Operation and Maintenance Manual, OnyX Sky Heat Recovery Units, 2022/01
Frapol Sp. z o.o. reserves the right to introduce changes without any prior notice.
Page
21
3.8.4
OnyX Sky 1000
Product data sheet (technical data in accordance with Regulation of the European Commission No. 1254/14)
Name or trade mark of the Supplier
-
Frapol Sp. z o.o.
Model identifier
-
OnyX Sky 1000
SEC (polar, temperate and tropical climates)
kWh/(m
2
/year)
-79,12
-37,43
-13,56
SEC class
A+
A
E
Declared type
-
Two-way
Type of drive installed
-
Stepless adjustment system
Type of heat recovery system
-
Other (diaphragm)
Thermal efficiency of heat recovery
%
80,0
Maximum flow rate
m3/h
998,7
Power consumption by the fan drive system
W
438
Sound power level
dB(A)
49
Reference flow rate
m
3
/s
0,19
Reference pressure difference
Pa
50
SPI
W/(m
3
/h)
0,272
Control factor and type of control
-
0.85
–
central control
Maximum internal and external air leakage rates
%
Internal
–
2
External
–
1
Location and description of the visual warning for filter
replacement
-
Alarms displayed on the control panel
screen
Website address for downloading pre-assembly/dismantling
instructions
-
AEC (polar, temperate and tropical climates)
kWh/year
828
291
246
AHS (polar, temperate and tropical climates)
kWh
8527
4359
1971