SWT
8
(1)
SE:
Värme effekt
GB:
Heat output
(2)
SE: Luftflöde
GB:
Air flow
(3)
SE: Ljudnivå
GB:
Soud level
(4a)
SE: Kastlängd
GB:
Air distribution
(4b)
SE:
Kastlängd med förlängningsstos
GB:
Air distibution with extension sleeve
(5)
SE: Vattenvolym
GB:
Water volume
Technical specification
|
Fan heater SWT
2
(6)
SE: Spänning
GB: Voltage
(7)
SE: Ström
GB: Amperage
(8)
SE: LxBxD
GB: LxWxH
(9)
SE: Vikt
GB: Weight
Type
Heat (1)
output*
1
[kW]
Air flow (2)
[m
3
/h]
Air flow(2)
[m
3
/s]
Sound (3)
level*
2
[dB(A)]
∆
t*
1,3
[°C]
Air throw*
4
(4a)
[m]
Air throw*
4
(4b) with
extension collar
[m]
SWT02
7,8/11
700/1100
0,19/0,31
37/53
33/29
2,2/4
4/7
SWT12
14/18
1300/2000
0,36/0,56
44/57
25/22
2,7/4,5
5/8
SWT22
29/40
2500/3900
0,69/1,08
48/60
34/30
4,5/7,5
7/12
Type
Water (5)
volume*
5
[l]
Voltage (6)
[V]
Amperage (7)
[A]
LxWxH (8)
[mm]
Weight (9)
[kg]
RSK
(SE)
NRF
(NO)
SWT02
1,2
230V~
0,4
705x535x330
19
672 67 03
850 23 11
SWT12
1,7
230V~
0,6
825x625x355
26
672 67 04
850 23 12
SWT22
3,9
230V~
1,0
1135x735x415
41
672 67 05
850 23 13
*
1
) Applicable at water temperature 80/60 °C, air temperature, in +15 °C.
*
2
) Conditions: Distance to the unit 5 metres.
*
3
)
∆
t = temperature rise of passing air at maximum heat output and lowest/highest airflow.
*
4
) The air throw data above is valid when the horizontally adjustable air director is used and the outlet temperature is +40 °C and the
room temperature is +18 °C. The air throw is defined as the distance in a straight angle from the fan heater to the the point where the
air speed has dropped to 0,2 m/s.
*
5
) Water volume inside battery.
Protection class: (IPX4), splash-proof design.
CE compliant.