IL-C-DRW-A001/A003
- 11 -
© Future Products Group
TROUBLE SHOOTING
FAULT
POSSIBLE CAUSE
REMEDY
Cabinet does not
operate/start
The mains isolating switch on
the wall, circuit breaker or fuses
are off at the power board
Turn isolating switch circuit
breaker or fuses on
High pressure switch tripped
Switch cabinet off and on.
Clean condenser and radiator
Check gas pressure
Low pressure switch tripped
The power switch on the cabinet
is OFF
Turn the power switch ON
The power switch is faulty
Have the switch replaced
Cabinet does not reach
correct temperature
The drawer is open
Close drawer and re-test
temperature after thirty minutes
Ventilation grills are blocked
Vacuum or remove blockage
Evaporator coil fins blocked
Clean coil fins of food etc.
Thermostat needs adjustment
Adjust controller
Ambient temperature > 25
C
Adjust store air conditioning
Damaged drawer seal
Replace drawer seal
Evaporator coil iced up
De-ice coil
Condenser radiator blocked
Remove dust and debris
Controller faulty
Replace Dixell controller
Temperature probe damaged
Replace temperature probe
Auto defrost faulty
Have defrost settings checked
Fans not operating
Have fans checked/replaced
Excess external
condensation
Frame heating is not working
Check/replace power supply
Drawer hard to open
Debris in track
Clean door tracks (see cleaning)
Drawer runner damaged
Have runner replaced
Service
Personnel Only
The table entries in
italics
indicate actions to be taken only by qualified Service
Personnel.