Replacing heating elements (E) 

1. Mark and disconnect the cables to the electric 

coil package.

2. 

Remove  the  mounting  screws  securing  the 

electric coil package in the unit and lift it out.

3. 

Replace faulty electric coil.

4. Install the electric coil package in reverse order 

to the above.

Replacing the water coil (W) 

1. Shut off the water supply to the unit.

2. 

Disconnect the connections to the water coil.

3. 

Remove the mounting screws securing the coil 

in the unit and lift the coil out.

4. Install  the  new  coil  in  reverse  order  to  the 

above.

Troubleshooting 

If the fans are not working or do not blow properly, 
check the following: 

• 

That the intake grille/filter is not dirty.

• 

Functions and settings of the SIRe control 

system, see manual for SIRe.

  

If there is no heat, check the following:

• 

Functions and settings of the SIRe control 

system, see manual for SIRe.

  

For units with electrical heating, also check the fol-
lowing:

• 

Power supply to electric heater coil; check 

fuses and circuit-breaker (if any).

• 

That the overheat protection has not been 

deployed.

  

For units with a water coil, also check the following:

• 

That the water coil is air free.

• 

That there is sufficient water flow and 

pressure.

• 

That incoming water is heated adequately.

 

If the fault cannot be rectified, please contact a 

qualified service technician. 

Residual current circuit breaker (E)

When the installation is protected by means of 

a residual current circuit breaker, which trips 

when the appliance is connected, this may be 

due to moisture in the heating element. When 

an appliance containing a heater element has 

not been used for a long period or stored in 

a damp environment, moisture can enter the 

element. 

This should not be seen as a fault, but is 

simply rectified by connecting the appliance to 

the main supply via a socket without a safety 

cut-out so that the moisture can be eliminated 

from the element. The drying time can vary 

from a few hours to a few days. As a preventive 

measure, the unit should occasionally be run 

for a short time when it is not being used for 

extended periods of time. 

Fan replacement 

1. Determine which of the fans is not functioning.

2. 

Disconnect the cables from the relevant fan.

3. 

Remove the screws securing the fan and lift 

the fan out.

4. Install the new fan as above in reverse order.

Overheating 

The air curtain unit with electrical heating is 

equipped with an overheat protection. If it is 

deployed due to overheating, reset as follows: 

1. Disconnect the electricity supply with the fully 

isolated switch.

2. 

Allow the electrical coil to cool.

3. 

Determine the cause of overheating and rectify 

the fault.

4. Reconnect the air curtain.

 

All motors are equipped with an integral 

thermal safety cut-out. This will operate, 

stopping the air curtain should the motor 

temperature rise too high. The cut-out 

will automatically reset when the motor 

temperature has returned to within the motor’s 

operating limits.

 

Temperature control 

Temperature control of SIRe maintains the 

exhaust temperature. If the temperature 

should exceed the preset value anyway 

the overheating alarm goes off. For more 

information see the manual for SIRe. 

Содержание 161049

Страница 1: ...ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program The AM...

Страница 2: ...NA 8 24 4650 82 30 1000 6 0 600V3 24 84 PAEC4025E30 600VNA 10 30 5600 83 38 1173 7 5 600V3 30 106 Type Output 4 kW Airflow 1 m3 h Sound power 2 dB A Motor power W Voltage motor V Amperage motor A Wate...

Страница 3: ...C4000E and PAEC4000A shown herein are licensed to bear the AMCA Seal The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and...

Страница 4: ...NA 27 82 2800 82 30 1000 6 0 600V3 24 185 PAEC4025E30 600VNA 34 102 3300 83 38 1173 7 5 600V3 30 234 Type Output 4 MBH Airflow 1 cfm Sound power 2 dB A Motor power W Voltage motor V Amperage motor A W...

Страница 5: ...00E and PAEC4000A shown herein are licensed to bear the AMCA Seal The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and com...

Страница 6: ...6 6 2 79 9 100 269 2 12 2 PAEC4020W NA max 2855 96 6 95 257 8 5 5 112 3 100 379 5 10 7 PAEC4025W NA max 3090 105 5 95 257 8 6 5 132 1 104 447 0 17 2 1 Recommended outlet air temperature for good comfo...

Страница 7: ...s EN Les pages de pr sentation contiennent principalement des images Pour la traduction des textes en anglais consultez la page correspondante la langue souhait e Las p ginas introductorias contienen...

Страница 8: ...80 Q 36 1 44 R 1572 62 88 PAEC4015x S 2062 82 48 PAEC4020x T 2572 102 88 PAEC4025x U 1515 60 60 PAEC4015x V 2004 80 16 PAEC4020x W 2515 100 60 PAEC4025x X 23 0 92 Y 40 1 60 Z 611 24 44 611 L 295 36 40...

Страница 9: ...position with the front hatch hook Fig 2 Control card SIRe is integrated in the air curtain at delivery SIRe Fig 1B When the front has been removed it it important to be sure it is firmly seated in th...

Страница 10: ...PAEC4015x PAEC4020x PAEC4025x Ref Metric mm Imperial in Product type A 127 5 08 PAEC4010 15 20 25x B 102 4 08 PAEC4010 15 20 25x C 235 9 40 PAEC4010 15 20 25x D 750 30 00 PAEC4010x E 1260 50 40 PAEC40...

Страница 11: ...15x 2 pcs 400 15 75 Fig 6 PA34WB20 PAEC4020x 3 pcs 400 15 75 Fig 6 PA34WB30 PAEC4025x 4 pcs 400 15 75 Fig 6 PAWBL15 PAEC4015x 2 pcs 560 22 05 Fig 6 PAWBL20 PAEC4020x 3 pcs 560 22 05 Fig 6 PAWBL30 PAEC...

Страница 12: ...tric Length Imperial PA34CB15 PAEC4010 15x 4 pcs PA34CB20 PAEC4020x 6 pcs PA34CB30 PAEC4025x 8 pcs PA34WS15 PAEC4010 15x 4 pcs 3 m 9 8 ft PA34WS20 PAEC4020x 6 pcs 3 m 9 8 ft PA34WS30 PAEC4025x 8 pcs 3...

Страница 13: ...24x2516 3 48x16 96x100 64 Type Product type Length Metric mm Length Imperial in PA4XT10 PAEC4010x 130 200 5 20 8 00 PA4XT15 PAEC4015x 130 200 5 20 8 00 PA4XT20 PAEC4020x 130 200 5 20 8 00 PA4XT25 PAEC...

Страница 14: ...PAEC4000 14 Accessories Note The air curtain must be secured in the wall or ceiling Fig 11 See separate manual for PA4JK PA4VDW PA4JK...

Страница 15: ...000 PA4HEVDW PAEC4000 AXP300 PAEC4000 Accessories Type Product type Length Metric Length Imperial PA34EF10 PAEC4010W PA34EF15 PAEC4025W PA34EF20 PAEC4020W PA34EF25 PAEC4025W DTV200S PAEC4000W FHDN20 P...

Страница 16: ...0 m 32 8 ft SIReCC615 15 m 49 2 ft SIReCC640 40 m 131 2 ft SIReCC403 3 m 9 8 ft SIReCC405 5 m 16 4 ft SIReCC410 10 m 32 8 ft SIReCC415 15 m 49 2 ft Accessories SIReACY SIReAAY SIReRTX SIReWTA SIReCC S...

Страница 17: ...H1 H2 N Id SIRe B1EC Room C2 C1 Actuator 230V Supply 230V PE L N Heating L N L Trafo Motor protection 0 10V GND PWM L N Motor Internal sensor M M M M 4010WA 4025WA 4020WA 4015WA 208V1 PE L1 L2 AREC400...

Страница 18: ...EC Room C2 C1 Actuator 230V Supply 230V PE L N Heating L N L Trafo K2 K1 4010E 4015E 4010E 4015E TS1 TS2 Motor protection 0 10V GND PWM L N Motor Internal sensor M M M M L1 L2 L3 L1 K2 L2 K2 L3 K2 L1...

Страница 19: ...Trafo K 2 K 1 K 2 K 1 4020E 4025E 2 X 208V3 TS 2 TS 1 Moto r p rotec tio n 0 10 V GND P WM L N Moto r Inte rna l se n so r M M M M 208V3 L1L2 L3 4025E 4020E 4020 6 motors 4025 7 motors L1 K 2 L2 K 2...

Страница 20: ...oom C2 C1 A ctuato r 230V S upply230V PE L N He ating L N L Trafo K 2 K 1 4010E 4015E TS1 TS2 Motor protec tio n L N Motor Internal sensor M M M M 6 0 0 48 0V 230V Transformer 2 x 10A FUSE L1 L2 L3 2...

Страница 21: ...0V PE L N Heating L N L Trafo K2 K1 K2 K1 4025E 4020E 4020E 4025E 2 X 600V3 480V3 TS2 TS1 TS3 TS4 Motor p rotection 0 10V GND PWM L N Motor Internal sensor M M M M 600V3 480V3 600 480V 230V Transforme...

Страница 22: ...les Veuillez vous assurer que la tension d alimentation de l unit correspond la tension de secteur locale La tension d alimentation de l unit et les calibres maximums sont indiqu s sur l tiquette de d...

Страница 23: ...ountings is available for both wall and ceiling installations se accessories pages Mounting with wall brackets 1 Remove the plastic covers on the wall brackets Fig 6A 2 Mount the brackets on the wall...

Страница 24: ...d control card see fig 2 SIRe is supplied pre programmed with quick fit connections Modular cables are connected to the control board See manual for SIRe Unit without heating or with water heating Con...

Страница 25: ...top of the unit horizontal mounting or on the reverse vertical mounting via connections DN20 3 4 external thread Flexible hoses are available as an accessory see accessories pages The connections to...

Страница 26: ...nce is connected this may be due to moisture in the heating element When an appliance containing a heater element has not been used for a long period or stored in a damp environment moisture can enter...

Страница 27: ...3 years and less than 8 years shall only switch on off the appliance provided that it has been placed or installed in its intended normal operating position and they have been given supervision or ins...

Страница 28: ......

Страница 29: ......

Страница 30: ...13 December 2021 Main o ce Frico AB Tel 46 31 336 86 00 Industriv gen 41 SE 433 61 S vedalen mailbox frico se Sweden www frico net For latest updated information and information about your local conta...

Отзывы: