16

SubDrive Duplex Alternator

16

17

# of

 

Flashes

Fault

Possible Cause

Corrective Action

1

System 1 down 

or shorted low 

pressure sensor

System 1 is not meeting 
demand properly or 
lower set pressure 
sensor is shorted

Check Drive 1’s front panel for 
possible fault code and follow 
corrective actions for that fault code. 
Make sure that Drive 1 has a green 
light (i.e. it has power). If there is no 
fault code and a green light is present, 
check the lower set pressure sensor to 
see if its contacts are shorted together.

2

System 2 down 

or shorted low 

pressure sensor 

System 2 is not meeting 
demand properly or 
lower set pressure 
sensor is shorted

Check Drive 2’s front panel for 
possible fault code and follow 
corrective actions for that fault code. 
Make sure that Drive 2 has a green 
light (i.e. it has power). If there is no 
fault code and a green light is present, 
check the lower set pressure sensor to 
see if its contacts are shorted together.

3

Open high

pressure sensor

Leads to higher set 

pressure sensor may be 
open or broken or the 
sensor itself may have 
failed to open

Check the leads to the higher set 
pressure sensor. Check the sensor 
itself. Check the leads to Alternator’s 
terminal block.

4

Leads to Drive 1 

are open circuit 

Leads from Drive 1 to 

Alternator are damaged 
or not connected

Check leads from Drive 1 to Alternator. 
Check connection at terminal block of 
Drive 1 and connection at Alternator 
terminal block.

5

Leads to Drive 2 

are open circuit

Leads from Drive 2 to 

Alternator are damaged 
or not connected

Check leads from Drive 2 to Alternator. 
Check connection at terminal block of 
Drive 2 and connection at Alternator 
terminal block.

6

Pressure 

sensors not 

set far 

enough apart

Pressure sensor 
differential’s too close. 
Both Drives are trying to 
meet system demand at 
the same time

Adjust pressure sensors so the PSI 
difference is great enough to get only 
one drive to run at a time; at least 3 
psi should be enough difference.

Input from Power Source 
to Indoor/Outdoor 
Transformer

Voltage

115 VAC

Frequency

60 Hz

Input to Controller Unit

Voltage

12 VAC

Frequency

60 Hz

Power (A)

1.4 Watts

Pressure Setting (B)

Factory preset

50 psi

Adjustment range

25-80 psi

Operating Conditions

NEMA 4 (indoor/outdoor)

Model 5850012000

Temperature

-13 to 125 ºF (-25 to 51 ºC)

Relative humidity

0-100%, non-condensing or 

condensing

Controller Size 

(approximate)

Outer dimensions 

5.9” H x 5.9” W x 3.6” D

Weight

1.3 lbs (0.59 kg)

For Use With

Franklin Electric SubDrives/
MonoDrives

All models (see Table 1 pg. 3 
for details)

Note: 

(A) Power is on the secondary side of Transformer. 

 

(B) Pressure sensors must be set at least 3 psi apart.

Specifications

Содержание SubDrive Duplex Alternator

Страница 1: ...Installation Manual SubDrive Duplex Alternator ...

Страница 2: ...e 9 Wiring Connections 10 13 Start Up and Operation 13 14 Mounting Dimensions 15 Accessories 15 Diagnostic Fault Codes 16 Specifications 17 Appendix 1 Duplex Inline Constant Pressure Quick Reference Guide 18 Tables 1 SubDrive MonoDrive and Inline Models 3 Figures 1 Mounting Screws 9 2 Drive Sensor Cable Connections 10 3 Pressure Sensor Connections 11 4 Alarm Connections 13 SubDrive Duplex Alternat...

Страница 3: ...work with any combination of the listed Franklin Electric SubDrives MonoDrives Descriptions and Features The Franklin Electric SubDrive Duplex Alternator allows for two Franklin Electric SubDrive units to operate on the same water system and share the work load equally The Alternator will alternate between the two SubDrive units when the defined amount of run time has been reached The Alternator i...

Страница 4: ...ensor Cable Pressure Sensors 4 conductor C Sensor Cable SubDrives 2 conductor X2 D Mounting Brackets E Outdoor Rated 120 VAC 12 VAC Transformer F Transformer Output Cable G Rubber Plug H Installation Manual Installation Manual SubDrive Duplex Alternator A B C D F E G H ...

Страница 5: ...tically start and provide additional water After the primary drive has reached its defined amount of run time the Alternator will interchange the pressure sensors thus causing the two drive units to switch roles System Diagnostics In addition to alternating the two drive systems the Alternator monitors the two systems to see if they are meeting the water demand as expected If a system is not meeti...

Страница 6: ...f SubDrive products from Franklin Electric one model fits all s WARNING For the indoor outdoor transformer note the following Risk of fire If installation involves running wiring through a building structure special wiring methods are needed Consult a qualified electrician Not for use with dimmers Before Getting Started s ATTENTION This equipment should be installed by technically qualified person...

Страница 7: ...operly the Alternator enclosure is suitable for indoor or outdoor installations see Installation Procedure section for details pg 9 4 The Alternator should only be mounted with the wiring end oriented downward The controller should not be placed in direct sunlight 5 The mounting location should have access to 115 VAC electrical supply For outdoor installations the indoor outdoor transformer must b...

Страница 8: ...able Supplied Pump 1 Pump 2 Motor 1 PRESSURE SENSORS 12 VAC DRIVES 1 2 1 2 PS HI PS LO SD1 SD2 1 2 1 2 ALARM 24VAC 1A MAX 24 VDC 0 5A MAX Drive Sensor Cables GFCI Outlet Drive 2 Drive 1 Motor 2 To Power Source To Power Source Outdoor outlet cover for outdoor use Motor Cable Motor Cable Pressure Sensor When installing an Alternator with a SubDrive 300 do not hook up the pressure shut off sensor to ...

Страница 9: ...ssure tank should be between the pressure sensors and the pump The sensors have a 18 National Pipe Thread NPT connection 5 Mount the Alternator unit in a suitable location using four mounting screws not included as shown in Figure 1 below Figure 1 Mounting Screws Mounting Screw Locations User Supplied Quantity 4 Rear View Front View Note For installation procedures for the Duplex Inline Constant P...

Страница 10: ...te leads linking the pressure shut off switch to its connections on the SubDrive300 B For all other SubDrives cut off the quick connect ends and strip the wire to make a two conductor cable with stripped leads at both ends 4 Repeat step 3 for Drive 2 but connect Drive 2 s pressure sensor cable to the Alternator s terminal block labeled SD2 on the right side Figure 2 Drive Sensor Cable Connections ...

Страница 11: ...rated for use indoor or outdoor so it can be mounted in any convenient location 6 Open Circuit Check After completing steps 1 5 do the following A Apply power to the Alternator without applying power to the drives B The indicator lights should all be OFF except for the orange 1 hour switching interval light If the Alternator s red light flashes it means that there is an open circuit to one of the ...

Страница 12: ...The two pressure sensors communicate the system pressure to the SubDrive units The Alternator requires that the pressure sensors have at least a 3 psi differential The sensor connected to the Alternator s PS HI terminal must be the one set higher than the other sensor The sensors are preset at the factory to 50 psi but must be adjusted by the installer using the following procedure A Remove the ru...

Страница 13: ...arger center strain relief to 55 60 in lbs to maximize the unit s weather protection PRESSURE SENSORS 12 VAC DRIVES 1 2 1 2 PS HI PS LO SD1 SD2 1 2 1 2 ALARM 24VAC 1A MAX 24 VDC 0 5A MAX Alternator PRESSURE SENSORS 12 VAC DRIVES 1 2 1 2 PS HI PS LO SD1 SD2 1 2 1 2 ALARM 24VAC 1A MAX 24 VDC 0 5A MAX Load 24 VAC 1A Max 24 VDC 0 5A Max Use the rubber pull plug on the unused strain relief to seal the ...

Страница 14: ...ith the system While it s looking the Alternator will alternate the two drives back and forth a few times After performing the check the Alternator will either declare a fault or leave the system as it was if no problem was found Manual Override Clear Fault Button The manual override button allows the user to switch which SubDrive system is the primary system at any time When the user presses the ...

Страница 15: ... 5 80 Accessories Duplex to Pressure Sensor Cable Kit 22 AWG 4 conductor pressure sensor cable 10 feet 225597901 100 feet 225597902 Drive to Duplex Cable Kit 22 AWG 2 conductor pressure sensor cable 10 feet 225597903 100 feet 225597904 Indoor Outdoor Transformer Kit 225597905 ...

Страница 16: ... 2 down or shorted low pressure sensor System 2 is not meeting demand properly or lower set pressure sensor is shorted Check Drive 2 s front panel for possible fault code and follow corrective actions for that fault code Make sure that Drive 2 has a green light i e it has power If there is no fault code and a green light is present check the lower set pressure sensor to see if its contacts are sho...

Страница 17: ...psi Operating Conditions NEMA 4 indoor outdoor Model 5850012000 Temperature 13 to 125 ºF 25 to 51 ºC Relative humidity 0 100 non condensing or condensing Controller Size approximate Outer dimensions 5 9 H x 5 9 W x 3 6 D Weight 1 3 lbs 0 59 kg For Use With Franklin Electric SubDrives MonoDrives All models see Table 1 pg 3 for details Note A Power is on the secondary side of Transformer B Pressure ...

Страница 18: ...revention device a check valve is required on the incoming water supply line NOTES 1 These optional components are shown in a typical installation diagram They should be used at the installer s discretion as required for particular applications 2 If the optional high pressure shut off kits 305707912 are being used on this duplex Inline Constant Pressure System they should be installed as per the s...

Страница 19: ...Notes 19 ...

Страница 20: ... A FRIEND Franklin Electric Submersible Service Hotline 800 348 2420 225589101 REV 3 M1557 06 11 400 East Spring Street Bluffton Indiana 46714 Tel 260 824 2900 Fax 260 824 2909 www franklin electric com 2 2 5 5 8 9 1 0 1 ...

Отзывы: