Install Pressure/Vacuum Foam Tank Vent

A pressure/vacuum foam tank vent is supplied for use on sealed foam tanks. The 

recommended location to mount the vent is in the cover of the foam tank fill tower. If 

there is no fill tower, mount the vent at the highest point of the tank top so that it is not 

immersed in foam. For installations where clearance above the fill tower is limited, a 

90° mounted vent is available.

Note:

 The vent can compensate for a maximum foam concentrate flow rate 

of 60 GPM. If the flow rate of foam concentrate from the tank will exceed 

60 GPM, two (2) vents will be required. 

Install Top Mounted Tank Vent

The top mounted tank vent is mounted in a vertical position through a 1 1/8-inch 

hole on the lid of the fill tower and is secured by a hand tightened nut.

Note:

 The tank vent must be in a vertical position and can not be immersed 

in foam. 

1.  Measure and mark mounting location for vent. Make sure there is clearance 

for the valve before drilling hole. Refer to Figure 4 for dimensions.

2.  Drill 1 1/8-inch diameter hole. 
3.  Insert vent into the hole with the gasket in place.
4.  Screw on nut and hand tighten.

Install 90° Mounted Tank Vent

The 90° mounted tank vent is mounted on a vertical side of the fill tower. It must 

be located as close to the top of the fill tower as possible. The vent is held in place with 

with two (2) 1/4-20 x 3-inch bolts, washers, and locknuts.

Note:

 The tank vent must be in a vertical position and can not be immersed 

in foam. 

1.  Measure and mark mounting location for vent. Make sure there is clearance 

for the valve before drilling holes. Refer to Figure 4 for dimensions.

2.  Drill 3/4-inch diameter hole and two through holes for 1/4-20 bolts. 
3.  Apply sealant to mounting surfaces and bolt holes. 
4.  Secure vent in place with two bolts, washers, and locknuts.

Содержание TankVision WLA200

Страница 1: ...70 CLASS B FOAM CONCENTRATE TANKS Document Number XE WLA2PM R0A PRIMARY and REMOTE DISPLAYS HORIZONTAL OPTION MAXVISION LED TANK DISPLAY CAB MINIATURES FIRE RESEARCH CORPORATION www fireresearch com 2...

Страница 2: ...re Vacuum Foam Tank Vent 12 Install MaxVision LED Tank Display 14 Program MaxVision LED Tank Display 14 Install Remote Light Driver 16 Install Buzzer 16 OPERATION 17 Options 17 CALIBRATION 18 Overview...

Страница 3: ...gure 5 MaxVision LED Display Mounting Dimensions 15 Figure 6 Remote Light Driver 16 Figure 7 Diagnostics Faults 22 Figure 7 Diagnostics Warnings 23 Figure 8 Primary Display Wiring 24 Figure 9 Remote C...

Страница 4: ...ly read from all line of sight angles for a full 180 degrees The pressure vacuum foam tank vent is supplied for use on foam concentrate storage tanks These tanks should remain closed to the atmosphere...

Страница 5: ...mic Diaphragm Pressure Range 0 5 PSI Maximum Tank Height 10 Feet Excitation Voltage 5 VDC Pressure Vacuum Foam Tank Vent Material PVC and Aluminum with Delrin Valves Relief Pressure 0 01 PSI Maximum F...

Страница 6: ...Foam Fill FFA100 and Auto Tank ATA400 systems These require special programs for the correct controlling output on display connector pin 5 Cab Miniature Display Optional The cab miniature display has...

Страница 7: ...ut on a two wire datalink and input to the LED light to show the volume of liquid in the tank The display shows the level in 1 8 tank increments It has a photo sensor that adjust brightness for day or...

Страница 8: ...re there is clearance behind the panel for the display and cables before cutting holes Refer to Figure 1 for layout and dimensions 2 Cut out a 4 by 2 1 8 inch hole and drill four 4 holes clearance or...

Страница 9: ...Dimensions 5 8 1 1 2 1 3 16 1 9 16 Drill a clearance hole for 3 8 threads 2 3 4 3 4 Figure 2 Cab Miniature Display Mounting Dimensions 2 2 1 2 2 1 2 1 1 2 4 3 8 2 1 2 3 3 1 2 2 1 8 1 3 4 3 1 2 4 1 1...

Страница 10: ...rance for sensor and cable before drilling hole Refer to Figure 3 for dimensions 2 Drill and tap a 1 4 NPT hole 3 Apply sealant around base and threads of pressure sensor 4 Screw sensor into hole 5 Co...

Страница 11: ...ical Pressure Sensor Location Typical Tank 1 2 NPS 2 Mount sensor approximately 2 from bottom of tank Note The sensor can be mounted vertically on a 90 fitting in cold areas to help prevent water free...

Страница 12: ...he tank vent must be in a vertical position and can not be immersed in foam 1 Measure and mark mounting location for vent Make sure there is clearance for the valve before drilling hole Refer to Figur...

Страница 13: ...lts 3 4 Dia 2 5 8 Figure 4 Pressure Vacuum Foam Tank Vent Note The tank vent must be mounted in a vertical position The vent can not be immersed in foam If there is no fill tower mount the vent at the...

Страница 14: ...datalink requires two terminating resistors a TankVision display always has one One TankVision with one or two LED displays Install resistor at farthest light Two TankVision displays Do not install t...

Страница 15: ...4 6 5 8 6 5 8 7 8 7 8 7 8 1 7 8 Front View Side View Rear View Three locations are available for the wires to exit the rubber gasket Drain Notch Figure 5 MaxVision LED Display Mounting Dimensions Mou...

Страница 16: ...d cable before drilling holes Refer to Figure 5 for dimensions 2 Drill and tap two 10 32 holes 3 Secure remote light driver with two screws 4 Connect cable and wires Refer to Wiring section Install Bu...

Страница 17: ...r display Cab Miniature Display All 5 LEDs is on when the tank is full The LEDs will show full 3 4 1 2 1 4 and empty tank MaxVision LED Display The LED display repeats exactly what is shown on the mas...

Страница 18: ...used for any shape or size tank This procedure must to be used for irregular shape tanks e g T shape oval elliptical tank with through hole etc The program compares the pressure in the tank as the tan...

Страница 19: ...e display module 3 Swipe the magnet three times to enter the calibration mode Result Top three display LEDs flash on and off Note Once the calibration process is activated the flow rate of liquid into...

Страница 20: ...the calibration program terminates no program data is changed 1 Fill the tank Do not fill up into the fill tower 2 Apply power to the display module Note Once the calibration program is activated the...

Страница 21: ...op eight display LEDs go on the calibration program terminates no program data is changed 1 Fill the tank Do not fill up into the fill tower 2 Apply power to the display module Note Once the calibrati...

Страница 22: ...ressure Sensor high output voltage voltage 4 6V Shorted wire on sensor cable Pressure Sensor or Primary Display Failure Checksum Error Primary Display Failure Top 2 3 Bottom 2 3 LEDs Alternately Flash...

Страница 23: ...ltage from the Pressure Sensor is more than 0 5V above calibrated full tank voltage Top 2 and Bottom 2 LEDs Blink ON and OFF Top and Bottom LEDs Blink ON and OFF The difference in voltage from the Pre...

Страница 24: ...ch Plug DTM06 8S Primary Display Module To Pressure Sensor Power Figure 8 Primary Display Wiring Note When the TankVision primary is used to control a remote valve Foam Fill or Auto Tank system pin 5...

Страница 25: ...nnector and a butt connector on the other to connect to customer provided wire is provided with the Cab Miniature Display Wires can be routed from top middle or bottom feed through The datalink requir...

Страница 26: ...ied together The maximum current is 20 AMPS 12VDC 10 AMPS 24 VDC 1 4 5 8 Figure 10 Remote Light Driver Wiring Light Driver Connector Pin Signal Description 1 Ground 2 Signal Input 3 Remote Light Power...

Страница 27: ...An unlimited number of remote displays can be connected Any remote display can become a primary by disconnecting the sensor from the primary and connecting it to the remote To Other Miniature Displays...

Страница 28: ...sure and vacuum valves are easily accessed and disassembled for periodic cleaning or inspections Unscrew the cap from the main body and lift the valves out of the center cavity Clean all parts with wa...

Страница 29: ...splay Module Class B Foam 2 XE WL200S CXXA Primary Display Cable XX Length 3 XE WL200R CXXA Remote Display Cable XX Length 4 XE WLPT4 S Pressure Sensor 5 XE WL20A A Thin Wall Adapter Kit 6 XE WL400 A...

Страница 30: ...WLA200 Rev140407 30 NOTES...

Страница 31: ...WLA200 Rev140407 31 NOTES...

Страница 32: ...WLA200 Rev140407 32...

Отзывы: