TGA100 Rev0106
19
Preliminary Set-up
This procedure can be performed prior to installing the INControl on the apparatus.
Connect 12 volt power as follows:
12-Pin connector pin 1 (red wire)
+12 VDC
12-Pin connector pin 2 (black wire)
Ground
If the INControl is installed on the apparatus, turn on electrical power. Do not
operate the engine. The pump engaged interlock circuit must be open. No input
information from sensors or the engine is needed.
Enter Engine Type
Note: Do not operate the engine. The pump engaged interlock circuit must
be open to do this procedure (the OK TO PUMP LED must be off).
Note: There is a time out feature that will return the program to normal
operation in three seconds if input is not detected at the buttons
1. Press the SILENCE button and hold it for 5 seconds until the RPM display
shows four dashes. The program is ready for a three digit program code to be
input.
Note: The RPM and PSI buttons are used to enter the code. The RPM
button will select the digit that is to be changed. The PSI button will
change the digit.
2. Press PSI button first and enter code 441.
Results: After a few seconds the RPM display will flash the current engine type
setting. The timeout feature is disabled.
4. Press
INC
or
DEC
button to change the setting. (Refer to Table 2.)
5. Press the
SILENCE
button and hold it for 5 seconds.
Result: Display will return to normal.
6. Power down the INControl to reset the program and the new engine type
setting is programmed.
Table 2. Engine Type Setting
Engine Model
Engine Type
Setting
Cummins
101A
Detroit Diesel Series 50/60
102A
Navistar
104A
Caterpillar
105A
Mercedes
110A