Wiring Connections
1. Verify that the power has been shut off at the main breaker.
2. Open the cover to the Alternator.
3.
Drive Connections
Connect a two-conductor pressure sensor cable from Drive 1 to the
Alternator’s terminal block labeled SD1 on the right side. The red and
black wire connections are interchangeable. (See Figure 2 below).
Whichever Drive unit is connected to the SD1 terminal will be the primary
system first. The Drive unit connected to the SD2 terminal will be the
backup system first.
A. If connecting to a SubDrive300, use the supplied two-conductor
pressure sensor cable. Cut the terminals off both ends of the red
and black leads from the existing four-conductor cable. Leave
only the Green and White leads linking the pressure shut-off
switch to its connections on the SubDrive300.
B. For all other SubDrives, cut off the quick connect ends and strip
the wire to make a two-conductor cable with stripped leads at
both ends.
4. Repeat step 3 for Drive 2, but connect Drive 2’s pressure sensor cable to
the Alternator’s terminal block labeled SD2 on the right side.
Figure 2: Drive Sensor Cable Connections
PRESSURE
SENSORS
12 VAC
DRIVES
1
2
1
2
PS-HI
PS-LO
SD1
SD2
1
2
1
2
ALARM
24V-1A
SubDrive
1
2
ON
1
2
3
4
SW1
Alternator
PRESSURE
SENSORS
12 VAC
DRIVES
1
2
1
2
PS-HI
PS-LO
SD1
SD2
1
2
1
2
ALARM
24V-1A
Alternator
SubDrive300
PRESSURE
SENSOR
SHUT-OFF
SW2
SW1
To Pressure Shut-off Switch
PRESSURE
SENSORS
12 VAC
DRIVES
1
2
1
2
PS-HI
PS-LO
SD1
SD2
1
2
1
2
ALARM
24V-1A
Alternator
SubDrive300
PRESSURE
SENSOR
SHUT-OFF
INT
FAN
INV
FAN
PFC
FAN
NO
NO
COM
RELAY
SW2
SW1
O N
(Cut Black and Red wire on both end only if using SubDrive300)
To Pressure Shut-off Switch
(Cut black and red wires; leave only
the green and white connected to
the pressure shut-off switch.)
Note:
If using a NEMA 4 the quick connects or stripped leads may be used.