Frick IDSC / ECOSS Series Скачать руководство пользователя страница 16

140.010-IOM (APR 2018)

Page 16

IDSC/ECOSS

 EVAPORATIVE CONDENSERS

MAINTENANCE

ü

  Heavier moisture or greasy dirt must be removed with a 

high-pressure water jet (max. 725 psi pressure), steam 
pressure jet (max. 725 psig pressure), minimum 8 inches  
away with a flat jet nozzle, or using a neutral cleaning 
agent where applicable. 

NOTE:

o  With oily and greasy dirt it helps to add a cleaning 

agent to the water.

o  Cleaning should be done from inside to the outside 

(always opposing the dirt onset) and from top to bot-
tom.

o  Continue cleaning until all dirt has been removed.

WATER TREATMENT

WATER TREATMENT AND MINIMUM WATER 
QUALITY REQUIREMENTS

Biological Control

With the inlet louvers structure of the side coverings, which 
effectively shut out the sunlight and the double inclination 
of the basin for complete drainage, it is ensured that there 
will be minimal biological growth in the basin.

Chemical treatment

For necessary measures to maintain the prescribed limit 
values (see Table "Recirculated Water Quality Guidelines), 
please contact your local water treatment specialist. 

Recirculated Water Quality Guidelines

Property

Recommended Value

304L SST

316L SST

(Std. Tube Material)

Total Bacteria 

(cfu/ml)

< 1,000

pH (90

°

F)

6.0 - 9.0

Chlorides as Cl

< 250 ppm

< 400 ppm

Sulfates as SO

4

2-

< 250 ppm

Silica

< 150 ppm

Hardness

< 500 ppm (as CaCO

3

)

Alkalinity

< 600 ppm (as CaCO

3

)

Total Dissolved 

Solids

< 1,500 ppm

Total Suspended 

Solids

< 40 ppm

Conductivity

< 3,000 (micromhos)

Free Chlorine

< 1.0 ppm

< 2.0 ppm

NOTES:

1. The water quality guidelines listed above are for clean 

surfaces. Proper and periodic equipment maintenance is 

required to prevent tube fouling, surface deposit(s), scale, 

microbial deposit(s), etc. which in turn can reduce the range 

of the guidelines provided above.
2. Water distribution nozzles are to be kept clean at all times 

to ensure complete wetting of the coil. Failure to do so will 

result in warranty being voided.
3. Only Non-Chlorinated Biocides should be used for biologi-

cal control.
4. Anaerobic dip slide: Sessile bacteria sampling must be 

conducted along with bulk water (planktonic) sampling.

Water Treatment Guidelines:

Water related problems that typically occur in an evaporative 
condenser can be broadly classified as:

• 

Scale Deposits

• Corrosion
• 

Microbiological Fouling

Scale deposits are a serious concern in evaporative heat 
transfer products. When dissolved solids become overly 
concentrated, an adherent deposit termed "scale" will form 
on the tubes of the heat exchanger, severely impacting the 
thermal performance of the heat exchanger. Evaporative 
cooled deposits may also include dust scrubbed from the 
air, corrosion byproducts and microbiological contaminants 
(slime). Regardless of the source, the end result is reduced 
thermal performance, increased operating costs and eventu-
ally, equipment failure.

Corrosion in water is usually an electrochemical reaction 
initiated by the presence of naturally occurring impurities in 
water or microbiological growth. Corrosion is the destructive 
reaction of a metal with its immediate environment, resulting 
in metal loss and ultimately equipment failure. 

Metal corrosion occurs as a result of galvanic action at a 
negatively charged pole, or site on the metal surface. Both 
anodes and cathodes can be created on metal surfaces due 
to impurities in the metal, localized stress, metal grain size 
or composition differences. The difference in charges be-
tween anodes and cathodes creates an electrical potential 
between them which results in an electrical charge flowing 
from anodes to cathodes, using the surrounding water was 
a conductor. General corrosion is wide spread and normally 
caused by impurities in the metal or characteristics of the 
metal or its environment that results in an overall fouling of 
the metal surface. Localized corrosion results from stress or 
localized environment. 

Having a consistent maintenance program in place and 
maintaining the equipment in a clean state all ascribe to the 
longevity of IDSC/ECOSS units. 

Microbiological fouling results from bacteria, fungi, zooplank-
ton and algae introduced into the system through makeup 
water  or  filtered  from  the  air.  Fouling  results  when  these 
microorganisms grow in open systems rich in oxygen and 
form slime on the surfaces of the equipment. Slime is an 
aggregate of both biological and non-biological materials. 

The best method of controlling biological fouling in evapora-
tive units is to keep them clean. At least twice during the 
cooling season, the unit should be drained, scrubbed clean 
and allowed to dry fully before refilling. Thereafter, a chemical 
treatment will complete the process. 

Uncontrolled microbiological fouling can cause major corro-
sion and deposit problems in evaporative units. Microbials in 
condenser water systems can become resistant to a single 
method of treatment, therefore it is recommended that both 

Содержание IDSC / ECOSS Series

Страница 1: ...10 IOM OCT 2017 Dist 3 3a 3b 3c THIS MANUAL CONTAINS RIGGING ASSEMBLY START UP AND MAINTENANCE INSTRUCTIONS READ THOROUGHLY BEFORE BEGINNING INSTALLATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESUL...

Страница 2: ...Johnson Controls Frick makes no commitment to update or provide current information automatically to the manual owner that information if applicable can be obtained by contacting the nearest Frick Fac...

Страница 3: ...reatment Guidelines 16 TROUBLESHOOTING 17 SERVICE 17 TROUBLESHOOTING TABLE 17 APPENDIX I 1 GENERAL INFORMATION 18 1 1 RESPONSIBILITIES 18 1 2 LEGAL NOTES 18 1 3 OPERATING INSTRUCTIONS 19 1 3 1 Scope 1...

Страница 4: ...ty information please refer to Appendix I 2 Safety INFORMATION ON COMPONENT PARTS For safety information see Appendix I 3 Information on component parts CASING COIL BASIN WATER SYSTEM All Frick IDSC E...

Страница 5: ...r and over temperature protection real time diagnostics measured process value motor speed operating hours power consumption and motor temperatures lower EC motor temperature rise at reduced speed res...

Страница 6: ...sin at 40 F The design temperature of 40 F has been determined with the fans being off and options are available for ambient temperatures of 20 F Factory installed electrical contactors and wiring are...

Страница 7: ...I beams must be level to within 1 8 over a 6 span Shims cannot be used to level the unit as this will compromise the load bearing surface Mounting holes 13 16 diameter are provided at the base of the...

Страница 8: ...the support structure for bolt hole locations see unit certified drawing o Make sure that all mounting bolts are tightened equally to achieve a load distribution on the connections that is as balanced...

Страница 9: ...tions 10 WIDE UNITS 12 WIDE UNITS 18 LONG UNITS 12 LONG UNITS 60 120 0 10 48 106 3 8 10 3 138 2 11 6 2 120 0 10 113 9 9 5 9 51 109 0 9 1 120 0 10 120 0 10 49 Appropriately guiding the top section safe...

Страница 10: ...nger of damage to the system s cooling equipment see Appendix I 5 1 Safety instructions Damage to the system s cooling equipment NOTICE Danger of corrosion and dirt build up for units using ammonia as...

Страница 11: ...mes o Ensure that sufficient space is provided for mainte nance o Ensure that all liquid carrying components connection lines and all electrical connections and lines are easy to access o Ensure that...

Страница 12: ...connec tions the arrangement of the fittings and the ability to operate Check and retighten all threaded connections especially on the fans Check installation of pipe connections Check support of ref...

Страница 13: ...out with appropriate media and at the appropri ate test pressure Put the unit into operation see section 5 9 Putting the unit into operation for the first time PUTTING THE UNIT INTO OPERATION FOR THE...

Страница 14: ...ing and sanitizing the water distribution system sprinkler X X Basin cleaning and sanitizing X X Cleaning and sanitizing the side top and bottom panel enclosures fairings X X X Cleaning and sanitizing...

Страница 15: ...ng than under greasing If the bearing has a vent cap remove the cap and run pump for 30 minutes before reinstalling cap This allows excess grease to work its way out of the bearing Electrical motor Ch...

Страница 16: ...sfer products When dissolved solids become overly concentrated an adherent deposit termed scale will form on the tubes of the heat exchanger severely impacting the thermal performance of the heat exch...

Страница 17: ...aintenance schedule The water treatment program must be compatible with the unit s construction materials In systems with mixed metallurgy the water treatment expert must devise a program to ensure ad...

Страница 18: ...ational disrup tions a warning system which immediately signals all faults must be provided on site Prepare emergency measures that prevent consequential damage for people and property should faults o...

Страница 19: ...or otherwise injured with non com pliance Warns against hot surfaces The temperature is over 110 F protein clotting and can cause burns Warns against dangerous electrical voltage Danger of an electric...

Страница 20: ...g refrigerant liquid or vapor from the heat exchanger or pipe components o Sudden large release release and evaporation of the greater part of the entire refrigerant filling in a short time e g in les...

Страница 21: ...temperature Fan kW Air inlet bulb temperature The specified operating point is provided in the order related documents Operating Conditions The unit is a component of a cooling system including its re...

Страница 22: ...aces or clothing parts Do not operate fans without guard grille Pinch trap point hazard With automatic fan start during mainte nance work there is a danger of pinching trapping for the hands and finge...

Страница 23: ...ntrations Please ensure that the halocarbon refrigerant leaking from the unit cannot penetrate the interior of the building or put people at risk in any other way Halocarbon refrigerant vapor or gas m...

Страница 24: ...al Ensure that the maximum permissible limit values in the setup room are not exceeded Monitor the ammonia concentration in the ambient air with detectors and alarm devices Frostbite hazard Leaks in t...

Страница 25: ...ctrical components connections and cables no recognizable identifiers on the pipes and insufficient space for tests With ammonia units defective installation may also result in hazards caused by under...

Страница 26: ...il heat exchangers fans must be disposed of properly as specified Used refrigerant that is not determined for reuse must be treated as waste and safely disposed of There must be no emissions into the...

Страница 27: ...e unit is intended for outdoor use only To protect the unit from damage due to the elements the unit should be stored in a clean dry location and away from areas with excessive traffic The unit should...

Страница 28: ...d dirt may not get into the unit s in terior If humidity or dirt gets into the unit s interior fittings and other components of the refrigeration installation can be damaged Protect the unit against d...

Страница 29: ...not exercise any forces upon the distribution and header points This can cause leaks on the refrigerant connection points of the unit and on connection points of the on site pipe laying Ensure that R...

Страница 30: ...ICE For unit shutdown consider the maximum operating pressure If necessary take precautions so that it cannot be exceeded NOTICE With shutdown times of a month or longer energize the fans for approxim...

Страница 31: ...at can involve ignition sources ex grinding welding soldering etc With all work involving ignition sources ex grinding welding soldering etc in the work area keep suitable fire extinguishing equipment...

Страница 32: ...still under effervescence has a temperature of 28 F Contact with refrigerant under effervescence caused by spraying causes frostbite Use eye protection Use hand protection Ensure that the unit in ques...

Страница 33: ...this point in service life 6 6 CLEAN UNIT 6 6 1 General NOTICE If during maintenance or cleaning any corrosion is be ing detected please contact the manufacturer directly 6 6 2 Cleaning coil casing a...

Страница 34: ...ways be dependent on the loca tion wet bulb temperature and the heat load There are two methods to control the blow down bleed rate 1 Constant Blow Down manually setting the bleed regu lating valve at...

Страница 35: ...uate 13 Explosion hazard 24 eye protection 30 F fan blades 12 15 21 fan capacity 21 fan motor bearing 15 fan motor drives 13 fan motors 5 fans 25 Fans 27 fire extinguishing equipment 30 fittings 12 fl...

Страница 36: ...f device 27 system installer 17 T TEFC motor 6 terminal box 27 thermostat 6 threaded connections 12 U Unstable oils 27 V vaporous ammonia 23 variable motor speed 5 vent cap 15 ventilation system 11 vi...

Отзывы: