![FPS 9650 Series Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/fps/9650-series/9650-series_installation-and-maintenance-manual_2326017015.webp)
9650 Valve Series
Installation and Maintenance Manual
15
4)
Apply Molykote 55 O-ring grease or equivalent to the two O-rings and rubber gasket. The O-rings should face
the actuator and the adapter plate should be oriented so the set screw mates with the hole in the plate as
shown.
5)
Note correct orientation of solenoid depending on combination of actuator and solenoid.
A125-A11000 Actuator
A125-A11000 Actuator
AS125-AS160 Actuator
Parker 74317 Solenoid
ASCO 8551 Solenoid
ASCO 8551 Solenoid
6)
Follow assembly steps 2) to 7) in reverse for assembly.
7)
Following solenoid replacement, refer to section 7 for valve testing.
Note:
For explosion proof solenoids, solenoid coil must be wired as per Class 1 Division 2 wiring methods using class 1
Division 2 rated sealing fittings as required.