AREC3200C

21

EN

Replacing heating elements/heating 

package (E) 

1. 

Mark and disconnect the cables to the heating 

elements/package. 

2. 

Remove  the  mounting  screws  securing  the 

heating elements/package in the unit and lift 

the heating elements/package out.

3. 

Install the new heating elements/package in 

reverse order to the above.  

Temperature control 

See control pages. 

Replacing motor or impeller 

1. 

Remove frame and side panel.  

2. 

Remove the screw between motor and fan.   

3. 

Disconnect the cables to the motor.  

4. 

Remove the screws securing the motor and lift 

it out together with the impeller. 

5. 

Install the new motor and/or the new impeller 

as above in reverse order. 

Overheating  

The air curtain unit with electrical heating is 

equipped with an overheat protection. If it is 

deployed due to overheating, reset as follows: 

1. 

Disconnect the power supply with the isolator 

switch. 

2. 

Determine the cause of overheating and rectify 

the fault. 

3. 

Open the service hatch. Locate the red button 

next to the terminal box inside the air curtain. 

The 2 and 2.5 metre/6.6 and 8.2 feet units are 

equipped with two red buttons, one on the 

outside of each terminal box.  

4. 

Press the red button until a click is heard.  

5. 

Reconnect the unit. 

All motors are equipped with an integral 

thermal safety cut-out. This will operate, 

stopping the air curtain should the motor 

temperature rise too high. The cut-out 

will automatically reset when the motor 

temperature has returned to within the motor’s 

operating limits.

 

Replacing the water coil (W) 

1. 

Shut off the water supply to the unit. 

2. 

Open the vent valve.  

3. 

Open the drain valve.  

4. 

When the water coil is empty, disconnect its 

connections.  

5. 

Remove the covering plate.  

6. Remove the mounting screws securing the coil 

in the unit and lift out.

7. 

Move the filter to the new unit. 

8. Install  the  new  coil  in  reverse  order  to  the 

above.  

 

Draining the water coil (W) 

The drain valve is on the underside of the coil 

on the connector side. It can be accessed via 

the service hatch.

Maintenance 

Unit with water heating 

The appliance filter should be cleaned regularly 

to ensure the air curtain effect and heat 

emission from the device. How often depends 

on local circumstances. A clogged filter is not a 

risk, but the appliance function can fail.  

1. 

Disconnect the power supply. 

2. 

The service hatch is opened by loosening the 

snap fixings located on the bottom of the unit 

(turn 90°). The hatch must be held when the 

snap fixings are loosened. See fig. 3a and 3b.  

3. 

Remove the filter and vacuum clean or wash it. 

If the filter is clogged or damaged, it may need 

to be changed. 

  

All units 

Since fan motors and other components are 

maintenance-free, no maintenance other than 

cleaning is necessary. The level of cleaning can 

vary depending on local conditions. Undertake 

cleaning at least twice a year. Inlet and exhaust 

grilles, impeller and elements can be vacuum 

cleaned or wiped using a damp cloth. Use a 

brush when vacuuming to prevent damaging 

sensitive parts. Avoid the use of strong alkaline 

or acidic cleaning agents. 

Содержание 189403

Страница 1: ...MCA Seal The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings P...

Страница 2: ...utput steps kW Airflow 1 m3 h Sound power 2 dB A FLA full load amperage 3 A Motor power W Amperage motor A Voltage V Amperage A heat Weight kg AREC3210CE07 208VNA 4 7 1630 72 21 127 0 8 208V3 20 31 AR...

Страница 3: ...AREC3210CW NA Distance from Nozzle mm 70 500 1000 Core Velocity m s 8 5 87 4 17 Uniformity 79 87 88 Frico AB certifies that the AREC3200CA AREC3200CE and AREC3200CW air curtains shown herein are lice...

Страница 4: ...C3210CE08 600VNA 17 27 950 72 9 127 0 8 600V3 8 68 AREC3215CE12 600VNA 27 41 1350 73 13 148 0 9 600V3 12 91 AREC3220CE16 600VNA 34 55 1900 74 17 254 1 5 600V3 16 130 Type Output MBH Airflow 1 cfm Soun...

Страница 5: ...AREC3210CW NA Distance from Nozzle in 2 7 20 40 Core Velocity fpm 1574 1155 820 Uniformity 79 87 88 Frico AB certifies that the AREC3200CA AREC3200CE and AREC3200CW air curtains shown herein are lice...

Страница 6: ...20 48 5 14 4 34 0 17 37 2 AREC3220CW NA max 2550 18 2 41 0 23 27 5 17 9 35 0 22 24 1 Metric chart Imperial chart 1 Recommended outlet air temperature for good comfort and optimized output 2 Nominal ou...

Страница 7: ...es EN Les pages de pr sentation contiennent principalement des images Pour la traduction des textes en anglais consultez la page correspondante la langue souhait e Las p ginas introductorias contienen...

Страница 8: ...AREC3210Cx E 1538 61 52 AREC3215Cx F 2028 81 12 AREC3220Cx G 29 1 16 H 90 3 60 I 51 2 04 J 135 5 40 K 70 2 80 L 475 19 00 M 256 10 24 N 525 21 00 B A 475 525 90 70 256 1 1 5 m 4 x M8 2 m 6 x M8 90 29...

Страница 9: ...bars outside the unit AREC3220Cx AREC3210Cx AREC3215Cx Front view Side view Ref Metric mm Imperial in Product type A 805 32 20 AREC3210Cx B 1315 52 60 AREC3215Cx C 66 2 64 D 157 6 28 E 933 37 32 F 80...

Страница 10: ...AREC3200C 10 Fig 1b Mounting on threaded bars outside the unit Mounting on threaded bars outside the unit Fig 1a Mounting brackets on delivery AREC3220Cx...

Страница 11: ...88 Top view Side view AREC3220Cx AREC3210Cx AREC3215Cx E A 851 W 935 121 88 Ref Metric mm Imperial in Product type A 850 34 00 AREC3210Cx B 1360 54 40 AREC3215Cx C 54 2 16 D 124 4 96 E 851 34 04 AREC...

Страница 12: ...2c Location of the mounting brackets on the inside of the unit AREC3210Cx AREC3215Cx 4x AREC3220Cx 6x Fig 2d In order to mount the brackets remove the service hatch outlet grille and covering plates A...

Страница 13: ...AREC3200C 13 Fig 3a Snap fixings 2 1 1 2 90 AR Service hatch Fig 3b Open the unit Fig 4 Terminal box and control panel inside unit AREC...

Страница 14: ...EC3220Cx 1 m 3 3 ft PA34CB15 AREC3210Cx AREC3215Cx PA34CB20 AREC3220Cx PA34VD15 AREC3210Cx AREC3215Cx PA34VD20 AREC3220Cx FHDN15 AREC3200CW PA34TR PA34CB PA34VD FHDN15 VKF SD230 Nipple G NPT BPV10 VLS...

Страница 15: ...4 2 3 1 A L PE N SENSOR 208V1 0 10V Only water N L PE L1 L2 L3 N L PE L1 L2 L3 Blue Yellow Red White M M Left motor Right motor 6 5 4 2 3 1 A L PE N Red 10 V Yellow 0 10 Blue GND White Tach 0 10V DOO...

Страница 16: ...b1 L3 L2 L1 a1 a2 b2 c2 c1 b1 C Over heat cut out L1 L2 L3 L3 L1 L2 C3 L1 L2 L3 L3 L1 L2 C4 L3 L2 L1 a1 a2 b2 c2 c1 b1 L3 L2 L1 a1 a2 b2 c2 c1 b1 208V3 0 10V 6 5 4 2 3 1 A L PE N M M Left motor Right...

Страница 17: ...TE R WATER PE N L PE C1 L1 L2 L3 C2 C Over he at cut out L1 L2 L3 C3 L1 L2 L3 C4 0 10V PE L1 L2 L3 6 5 4 2 3 1 A L PE N M M Left motor Right motor 6 5 4 2 3 1 A L PE N Blue Yellow Red White Red 10 V Y...

Страница 18: ...les Veuillez vous assurer que la tension d alimentation de l unit correspond la tension de secteur locale La tension d alimentation de l unit et les calibres maximums sont indiqu s sur l tiquette de d...

Страница 19: ...d bars inside the unit 1 The mounting brackets are fixed to the unit during transport Loosen them and screw them into place inside the unit in the intended holes In order to mount the brackets remove...

Страница 20: ...red Basic setting fan speed The fan speed when the door is open is set using the control Note that the airflow direction and the fan speed may need fine adjustment depending on the loading of the door...

Страница 21: ...the motor temperature has returned to within the motor s operating limits Replacing the water coil W 1 Shut off the water supply to the unit 2 Open the vent valve 3 Open the drain valve 4 When the wa...

Страница 22: ...le filter is not dirty If there is no heat check the following The functions internal sensor and settings of the built in control system For units with electrical heating also check the following Powe...

Страница 23: ...A2DR Factory setting dip switches Unit with water heating Dip switch 3 is used for PA2DR 2 1 3 Factory setting dip switches Unit without heating or with electrical heating Dip switch 3 is used for PA2...

Страница 24: ...lf full power Water On off 1 LED Temperature control If the temperature exceeds 50 C the fan runs at full speed for 2 minutes to vent out the heat if the temperature rises above 50 C again during the...

Страница 25: ......

Страница 26: ...B Tel 46 31 336 86 00 Industriv gen 41 SE 433 61 S vedalen mailbox frico se Sweden www frico net For latest updated information and information about your local contact www frico net Art no 189416 KG...

Отзывы: