background image

Parameter

Description

Fan & Pump - Recommended Settings

NOTE*: When entering parameters, any changes made will only be stored if the Enter button is pressed twice after making the change.*

0.00

Frequency command  / Reference (Paramter that first appears when 
VFD is powered up.)

Local Control: Set target speed (Hz) (*PID see below)

DRV

Drive Start / Stop Control Method (Looks like DRU on display)

Local Control: 0 (Keypad)

Remote Control: 1

FRQ

Frequency Setting Method (Looks like FR9 on display)

Local: 1 (Keypad-2)
PID Control: 0 (KeyPad-1)

Remote: 3 for 0-10V or 4 for         
4-20mA

F1

Forward / Reverse Run Disable

Reverse Run Disable: 2

F24

High / Low Frequency Limit enable

If Needed: 1 (Do not use for PID control)

F26

Minimum frequency limit. (Only visibe if FU1-33 = Yes)

Set desired low limit (Hz) (Do not use for PID control)

F39

Output Voltage Adjustment (If motor rated voltage is less than input 
voltage, set this parameter accordinglyy.  For example, if Input Voltage is 
480VAC &  Motor Voltage is 460VAC, set parameter to 96%)

100%= Output voltage will be the same as input voltage when 
drive is running at full speed. 

F50

Electronic Motor Thermal Overload Protection

1 (Yes)

F59

Stall Prevention (Stall level can be adjusted if necessary on F60)

111*

H19

Input/Output Phase Loss Protection

11*- not needed for Single Phase input

H20

Power on Start (VFD will start if remote start contact is closed at drive 
power-up)

1 (Yes)

H21

VFD will Restart After a Fault was Reset.

1 (Yes)

H22

Speed Search (VFD will start on the fly if motor is still spinning)

1110*

H26

Number of Auto Restart Attempts

3

H27

Restart Delay (Set as maximum as possible for your application)

60.0sec.

H30

Motor size: kW= HP x 0.75

Kilowatt rating of motor

H31

Number of Motor Poles = 7200/ max RPM of motor

Number of motor poles

H33

Motor Full Load Current = Full Load Amps x Service Factor 

Motor Full Load Current 

Additional Parameters for Proportional Integral Derivitive (PID) Control in Single Motor Applications 

(Typically used when VFD needs to maintian a desired pressure or temperature based on direct sensor feedback to VFD)

H49

PID Control Enable 

1 (Parameters “rEF” will not appear until this parrameter is set to 1)

*rEF

PID Set Point Reference Parameter 

Set Point=(Desired press or temp) x 60Hz/ (Max Range of Sensor)

H50

Feedback for PID control: select 0 for 4-20mA or 1 for 0-10V

0 for 4-20mA feedback or 1 for 0-10V feedback

H51

Proportional Gain for PID Control Response 

Higher percentage = greater speed change at same feedback 
value 

H52

Integral Time for PID Control Response 

Higher number = longer response time at same feedback value

H56

Minimum Frequency Limit for PID Control 

Set desired low limit in Hz

H61

Sleep Mode Delay Time 

Desired sleep mode delay time in seconds

H62

Sleep Mode Frequency (VFD enters sleep mode when VFD speed        
decreases below frequency entered here for time set on H-61)

Desired sleep frequency in Hz (If minimum frequency is entered 
on H-56, set H-62 to .5-1Hz. higher than H-56)

H63

Sleep Mode Wake Up Level (Percentage of sensor range that feedback 
signal must reach before VFD will wake up from sleep mode)

Desired level in % (for normal PID control, set level slightly lower 
than desired press.  Set opposite for inverted PID control)

Reset Parameters

H93

If Needed, Use this Parameter to Reset all Setting to Default

Reset all Setting: 1 (Will return to 0 when done). 

NOTE:

  For reversed PID control (VFD should increase speed when feedback value is more than a set-point) change I8 or I13 to 60Hz and I10 

or I15 to 0.0Hz. To calculate a set-point = 

60Hz-(Pset. x 60Hz/Pmax).

Using the LCD keypad  display

PARAMETER   “GROUP”    “CODE”

Use the

 

t

 (Left), 

u

 (Right) keys to scroll through the five parameter groups: DRV

u

F

u

H

u

 

u

DRV

Use the

 

p

 

(Up),

 

q

 (Down) keys to scroll through parameter codes within each parameter group.

*  For Binary Bit parameters the bit must be in the top position to equal On (1) and the bottom position to equal Off (0) and are numbered from right to left. 

Example: H22: 1110 =  ı ı ı ı  =  Bit 3 on, Bit 2 on, Bit 1 on, Bit 0 off)

** When entering parameters any changes made will only be stored if the Enter button is pressed twice after making the change.

GS/C Series VFD 
QUICK START GUIDE

Отзывы: