4. Important Notes
• Installation, commissioning and maintenance are to be performed only by a
qualified technician according to the instructions provided and in accordance with
legal requirements and acknowledged rules of technology.
• All technical connection regulations specified by the local water and electricity
supply utility companies must be complied with.
• All rights reserved to make technical alterations.
5. Application
PROTRONIC - A3000 open opto-electronically controlled washing-unit fitting DN 15
for in-wall installation, for connecting to premixed warm or cold water.
With facility for externally controlling options such as fittings settings and
communication via ECC function controller.
Control functions:
• Hygiene flushing (10 seconds), 24 hours after last usage
• Safety shut-off after 5 minutes duration reflection
Additional functions with ECC function controller (Ethernet):
• Automatic thermal disinfection according to DVGW work sheet W 551 as well as
safety switch-off
• Cleaning system shut-down
6. Technical Specifications
Minimum flow pressure:
1.0 bar
Recommended flow
pressure:
1–5 bar
Maximum operating
pressure:
10 bar
Calculation flow rate:
0.10 l/s
Volumetric flow:
0.10 l/s for 3 bar flow pressure
Operating voltage:
24 V DC
Power consumption:
2.5 W
Communication:
Ethernet via ECC function controller
Type of protection:
IP 68