VISAIR CABINETS - SERVICING
Dixell Default
Settings cont.
Label
Name
Range
Default Setting
AFH
Differential for temperature alarm recovery
(0,1 °C÷25,5°C) (1 °F÷45°F)
1
ALd
Temperature alarm delay
0 ÷ 255 min
15
dAO
Delay of temperature alarm at start up
0 ÷ 23h e 50’
1.3
AP2
Probe for temperature alarm of condenser
nP; P1; P2; P3; P4
P4
AL2
Condenser for low temperat. alarm
(-55 ÷ 150°C) (-67÷ 302°F)
-40
AU2
Condenser for high temperat. alarm
(-55 ÷ 150°C) (-67÷ 302°F)
110
AH2
Differ. for condenser temp. alarm recovery
[0,1 °C ÷ 25,5°C] [1 °F ÷ 45°F]
5
Ad2
Condenser temperature alarm delay
0 ÷ 254 (min.) , 255=nU
15
dA2
Delay of cond. temper. alarm at start up
0.0 ÷ 23h 50’
1,3
bLL
Compressor OFF for condenser low temperature alarm
n(0) - Y(1)
n
AC2
Compressor OFF for condenser high temperature alarm
n(0) - Y(1)
n
i1P
Digital input polarity
oP=opening; CL=closing
cL
i1F
Digital input configuration
EAL, bAL, PAL, dor; dEF; Htr, AUS
EAL
did
Digital input alarm delay
0÷255min
5
Nps
Number of activation of pressure switch
0 ÷15
15
odc
Compress status when open door
no; Fan; CPr; F_C
no
rrd
Regulation restart with door open alarm
n – Y
y
HES
Differential for Energy Saving
(-30°C÷ 30°C) (-54°F÷ 54°F)
0
Adr
Serial address
0÷247
1
PbC
Kind of probe
Ptc; ntc
ntc
onF
on/off key enabling
nu, oFF; ES
nu
dP1
Room probe display
--
--
dP2
Evaporator probe display
--
--
dP3
Third probe display
--
--
dP4
Fourth probe display
--
--
rSE
Set operating value
actual set
--
rEL
Software release
--
--
Ptb
Map code
--
--
XR40CX
Hot Key
To program the controller from a Hot Key:
Turn OFF the instrument and remove the probe Pr4 from the XR40 socket.
Insert a programmed Hot Key into the 5 PIN socket and then turn the
Controller ON.
The parameter list of the Hot Key is automatically downloaded into the
Controller memory, the
doL
will blink, followed a by a flashing
End
.
After 10 seconds the instrument will restart working with the new
parameters.
Remove the Hot Key and replace probe Pr4.
NOTE the message
Err
is displayed if programming fails. In this case turn the
unit off and then on again, if you want to restart the download again, or remove
the Hot Key to abort the operation.
Continued on next page
Содержание Visair IN-VA10-A004
Страница 1: ...Open Front Food Drinks Cabinet AS NZS ...
Страница 33: ...IN VA10 33 Future Products Group ELECTRICAL CIRCUIT DIAGRAMS Model IN VA10 A004 5 Visair Refrigerated Cabinets ...
Страница 35: ...IN VA10 35 Future Products Group MECHANICAL DRAWINGS Inline Visair IN VA10 A004 ...
Страница 36: ...Part No 25553 Rev J November 2017 36 Visair Refrigerated Cabinets Inline Visair IN VA10 A005 ...
Страница 37: ...IN VA10 37 Future Products Group ...
Страница 38: ...Part No 25553 Rev J November 2017 38 Visair Refrigerated Cabinets ...
Страница 39: ...IN VA10 39 Future Products Group ...
Страница 40: ...Part No 25553 Rev J November 2017 ...