System Initial Start Up & Control Settings

APPLICATION SELECTION:

 Select either Submersible or Circulating pump to load preset programming. Refer 

to the parameter table at the end of this quick-start for presets.

Verify Rotation

Move HOA switch to AUTO position and the VFD will begin to run the motor.  Check the output flow and verify proper rotation.  If rotation is 

incorrect, stop the VFD, turn the VFD power off and wait 5 minutes.  Swap two motor leads to change rotation.  

The majority of drive setups can be accomplished by going through only one group; the setup [SET] group. This group was designed to 

have start-up specific parameters to make start-up easy. Navigate to the SETUP group [SET] by pressing the SHIFT button once from 

the main screen. Your display will show SET in the upper left hand corner of the display.

INPUT POWER # OF PHASES:

 Default is 3-Phase. Select 1-Phase for single-phase to three-phase conversion 

application which will change a motor HP rating setting to 50% of the VFD rating.

RATED MOTOR HP:

 Put the motor horsepower rating from the motor nameplate.

RATED MOTOR CURRENT:

 Put the motor FLA (full load amps) rating from the motor nameplate.

PRESSURE TRANSDUCER RANGE: 

The SET-25 default is for a 0-100PSI transducer. Program the maximum 

range of your pressure transducer. E.g. Program a value of 250PSI for a 250PSI transducer.

SET

Input Phase

01            3-Phase

SET

App. Select

00            None

SET

Motor HP

02           7.5 HP 

SET

F/B Unit Max 

25          100.0 PSI

Advanced Control Features

These parameters are set to optimal and safe default settings for the Submersible Pump application and can be changed 

in the field to fit application requirements. You may need to adjust some parameters to provide better control for your 

system. 

Pre-PID is designed for pump systems with long pipes that require filling pipe at every start. Upon PrePID time delay expiration or when 

system pressure (PSI) exceeds the PrePID Exit Level, the VFD will switch to PID control and maintain a system pressure at pressure set-

point. 

Note: SET-36 is set to 0.0Hz (Pre-PID is disabled by default) and can be enabled by changing SET-36 frequency. 

- Pre-PID Settings (Pipe Fill Mode)

PRE-PID FREQUENCY:

 Navigate to SET-36 and put VFD frequency at which drive will run to fill an empty pipe. 

Set this parameter for frequency above PID Low Frequency Limit and VFD will run to fill the pipe system for the 

time delay set in SET-37 or until pressure exceeds the exit level set in SET-38. Default setting is 0.0 Hz. 

PRE-PID STOP DELAY: 

This sets the time to fill an empty pipe. Test how much time it takes to fill an empty pipe 

during startup and adjust as necessary. Default setting is 180 sec.

PRE-PID EXIT LEVEL: 

PSI level above which the VFD will switch to PID control mode to maintain a system 

pressure at set-point. Default setting is 25 PSI.

SET

PrePID freq   

36      42.00 Hz 

SET

PrePID dly   

37      30 sec  

SET

PrePID Exit   

38      25.0 PSI  

SET

Motor FLA

03      2.2 A 

PRESSURE SET-POINT: 

Set SET-26 to desired pressure (psi) that VFD needs to maintain. The default is 50PSI 

and can be changed to any number within pressure transducer range. The pressure Set-point can be changed in 

DRV-00 parameter in remote mode too (in local mode it shows Hz). 

Parameter Programming Description

 

1) Press [MODE] or [SHIFT] key until the desired parameter group is displayed. 

2) Press UP [▲] or DOWN [▼] keys to scroll to the desired parameter. If you know the desired parameter number, you can set its number 

in the first parameter #00 “Jump code” of any parameter group (except SET and DRV groups) and after pressing [ENTER] key display will 

show that parameter.

3) Press [ENTER] key to enter the programming mode, which is indicated by a flashing cursor. Some parameters cannot be changed 

during VFD run or fault modes. Refer to the manual to check if desired parameter can be programmed during run. 

4) For selectable parameters press [▲] or [▼] keys to change parameter selection. 

When programming a numerical value, the value will be changed from maximum to minimum by pressing UP or DOWN key. In order 

to change any digit in a numeric value, use the SHIFT key to move the flashing cursor to that digit and UP or DOWN keys to adjust the 

selected digit.  

5) Press [▲] or [▼] keys to change the digit in numerical parameter value.

6) Press [ENTER] key to finish programming for this parameter. The flashing cursor disappears.

Verify Basic Settings

SET

PID SetPoint

26             50.0 PSI

Determine No-Demand Frequency and PID Frequency Low Limit

PID LIMIT LOW:

 Turn the HOA switch to Auto position and run system with No demand. When system pressure 

is at pressure set-point and frequency is stabilized, add 1Hz to this frequency and set it in SET-27. If system 

pressure is above pressure set-point, the first of three conditions for activation of the Sleep mode is met. 

For Flat curve pumps Minimum frequency is typically 53-54Hz.

- Setting Sleep Mode

Sleep mode will stop the VFD in no-demand condition when system pressure is slightly above SET-26 set-point and output frequency is 

below SET-32 Sleep mode frequency setting for SET-33 Sleep mode delay time. The most critical step is to determine and set a correct 

SET-27 PID Frequency Low Limit. 

Sleep Boost Mode: 

When pump system is ready to go into Sleep mode, it can increase a system pressure by some PSI to prevent 

short cycling at low demand changes.

Pipe Leak protection: 

Refer to VFD manual for detailed description on Dual Demand and Pipe Leak features.

Pump Speed Limit by Well Water Level: 

Refer to VFD manual for details. Requires well level transducer.

SLEEP MODE FREQUENCY:

 Set this parameter to [SET-27]+0.5Hz. If VFD frequency is below SET-32, the 

second condition for activation of the Sleep mode is met. 

SLEEP MODE DELAY TIME:

 The SET-33 is a delay time to activate Sleep Mode when other two conditions 

are met. If any of two above conditions is off, the Sleep Delay Timer will be reset. 

SLEEP BOOST:

 The VFD will boost the system pressure by the programmed in SET-34 value before going to 

sleep. Default is 3PSI for submersible and 2PSI for Centrifugal pumps. 

Program a value of 0PSI to disable this feature.

SLEEP BOOST TIMER: 

When VFD is ready for sleep mode it will increase pressure set-point by Sleep Boost 

value. When Set-point is met or Sleep Boost Timer SET-47 expires, VFD will activate sleep mode.

SET

PID Limit-L  

27       30.00 Hz

SET

Sleep Freq   

32       35.00 Hz

SET

Sleep Delay   

33        20 Sec 

SET

Sleep Boost   

34        3.0 PSI

- Broken Pipe Trip

SET

Pbroken Mode

40                 Yes

BROKEN PIPE MODE: 

Set to YES to enable, NO to disable. Default setting is NO. 

If the following three parameters are met simultaneously, VFD will trip on a broken pipe fault.

- UnderLevel Protection (Dry Well)

LEVEL DETECTION: 

Change SET-74 to NO to disable. Default setting is UnderLevel.

SET

Level Detect    

74     Under Level  

UNDERLOAD AMPERAGE: 

Adjust SET-78 to 65-70% of SET-03 (FLA) for submersible and  30-35% for 

centrifugal pump. Default setting is 0.0 A.

WELL FILL TIME: 

If parameter SET-80=YES, SET-81 fill time setting should be sufficient to fill the well before 

VFD attempting to start again. Default setting is 60.0 min. If VFD trips again on Under Level fault during restart 

attempt, the SET-81 value will be doubled for next restart.

SET

LDT Level    

78      0.0 A 

Underlevel trip (known as dry well protection) is designed to trip the VFD when the pump motor current draw is less than SET-78 for 

SET-77 time delay when VFD output frequency is above SET-76. For submersible pumps it is typically 65-70% and for centrifugal 

pumps 30-35%. For the correct adjustment check with motor manufacturer.

Broken Pipe will stop VFD operation if a broken pipe is detected while running in PID control mode to protected from flooding the field. 

For trip specifics, please refer to the installation & operation manual 

SET

LDT Fill Time    

81      60.0 min  

WAKE-UP LEVEL:

 The SET-35 is a percentage of  SET-25 pressure transducer range. The VFD will wake-up 

if system pressure is less than wake-up pressure that can be calculated [SET-26]-([SET-25]*[SET-35]/100). For 

100PSI transducer the SET-35 value equals to PSI (2% would be 2PSI).

SET

Pbroken F/B

43                 50

SET

PbrokenFreq

41                 59.00 Hz

SET

PbrokenDly

42                 30 sec

1) If drive is running over the speed indicated in SET 41,

2) If drive is running longer than time indicated in SET 42,

3) If the pressure is below PSI indicated in SET 43.

SET

WakeUp Level

35              2%

franklin-controls.com | 800.962.3787

SET   Boost Timer

47 

  10 sec

Содержание VFD 1

Страница 1: ... Transducer placement Placing the transducer too close to the pump discharge may cause oscillations and improper operation of the VFD Note If two transducers are used for redundancy refer to VFD manual for details Main Display DRV Current parameter group SET DRV FG1 FG2 I O APP EXT COM 00L Shows the current parameter number within a current group An L will appear when VFD is switched to Local cont...

Страница 2: ... key to move the flashing cursor to that digit and UP or DOWN keys to adjust the selected digit 5 Press or keys to change the digit in numerical parameter value 6 Press ENTER key to finish programming for this parameter The flashing cursor disappears Verify Basic Settings SET PID SetPoint 26 50 0 PSI Determine No Demand Frequency and PID Frequency Low Limit PID LIMIT LOW Turn the HOA switch to Aut...

Страница 3: ...for parameter Amps see manual for parameter Environmental Conditions Please select all applicable conditions Indoor Dirt Debris Outdoor Moisture Direct Sunlight Chemicals YES NO YES NO YES NO Please complete the fields below if the VFD is installed in an enclosed package that was not built by Franklin Electric Indoor Dirt Debris Outdoor Moisture Direct Sunlight Chemicals Indoor Dirt Debris Outdoor...

Страница 4: ... the intake of another 4 Mount the drive in a Separate Enclosure A simple step that can save a lot of headaches is to mount the drive separately from other heat generating electrical equipment Just a few extra devices in an enclosure can add significant heat that can push the internal ambient temperature of the cabinet beyond what is acceptable for the drive Terminal N is not a neutral it is negat...

Страница 5: ...sed by Enclosure dimensions in inches Cooling Fan AC Unit Size H W D H W D H W D V Ins V Ins V Ins HP FLA HP FLA SF RPM SF RPM SF RPM Max F Min F Max F Min F Max F Min see manual for parameter Amps see manual for parameter Amps see manual for parameter Environmental Conditions Please select all applicable conditions Indoor Dirt Debris Outdoor Moisture Direct Sunlight Chemicals YES NO YES NO YES NO...

Отзывы: