![France Air MOOREA Compensation Скачать руководство пользователя страница 4](http://html1.mh-extra.com/html/france-air/moorea-compensation/moorea-compensation_technical-manual_2326554004.webp)
4
NT 1786 A – 02/2017
ELECTRICAL CONNECTION
Optional flush-mounted lighting
Power is supplied to the flush-mounted light fittings and fluorescent tube lighting via the spare cable.
230 volt single-phase power supply, no light dimming possible.
Module
Light output
1000
1 x 21 W
1500
2 x 28 W
2000
2 x 28 W
2500
2 x 28 W
3000
2 x 28 W
LED lighting (option)
The LED spotlights must be positioned in the cut-outs in the top of the hood.
Power is supplied via the quick connection terminal on each spotlight; there are two terminals to enable the power supply to
be transferred from one spotlight to the next.
230 volt single-phase power supply, voltage reduction is possible to enable the lighting to be dimmed.
Module
Number of
spotlights
Total output (W)
1000
1
8
1500
2
16
2000
3
24
2500
4
32
3000
5
40
ADVICE
During commissioning, it is recommended that measurements (flow rate, pressure, etc.) are taken to assess whether the
installation is operating correctly.
FAULTS
Should any faults be observed: contact the after-sales service.
This hood is mainly made from stainless steel materials, therefore special care must be taken when selecting which cleaning
products to use. Only use products designed for stainless steel. Use a sponge to wipe in the direction of the brushing, then
rinse with water and dry with a soft cloth. The cleaning products used must not contain any hydrochloric acid or bleach-based
substances. We recommend that the cleaning and polishing product
Brilinox (product code 760030)
is used to maintain and
protect your stainless steel hood. We advise against the use of abrasive powders or pads as these may scratch surfaces and
alter their appearance. For minor scratches, we recommend that you use the
foam eraser pad (product code 760032)
. Before
using any maintenance product, please read through the technical information provided.
Visible areas of the hood must be cleaned every day after each service. The filters and extraction plenum must cleaned as
and when it is deemed necessary; once a week is the compulsory minimum. The filters can be removed for cleaning in a bath
of cleaning solution or in a pass through or normal dishwasher.
The extraction network must be cleaned at least once a year.
Maintenance must be performed on Mooréa Compensation and Atria Compensation hoods at least once a year by a
professional (general condition checked, electrical connections checked, etc.).
If there is a fault with an LED spotlight, it must be replaced as its components cannot be removed.
If there is a fault with the flush-mounted lighting, the polycarbonate diffuser will need to be removed to access the fluorescent
tubes and the various components; remove the screws around the perimeter of the diffuser. The tubes are fluorescent tubes,
16 mm in diameter, type T5, 4000 K, with a 21 W or 28 W output depending on the model.
4.
MAINTENANCE