NT 1786 A – 02/2017 

 

 

 

 

 

 

 

 

 

 

 

Number of modules based on length for wall-mounted hoods greater than 3000 mm; for dual hoods, the values are 

doubled. 

Length  

3500 

4000 

4500 

5000 

5500 

6000 

Modules 

2000 + 1500 

2000 + 2000 

2000 + 2500 

2500 + 2500 

2500 + 3000 

3000 + 3000 

 

 

 

POSITIONING  

 

The minimum installation height of the hood must be 2 metres for a new building and 1.90 metres for a renovated building. 

To ensure optimum capture, a minimum overflow system for the hood of 300 mm must be respected on the sides and front 

of the range cooker (for versions with visor).  

The hood must be suspended using threaded rods with a minimum diameter of 8 mm and a maximum of 10 mm; the number 

and positions of the mounting points are shown on the preceding diagrams. 

If there are several modules, the kit supplied must be used for mechanical connection; refer to the assembly instructions 

contained in the kit.

 

 

AIR SYSTEM CONNECTION 

 

This hood must be connected to air extraction and compensation networks made from a rigid, non-combustible material 

(material classed A1, formerly M0). The connection between the air extraction and compensation networks and the hood 

may be made using a flat take-off or a spigot plate. This take-off or spigot must be attached to the hood using rivets or any 

other means of fastening apart from self-tapping or self-drilling screws which could cause injuries during cleaning or 

maintenance operations. 

If the optional guillotine dampers are fitted, the extraction plenum is supplied with circular cut-outs (355 mm in diameter), 

shown on the preceding diagrams; otherwise the plenums are supplied without holes. 

The compensation plenums are supplied with circular cut-outs (250 mm in diameter) shown on the preceding diagrams. 

The diameter of the extraction network where it joins the hood must  be no less than 315 mm. There is a risk of noise 

disturbance if this dimension is smaller. 

 

 

 

 

 

 

 

 

 

3.

 

INSTALLATION 

module = 2500 or 3000 