Adjustment of the air curtain and airflow 

The direction and speed of the airflow should 

be adjusted considering the load on the 

opening. Pressure forces affect the airstream 

and force it inwards towards the premises 

(when the premises are heated and the 

outdoor air is cold).

The airstream should, therefore, be directed 

outwards to withstand the load. Generally 

speaking, the higher the load, the greater the 

angle required.

 

Basic setting fan speed 

The fan speed when the door is open is 

set using the control. Note that the airflow 

direction and the fan speed may need fine 

adjustment depending on the loading of the 

door.

 

Filter (W) 

The water coil is protected against dirt and 

blockage by an air filter which covers the coil 

face. In environments where the filter needs 

cleaning often, it is advisable to use an external 

intake filter (see accessories pages), which 

provides an easier maintenance, since the unit 

does not need to be opened.

Service, repairs and maintenance  

For all service, repair and maintenance first 

carry out the following:  

1. Disconnect the power supply. 

2. 

The front is locked in the open position with 

the front hatch hook, see fig 1A or removed 

completely, see fig. 1B. The service hatch is 

removed by loosening the screws. 

3. 

After service, repairs and maintenance fasten 

the service hatch and the front. 

Connecting the water coil (W) 

The installation must be carried out by an 

authorised installer.

The water coil has copper tubes with 

aluminium fins and is suitable for connection to 

a closed water heating system. Steel connection 

pipe. The heating coil must not be connected 

to a mains pressure water system or an open 

water system.

Note that the unit shall be preceded by a 

regulating valve, see Frico valve kit. 

The water coil is connected on top of the 

unit (horizontal mounting) or on the reverse 

(vertical mounting) via connections DN20 

(3/4’’), external thread. Flexible hoses are 

available as an accessory, see accessories 

pages.

The connections to the heating coil must be 

equipped with shut off valves (included in Frico 

valve kits) to allow problem free removal.

A vent valve should be connected at a high 

point in the pipe system. Air valves are not 

included. 

For vertical installation and bottom water 

connection it is not possible to bleed the coil 

in the unit. Ensure that the water coil is filled 

with water and that no air remains, prior to 

commissioning. See fig. 4.

 Our recommended solution is to use a 

T-connection and shut off valves. Small air 

bubbles may remain, but will disappear 

with normal operation. NOTE: Care must 

be taken when connecting the pipes. Use a 

pipe wrench or a similar tool to grip the air 

curtain connections to prevent straining of the 

pipes and subsequent water leakage during 

connection to the water supply pipe-work. 

Maintenance 

Unit with water heating 

The appliance filter should be cleaned regularly 

to ensure the air curtain effect and heat 

emission from the device. How often depends 

on local circumstances. A clogged filter is not a 

risk, but the appliance function can fail.  

1. Disconnect the power supply. 

2. 

Remove the screws and raise the front panel. 

The front is locked in open position with the 

front hatch hook. See Fig. 1A.  

3. 

Remove the filter and vacuum clean or wash it. 

If the filter is clogged or damaged, it may need 

to be changed. 

  

All units 

Since fan motors and other components are 

maintenance-free, no maintenance other than 

cleaning is necessary. The level of cleaning can 

vary depending on local conditions. Undertake 

cleaning at least twice a year. Inlet and exhaust 

grilles, impeller and elements can be vacuum 

cleaned or wiped using a damp cloth. Use a 

brush when vacuuming to prevent damaging 

sensitive parts. Avoid the use of strong alkaline 

or acidic cleaning agents. 

Содержание 161049

Страница 1: ...ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program The AM...

Страница 2: ...NA 8 24 4650 82 30 1000 6 0 600V3 24 84 PAEC4025E30 600VNA 10 30 5600 83 38 1173 7 5 600V3 30 106 Type Output 4 kW Airflow 1 m3 h Sound power 2 dB A Motor power W Voltage motor V Amperage motor A Wate...

Страница 3: ...C4000E and PAEC4000A shown herein are licensed to bear the AMCA Seal The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and...

Страница 4: ...NA 27 82 2800 82 30 1000 6 0 600V3 24 185 PAEC4025E30 600VNA 34 102 3300 83 38 1173 7 5 600V3 30 234 Type Output 4 MBH Airflow 1 cfm Sound power 2 dB A Motor power W Voltage motor V Amperage motor A W...

Страница 5: ...00E and PAEC4000A shown herein are licensed to bear the AMCA Seal The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and com...

Страница 6: ...6 6 2 79 9 100 269 2 12 2 PAEC4020W NA max 2855 96 6 95 257 8 5 5 112 3 100 379 5 10 7 PAEC4025W NA max 3090 105 5 95 257 8 6 5 132 1 104 447 0 17 2 1 Recommended outlet air temperature for good comfo...

Страница 7: ...s EN Les pages de pr sentation contiennent principalement des images Pour la traduction des textes en anglais consultez la page correspondante la langue souhait e Las p ginas introductorias contienen...

Страница 8: ...80 Q 36 1 44 R 1572 62 88 PAEC4015x S 2062 82 48 PAEC4020x T 2572 102 88 PAEC4025x U 1515 60 60 PAEC4015x V 2004 80 16 PAEC4020x W 2515 100 60 PAEC4025x X 23 0 92 Y 40 1 60 Z 611 24 44 611 L 295 36 40...

Страница 9: ...position with the front hatch hook Fig 2 Control card SIRe is integrated in the air curtain at delivery SIRe Fig 1B When the front has been removed it it important to be sure it is firmly seated in th...

Страница 10: ...PAEC4015x PAEC4020x PAEC4025x Ref Metric mm Imperial in Product type A 127 5 08 PAEC4010 15 20 25x B 102 4 08 PAEC4010 15 20 25x C 235 9 40 PAEC4010 15 20 25x D 750 30 00 PAEC4010x E 1260 50 40 PAEC40...

Страница 11: ...15x 2 pcs 400 15 75 Fig 6 PA34WB20 PAEC4020x 3 pcs 400 15 75 Fig 6 PA34WB30 PAEC4025x 4 pcs 400 15 75 Fig 6 PAWBL15 PAEC4015x 2 pcs 560 22 05 Fig 6 PAWBL20 PAEC4020x 3 pcs 560 22 05 Fig 6 PAWBL30 PAEC...

Страница 12: ...tric Length Imperial PA34CB15 PAEC4010 15x 4 pcs PA34CB20 PAEC4020x 6 pcs PA34CB30 PAEC4025x 8 pcs PA34WS15 PAEC4010 15x 4 pcs 3 m 9 8 ft PA34WS20 PAEC4020x 6 pcs 3 m 9 8 ft PA34WS30 PAEC4025x 8 pcs 3...

Страница 13: ...24x2516 3 48x16 96x100 64 Type Product type Length Metric mm Length Imperial in PA4XT10 PAEC4010x 130 200 5 20 8 00 PA4XT15 PAEC4015x 130 200 5 20 8 00 PA4XT20 PAEC4020x 130 200 5 20 8 00 PA4XT25 PAEC...

Страница 14: ...PAEC4000 14 Accessories Note The air curtain must be secured in the wall or ceiling Fig 11 See separate manual for PA4JK PA4VDW PA4JK...

Страница 15: ...000 PA4HEVDW PAEC4000 AXP300 PAEC4000 Accessories Type Product type Length Metric Length Imperial PA34EF10 PAEC4010W PA34EF15 PAEC4025W PA34EF20 PAEC4020W PA34EF25 PAEC4025W DTV200S PAEC4000W FHDN20 P...

Страница 16: ...0 m 32 8 ft SIReCC615 15 m 49 2 ft SIReCC640 40 m 131 2 ft SIReCC403 3 m 9 8 ft SIReCC405 5 m 16 4 ft SIReCC410 10 m 32 8 ft SIReCC415 15 m 49 2 ft Accessories SIReACY SIReAAY SIReRTX SIReWTA SIReCC S...

Страница 17: ...H1 H2 N Id SIRe B1EC Room C2 C1 Actuator 230V Supply 230V PE L N Heating L N L Trafo Motor protection 0 10V GND PWM L N Motor Internal sensor M M M M 4010WA 4025WA 4020WA 4015WA 208V1 PE L1 L2 AREC400...

Страница 18: ...EC Room C2 C1 Actuator 230V Supply 230V PE L N Heating L N L Trafo K2 K1 4010E 4015E 4010E 4015E TS1 TS2 Motor protection 0 10V GND PWM L N Motor Internal sensor M M M M L1 L2 L3 L1 K2 L2 K2 L3 K2 L1...

Страница 19: ...Trafo K 2 K 1 K 2 K 1 4020E 4025E 2 X 208V3 TS 2 TS 1 Moto r p rotec tio n 0 10 V GND P WM L N Moto r Inte rna l se n so r M M M M 208V3 L1L2 L3 4025E 4020E 4020 6 motors 4025 7 motors L1 K 2 L2 K 2...

Страница 20: ...oom C2 C1 A ctuato r 230V S upply230V PE L N He ating L N L Trafo K 2 K 1 4010E 4015E TS1 TS2 Motor protec tio n L N Motor Internal sensor M M M M 6 0 0 48 0V 230V Transformer 2 x 10A FUSE L1 L2 L3 2...

Страница 21: ...0V PE L N Heating L N L Trafo K2 K1 K2 K1 4025E 4020E 4020E 4025E 2 X 600V3 480V3 TS2 TS1 TS3 TS4 Motor p rotection 0 10V GND PWM L N Motor Internal sensor M M M M 600V3 480V3 600 480V 230V Transforme...

Страница 22: ...les Veuillez vous assurer que la tension d alimentation de l unit correspond la tension de secteur locale La tension d alimentation de l unit et les calibres maximums sont indiqu s sur l tiquette de d...

Страница 23: ...ountings is available for both wall and ceiling installations se accessories pages Mounting with wall brackets 1 Remove the plastic covers on the wall brackets Fig 6A 2 Mount the brackets on the wall...

Страница 24: ...d control card see fig 2 SIRe is supplied pre programmed with quick fit connections Modular cables are connected to the control board See manual for SIRe Unit without heating or with water heating Con...

Страница 25: ...top of the unit horizontal mounting or on the reverse vertical mounting via connections DN20 3 4 external thread Flexible hoses are available as an accessory see accessories pages The connections to...

Страница 26: ...nce is connected this may be due to moisture in the heating element When an appliance containing a heater element has not been used for a long period or stored in a damp environment moisture can enter...

Страница 27: ...3 years and less than 8 years shall only switch on off the appliance provided that it has been placed or installed in its intended normal operating position and they have been given supervision or ins...

Страница 28: ......

Страница 29: ......

Страница 30: ...13 December 2021 Main o ce Frico AB Tel 46 31 336 86 00 Industriv gen 41 SE 433 61 S vedalen mailbox frico se Sweden www frico net For latest updated information and information about your local conta...

Отзывы: