and is pointing towards the receiver Change batteries See next page An error code is displayed Check that the system main switch has not been tripped if it has reset it If the problem repeats im...

Страница 15: ...vent of an alarm check that the tube is not bent or obstructed thus preventing the water from flowing out Cooling Dehumidification and Heating modes can still be activated It only monitors the antifre...

Страница 16: ...ce Frico AB Tel 46 31 336 86 00 Industriv gen 41 SE 433 61 S vedalen mailbox frico se Sweden www frico net For latest updated information and information about your local contact www frico net 2022 07...

Отзывы: