INSTALLATION AND SETUP
Electrical Installation
25
Additional Control Input/Output Wiring
1.
Built-In Duplex Alternator
– Use the ALTERNATOR terminals to connect two drives in a lead/
lag configuration. Refer to
“Duplex Alternator Feature” on page
Alternator communication cable should for this connection. Refer to
.
•
Connect the black cable lead to the A terminal on both drives.
•
Connect the red cable lead to the B terminal on both drives.
•
Connect the green cable lead to the terminal when applicable.
IMPORTANT:
Both drives should be wired from the same panel to ensure proper communica-
tion and operation.
2.
Moisture Sensor
– The WET SENSOR terminal supports the Franklin Electric Moisture Sensor.
•
Connect the red cable lead to the +24 terminal.
•
Connect the black cable lead to the terminal.
•
Connect the white cable lead to the I+ terminal.
•
Connect the green cable lead to the I– terminal.
Refer to
for more information about configuring this input.