TESTING

a.  Ensure that all plumbing lines have been properly flushed. If lines are not properly flushed, it can clog the check stops in 

the mixing valve and/or clog the strainer in the input side of the solenoid valve. This can result in low water flow.

b.   Please note, the output side of the solenoid valve contains a pressure regulator. The water lines MUST be purged of all air 

prior to sink operation. Otherwise it can cause the water stream to spit out of the orifice causing water to spray outside 

the sink.

c.   With system flushed and pressurized, place your hand in front of the IR sensor inside the sink bowl. You will hear the 

solenoid valve open and water will begin to run.

d.   Holding your hand in front of the sensor, you will see ... 

i. water entering the clear laminar flow chamber, 

ii. the LED will be illuminated (seen from the spout), and 

iii. the electrolytic generator will be active. You will also see bubbles coming from the 

electrolytic generator into the water.

e.  If you have high pressure conditions, the shut off valve can be used to slightly reduce 

the stream length. Adjust as necessary so that the water targets this range when 

running. Cycle the sink multiple times until consistent.

f. Hold your hand in the target area to make sure water triggers. Depending 

on local lighting conditions, sensor sensitivity may need to be adjusted. 

This can be done using the wireless handheld programmer AC01-005.

 

If any of the above is not functional, double check that the connections are colour-matched  

and that the connection is made properly.

Normal operation is as follows:

- IR sensor will see a users hand. 

- This will trigger the water flow, LED and the electrolytic generator will turn on. 

- When the user removes their hands to lather, the water flow will turn off however the electrolytic generator will stay 

on for 20 seconds (unless programmed otherwise). The electrolytic generator is self programming based on local water 

conductivity. If conductivity is in normal range of 75-350 TDS, the LED will cycle in intensity. If the conductivity is too high, 

the LED will blink quickly. If the conductivity is too low, the LED will slowly blink. After the 20 seconds the water flow will 

trigger by itself for 3 seconds. This is done to help signal the user of the 20 second minimum lather time and also for a 

subsequent wash rinse of the sink. After the 3 second post wash occurs, the electrolytic generator will begin a purge cycle. 

Once again the LED will pulse in intensity as the water in the electrolytic chamber is being charged with oxidants. When this 

cycle is complete, the LED will turn off.

AC01-005

6

6

  WATER CONNECTIONS

a.  Connect the supply line (pre-mixed or via thermostatic mixing valve) to the ½

 MIP thread inlet (right side) of the solenoid 

valve.

b.  Take the supplied 3/8

 tube and insert it into the output side (left) of the solenoid valve. Insert the other in the supplied 

shut off valve. 

c.  Insert the other side into the bottom of the laminar flow chamber.
d.  If using a thermostatic mixing valve (Franke MEDI-MIX sold separately), recommended temperature is 27-35∘C (80-95 F) 

(Hot or warmer water is both harsher on the user’s skin and secondly, as water temperature increases, it loses its ability 

to dissolve ozone which can cause reductions in sanitization performance.) When adjusting the thermostatic mixing 

valve, set to minimum and verify water temperature is within recommended range.

Содержание HWSS2321W-00

Страница 1: ...INFECTION CONTROL WASH BASIN ...

Страница 2: ...ste treatment Medi flo is designed for hand washing only and is not to be used as a drinking source to wash instruments or bedpans etc Recommended for areas with normal water conductivity above 75 TDS total dissolved solids If unaware of your local water conductivity please contact customer service and this can easily be determined for you before you install the product Medi flo is recommended to ...

Страница 3: ... Location 17 5 8 448 mm 1 1 2 Waste Location FINISHED FLOOR Ø1 Ø25 mm 2 51 mm 3 1 2 89 mm 7 178 mm 31 9 16 801 mm 3 1 4 83 mm 3 7 8 98 mm WALL OPENINGS LAYOUT 21 1 4 539 mm 8 11 16 220 mm 10 3 8 263 mm Opening for rough in box 32 13 16 833 mm 2 2 2 2 EN No tools Hand tighten ...

Страница 4: ...pace is limited to install the shroud We recommend a 1 piece tubular trap without a cleanout plug on the bottom the trap 5 5 ELECTRICAL CONNECTIONS Check local codes for compliance prior to making any electrical connections The water tight fittings have an alignment feature Gently push the fittings together rotating until they engage Little to no force should be required to do so Once fitted toget...

Страница 5: ... as follows IR sensor will see a users hand This will trigger the water flow LED and the electrolytic generator will turn on When the user removes their hands to lather the water flow will turn off however the electrolytic generator will stay on for 20 seconds unless programmed otherwise The electrolytic generator is self programming based on local water conductivity If conductivity is in normal r...

Страница 6: ...trolytic generator is not seen running 1 Check cable connection 2 Ensure water is not distilled or R O filtered TDS 50 Water output is too high 1 Adjust shut off valve installed in 3 8 line 2 Faulty flow control regulator found in brass output port of the solenoid valve Water output is too low 1 Faulty flow control regulator found in brass output port of the solenoid valve 2 Obstruction on dirt st...

Страница 7: ... or by sending in a sample of 250ml minimum to our customer service Tests such as ORP and Indigo may not give valid readings due to hydrogen interference temperature water composition and PH Subtract the reading obtained from straight tap water to remove any reading from chlorine The default operation of the electrolytic generator is to run a charge cycle after every use Target canister charge is ...

Страница 8: ... 00 Medizmi102218 V15 EN EN WARRANTY If inspection the product confirms that it is defective in materials or workmanship Franke Kindred Canada Ltd will at their choosing repair or exchange the product during the following periods Sink waste fitting and shroud 2 years Water controls and electronics 1 year NOTE In the event of a limited warranty claim proof of purchase date will be required ...

Отзывы: