S90-010 CS (APR 08) FRICK
®
QUANTUM™ COMPRESSOR CONTROL PANEL
Page 22 COMMUNICATIONS SETUP
RETURN DATA VALUE FROM TABLE $IDT1
$
Start of command sequence.
ID
Compressor ID code.
T1
Return the value of a Table address.
0000 0000
0000 0000
0000 0000
0000 0000
0000 0000
0000 0000
0000 0000
0000 0000
Frick
®
Address(s) of data value in Table. Up
to 16 different addresses can be requested.
Example # 1: if requesting Suction
Temperature only, command would be (to
compressor ID of 1);
$01T10128CSCR
.
Example # 2: If requesting address 128
through 136, the command would be
$01T101280129013001310132013301340
1350136CSCR
.
CS
Checksum
CR
Carriage Return
RETURNED ANSWER
,
Starting
Character
Position
Description
of returned data
1
A
Acknowledge
2
01
Compressor ID code.
4
Value(s) of requested data.
CS (Checksum followed by CR, LF)
The response to example # 1 above would
look like:
A01+000018731F
, the plus
symbol (+) indicates that the data value
returned is positive.
The response to example # 2 above would
look like:
A01+000000
05652-000013354
+00000288109
CHANGE SETPOINT COMMAND: $IDCS
$
Start of command sequence.
ID
Compressor ID code.
CS
Change Table address’s setpoint value.
0000 Frick
®
’s Table address of the setpoint.
+/-
Polarity indicator (for the new setpoint).
0000 0000 Value of the new setpoint. Decimal point
assumed to two places (0000 00.00)
CS
Checksum
CR
Carriage Return
RETURNED ANSWER
,
A
followed by the
ID
,
and 1
CR
,
LF
if successful.
and 0
CR
,
LF
if unsuccessful.
CLEAR ALARMS COMMAND: $IDCA
followed by the
CS
,
CR
RETURNED ANSWER
,
A
followed by the
ID
,
CR
,
LF
if successful.
NOTE: The following commands are for remote
control of a compressor. A compressor should be in
both remote compressor mode and remote Slide Valve
or capacity mode for remote control.
COMPRESSOR START COMMAND: $IDCT
followed by the
CS
,
CR
RETURNED ANSWER
, A followed by the ID,
CR
,
LF
if successful.
COMPRESSOR STOP COMMAND: $IDCP
followed by the
CS
,
CR
RETURNED ANSWER
,
A
followed by the
ID
,
CR
,
LF
if successful.
SLIDE VALVE CONTROL COMMANDS: $IDCLXX
$IDCUXX
$
Start command sequence.
ID
Compressor ID code.
C
Slide Valve/Slide Stop command.
L
Load Slide Valve command.
U
Unload Slide Valve command.
XX = 00
Turns selected output off.
XX=01 to 15
Turns selected output on for XX seconds.
If the command is $01CL00, then the load Slide Valve
output on compressor #1 would be turned off. If the
command is $01CL05, then the load Slide Valve output
on compressor #1 would be turned on for 5 seconds,
and would then automatically turn off. Time is not
accrued, each command restarts timer.
NOTE:
the
Slide Valve must be in the remote mode for this
command to be executed.
RETURNED ANSWER (for L or U commands): A01
Character
Position
Description of returned data
1
Acknowledge of command sent.
2,3
ID code of compressor. (CR, line feed.)
COMPRESSOR MODE - MANUAL COMMAND: $IDMM
followed by the
CS
,
CR
RETURNED ANSWER
,
A
followed by the
ID
,
CR
,
LF
if successful.
COMPRESSOR MODE - AUTOCYCLE COMMAND:
$IDMA
followed by the
CS
,
CR
RETURNED ANSWER
,
A
followed by the
ID
,
CR
,
LF
if successful.
COMPRESSOR MODE - REMOTE COMMAND: $IDMR
followed by the
CS
,
CR
RETURNED ANSWER
,
A
followed by the
ID
,
CR
,
LF
if successful.
SLIDE VALVE MODE - AUTOMATIC COMMAND:
$IDVA
followed by the
CS
,
CR
RETURNED ANSWER
,
A
followed by the
ID
,
CR
,
LF
if successful.
SLIDE VALVE MODE - REMOTE COMMAND: $IDVR
followed by the
CS
,
CR
RETURNED ANSWER
,
A
followed by the
ID
,
CR
,
LF
if successful.
COMPRESSOR SEQUENCE - ACTIVATE
COMMAND: $IDS2
followed by the
CS
,
CR
RETURNED ANSWER
,
A
followed by the
ID
,
CR
,
LF
if successful.
COMPRESSOR SEQUENCE – DE-ACTIVATE
COMMAND: $IDS3
followed by the
CS
, CR
RETURNED ANSWER
,
A
followed by the
ID
,
CR
,
LF
if successful.