Equalization mode
Battery equalization enabled
Battery equalization disabled
(default)
This item is selectable when item 05 is set to either FLOOD or USER
DEFINED
34
Equalization mode
Default setting: 14.6V
- Selection range: 12.0V to 14.6V
Increments of 0.1V per click.
35
Equalization time
60min (default)
The time allowed for the
equalization to take place. The
duration ranges from 5min to
900min. Increments are set to
5min per click
36
Equalization timeout
120min (default)
The maximum time permitted for
equalization. The duration ranges
from 5 min to 900 min. Increment
of 5 min per click
37
Equalization time
30 days (default)
The days between automatic
equalization cycles. The duration
ranges from 0 min to a maximum
of 90 days. Increments of 1 day
per click
38
AC output, neutral and
ground connect
Disable:
neutral and ground conductors of the of AC output are
disconnected (default)
Enable:
the inverter can deliver a signal to trigger the grounding box to
short neutral and earth connections.
Neutral and ground of AC output are connected
This function is only available when the inverter operates with an
external grounding box. The signal will only be triggered when the
inverter is on in battery mode