8. Assembly
8.1
Secure the control box (2) to a wall near to the ECC2 function controller (1).
8.2
Connect the control box (2) to the ECC2 function controller (1).
Inputs
☞
The inputs must be programmed via the web application with an ECC2 function
controller.
a Input 1 - grey
Thermal disinfection
b Input 2 - yellow
Hygiene flush
c Input 3 - green
Cleaning deactivation
d GND - white
Ground for the inputs
e Input 4 - brown
Set switch (A/B)
Outputs
f Output 1 - red
Thermal disinfection
g Output 2 - pink
Collective error
h GND - blue
Ground for the outputs
i Bridge (+ 24 V)
Bridge these terminals if necessary
9. Function
Hygiene flush start command
9.1
Press the hygiene flush button (1) for at least 5 s.
• If the hygiene flush function and a flow time are defined in the program ID for the
fitting, the hygiene flush starts.
Cleaning circuit start command
9.2
Press the cleaning circuit button (2) for at least 5 s.
• The fittings in the network are switched to cleaning mode. No actuation of fittings
possible.
9.3
Press the cleaning circuit button (2) again.
• Cleaning deactivation is ended.