STEP 4 : UV Warning Sticker & Safety Sight Glass

1. Find a suitable location on the outside of the duct-work 

near the UV Lamp installation and apply the Fresh-Aire UV® 

warning/lamp replacement sticker

2. Drill a ½” hole through the circle on the sticker.  

Press the Sight Glass 

I

 into hole.

3. Turn on the power and use the sight glass to confirm that the 

UV Lamp is operating.

Lamp Replacement

Germicidal UV lamps need to be replaced 

periodically. Systems will include one-year, 

two-year, or three-year UVC lamp(s). 

Note: 

UV lamps will continue to emit visible 

light but they lose germicidal effectiveness 

over time. 

Note: Use of replacement UV lamps other than Fresh-Aire UV® voids warranty.

© Fresh-Aire UV®        LIT-FAUV-BTX-MAN 022122

DISCONNECT

L1-BLACK
L2 or N-WHITE
GND-GREEN

UV LAMP

BLUE CABLE

TUVP-ST

110-277 VAC

POWER SUPPLY

STEP 3: Power Supply & Electrical

IMPORTANT!

 Check which power supply is 

included with your Blue-Tube UV-X before 

connecting to power. Turn off main power source 

before installation.
1. Find a suitable location for the power supply 

inside the control panel of the air handler. 

Install using the self-tapping screws.

2. Use the wiring diagrams to connect to power.  

 

The low-voltage power supply connects to the 

air system’s 24 VAC transformer (or add a 24 

VAC transformer as needed). 

 

Line-voltage power supplies connect directly 

to 120-277 VAC power. 

STEP 3: Power Supply & Electrical Cont.

ST (line-voltage) wiring

IMPORTANT! Must be wired to constant power - do not connect to blower relay.

ER (low-voltage) models wiring

AIR HANDLER

24 VAC

TRANSFORMER

TUVP-ER

18-32 VAC

POWER SUPPLY

UV LAMP

BLUE CABLE

BLACK

RED

IMPORTANT! 

Systems with high 24 VAC loads may require the installation of a separate 24 VAC 

transformer to power the UV light.
Always use a separate 24 VAC transformer with “communicating” air systems.
Draws 20 VA, may need to do load calculation: Volts under load 

X

 Amps under load.

CAUTION! 

UV lamps contain small amounts of mercury  

Dispose of lamps in accordance with local environmental regulations. 

For more information visit www.lamprecycle.org

WWW.FRESHAIREUV.COM

PART: TUVL-315   LIFE: 3 Year

Important:

 some materials inside 

the air system (including filter 

media, flex duct, wiring etc.) may 

not be UV light resistant. Use the 

optional UV shield (part #TUV-

SHIELD-LPC) or cover the materials 

with reflective tape.

Typical UV lamp locations

Surface Mount

1. Determine the optimal position for placement of the UV lamp.
2. Use a utility knife to cut a slit in the insulation on the interior surface.
3. Place the magnetic mounting bracket directly on the metal surface or 

remove the magnet and hard-mount the bracket using the self-tapping 

screws provided. Use foil tape to close the cut in the insulation.

“ER” Power Supply LED functions

LEDs are visible through the translucent Power Supply housing.
1. Confirm LED Switch is in left position to enable LED indicators.  
2. Blue LED indicates normal operation.
3. Red LED indicates lamp fault
4. No LEDs indicates no power.

STEP 2: UV Lamp Installation

1. 

2. 

3. 

LED Switch