17
E33 FPI Direct Vent Gas Insert
31)
Locate the ground lug at the receptical
box, left of the unit.
32)
Connect one end of the supplied green
ground wire to the lug with the nut and
washer from the kit.
33)
Install the 1/2" bushing to the heat shield.
Ground
wire from
kit
35)
Plug the DC spark generator wires to the
DC Sparker.
36)
Connect the ground wire to the DC
Sparker mounting bracket.
38)
Mount the heat shield to the DC Sparker.
Secure into place with the velcro, which is
provided in the kit.
40)
Tie up the loose wire with the wire clip.
Heat Shield
34)
Run the other end of the ground wire and
DC spark generator wires through the
bushing on the heat shield.
39)
Find a location which is not too hot and is
easy to reach for changing the
battery.
Installer Notice:
These instructions must be left
with the appliance.
41)
Check for gas leaks with a proper soapy
solution or leak detector.
42)
Check for proper spark between the
ignitor and pilot cap. Refer to "Lighting
Procedure" section of the manual for light-
ing sequence.
43)
Check pilot fl ames. Correct fl ame pattern
has 3 strong blue fl ames. Adjustment can
be made by turning the slotted screw at
the top right corner of the valve. Refer to
"Maintenance Instructions" section of the
manual for correct fl ame patterns.
44)
Check inlet (12" WC min) and outlet (11"
WC) pressures. Refer to "Gas Pipe Pres-
sure Testing" section of the manual.
45)
Check operation of fl ame control.
46)
Check for proper fl ame appearance and
glow on logs.
37)
Install the supplied battery into the DC Sparker
Box by opening the battery compartment.
NOTE:
The battery in the DC Sparker Box
will need to be replaced annually.
Battery
Compartment
INSTALLATION