FR200H Special Purpose Inverters for Multi-pumps Constant Pressure Water Supply
- 17 -
loss (Err19) (Same as unit's
place)
Ten thousand's digit: Continuous
running time reached (Err20)
(Same as unit's place)
F11.12
Protection action 3
Unit's place: Module temperature
detection disconnection
(
Err24)
00030
×
0: Fault reported and coast to
stop
1: Stop according to the stop
mode
2: Fault reported but continue to
run
Ten's digit: Load becoming 0
(Err25) (Same as unit's place)
Hundred's digit:reserved
thousand's digit:reserved
Ten thousand's digit:reserved
F11.14
Frequency selection for
continuing to run upon
fault
0: Current running frequency
1
×
1: Set frequency
2: Frequency upper limit
3: Frequency lower limit
4: Backup frequency upon
abnormality
F11.15
Backup frequency upon
abnormality
0.00
~
Fmax
0.00Hz
×
F11.17
Motor overload
protection time
30.0
~
300.0s
60.0s
×
F11.18
Overload alarm
Unit's place: detection option:
000
×
0: Always detect
1: Detect at constant speed only
Ten's digit :compared object
0: Rated current of motor
1: Rated current of drive
Hundred’s digit:report error or not
0:Do not report
1:Report
F11.19
Overload alarm
threshold
20.0
~
200.0%
130.0%
×
F11.20
Overload alarm
activated time that
exceeding threshold
0.1
~
60.0s
5.0s
×
F11.21
Inverter overheat
warning threshold
50
~
overheatTemperature
Model
defined
×
F11.22
Detection level of power
loss
5.0
~
100.0%
20.0%
×
F11.23
Detection time of power
loss
0.1
~
60.0s
5.0s
×
F11.24
Action selection at
instantaneous power
failure
0: Disabled
0
×
1: Enabled
F11.25
Decel time at
instantaneous power
failure
0.0
~
6000.0s
5.0s
△
F11.26
Rapid current limit
0: Disabled
0
×
1: Enabled
F11.27
Times of automatic
0
~
20
0
×