Initialization
Rotary field direction
Check the direction of the voltage rotary field
on the measurement value display of the EM-
PQ2500.
A "right" rotary field is usually available.
Presentation of the phase sequence according
to the rotary field direction.
UL1-UL2-UL3 = right rotary field
UL1-UL3-UL2 = left rotary field
Apply measurement voltage
•
Voltage measurements in networks with
nominal voltages above 500VAC against
ground must be connected using a voltage
converter.
•
After connection of the measurement volta-
ges, the measurement values displayed by
the EM-PQ2500 for voltages L-N and L-L
must match those at the voltage measure-
ment input.
•
If a voltage converter factor is programmed,
this must considered upon comparison.
Warning!
The EM-PQ2500 is not suitable for
measuring DC voltages.