FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
- 22 -
U01.05
Code of previous fault
Same as U01.00
0
⊙
U01.06
Running frequency
when previous fault
occurred
0.00
~
Fu
0.00Hz
⊙
U01.07
Output current when
previous fault occurred
0.0
~
3000.0A
0.0A
⊙
U01.08
Bus voltage when
previous fault occurred
0
~
1200V
0V
⊙
U01.09
Cumulative running time
when previous fault
occurred
0
~
65535h
0h
⊙
U01.10
Before-previous fault
code
Same as U01.00
0
⊙
U01.11
Running frequency
when before-previous
fault occurred
0.00
~
Fu
0.00Hz
⊙
U01.12
Output current when
before-previous fault
occurred
0.0
~
3000.0A
0.0A
⊙
U01.13
Bus voltage when
before-previous fault
occurred
0
~
1200V
0V
⊙
U01.14
Cumulative running time
when before-previous
fault occurred
0
~
65535h
0h
⊙
H00 group: multi-pumps constant pressure water supply
H00.00
Special purpose
inverter function enable
0: Invalid
0
×
1: Valid
H00.01
Work modes selection
0: fixed variable-frequency
pumps mode
1: 2 variable-frequency pumps
cycle mode
0
×
H00.02
Frequency for add
pumps
Frequency for reduce
pumps~max frequency
50.00Hz
△
H00.03
Frequency for reduce
pumps
0.00Hz
~
frequency for add
pumps
5.00Hz
△
H00.04
Pressure tolerance for
add pumps
0.0
~
100.0%
0.0%
△
H00.05
Pressure tolerance for
reduce pumps
0.0
~
100.0%
0.0%
△
H00.06
Added pumps delay
0.0
~
300.0s
20.0s
△
H00.07
Reduced pumps delay 0.0
~
300.0s
15.0s
△
H00.08
Time for added pumps
speed arrival max
0.0
~
300.0s
1.0s
△
H00.09
Time for reduced
pumps zero-flow
0.0
~
300.0s
1.0s
△
H00.10
Switching time
0.1
~
10.0s
1.0s
×
H00.11
Pumps Status
Unit: No.1 pump status
0:Spare
1:Enable
Decade: No.2 pump status(same
with unit)
Hundreds: No.3 pump
status(same with unit)
Kilobit: No.4 pump status(same
with unit)
00011
△