2.5. Pre-utilisation check
Check, that the seals are in good condition, that the
door closes correctly, that the glasses are not
damaged.
2.6. Mounting the levelling feet
Fit the 3 screws and the 3 caps supplied (on the
burner) into each leg of the stove (fig. 4).
2.7. Levelling
It is essential to ensure that the appliance sits level
on the floor. Adjust the levelling feet. Use a spirit level
across the burner pot to check the level (fig. 4).
2.8. External tank
When the stove is connected to an external or remote
tank, it must be secured to the floor. The bracket is
included (fig. 6).
A barometric fuel tank should not be positionned where
it will be in the direct rays of the sun or adjacent to a
source of intense heat.
If the tank is more than 8 ft (2,5 m) higher than the stove
a pressure reducer must be installed on the oil line (see
fig. # 5).
If the tank is lower than the stove a lift pump will have
to be utilized (see fig. # 5).
A clearance of 6 “ (15 cm) must be maintained between
the external/remote tank and the stove.
1
3
4
6
2
7
1
5
3
6
2
7
1
2
3
Figure 4 - Levelling
1 - Spirit level
2 - Screw
3 - Cap
Figure 5 - Oil supply
1 - 8 ft max.
2 - At least 9,5 in.
3 - Oil Tank
4 - Filter
5 - Suction pump with re-
serve
6 - Pipe Ø 3/8" O.D.
7 - 0,15m minimum
1
2
3
Figure 6 - Bracket
1 - Rear foot
2 - Bracket
3 - Foot fixation screw
Document n° 952-3 EN ~ 02/03/2000
Continental
Poêle à combustible liquide
Notice de référence
5