14
Electrical
Input Voltage
3-Phase 190-600 VAC
Frequency
50 Hz or 60 Hz
Motor SF (Max) Amps Range
3 amps to 359 amps
Maximum Conductor Size Through
Sensors
0.920” (23mm) Diameter Max
Measurement Accuracy
Voltage
1% ± 1 digit
Current
1% ± 1 digit
Trip Time
Overload, underload, overheat,
unbalance, overvoltage, undervoltage
3 seconds
Input Current, L1, L2, L3
0.15 amps
Control Circuit Rating
1.5 amps AC, up to 600 volts
Signal Circuit Rating
1 amp AC, up to 250 volts
Incandescent lamp, 100 watts max
Agency Approvals
UL 508 classi
fi
cation NKCR
fi
le E160632
cUL
Standards Met
Surge
ANSI/IEEE C62.41
Electrical Fast Transient
IEC 1000-4-4 Level 4, 4kV
ESD
IEC 1000-4-2 Level 3, 6kV
Mechanical
Dimensions (WxHxD)
Base Unit
8.0” x 5.35” x 4.3” (20.3 x 13.6 x 10.9 cm)
Display Unit
7.0” x 3.0” x 1.4” (17.8 x 7.6 x 3.6 cm)
Total Unit
8.0” x 5.35” x 5.7” (20.3 x 13.6 x 14.5 cm)
Weight
Base Unit
46 oz (1.3 kg)
Display Unit
7 oz (0.2 kg)
Total Unit
53 oz (1.5 kg)
Operating Temperature Range
-20°C to +60°C
Storage Temperature Range
-30°C to +80°C
Relative Humidity
10-95% non-condensing
Protection Class
Display Unit
NEMA 3R
Base Unit
NEMA 1
Specifi cations