29
Model
Load (VA)
Backup time at 12VDC/100Ah (min)
Backup time at 12VDC/200Ah (min)
1KW
100
766
1610
200
335
766
300
198
503
400
139
339
500
112
269
600
95
227
700
81
176
9. Approximate runtime chart
Note:
Backup time depends on the quality, age and type of the battery.
Specifications of batteries may vary depending on different manufacturers.
10. Technical specifications
Table 1
Line mode specifications
INVERTER MODEL
1KW
Input voltage waveform
Sinusoidal (utility or generator)
Nominal input voltage
110/120VAC
Low-loss voltage
95VAC±7V(UPS)
65VAC±7V (appliances)
Low-loss return voltage
100VAC±7V (UPS)
70VAC ±7V (appliances)
High-loss voltage
140VAC±7V
High-loss return voltage
135VAC±7V
Max AC input voltage
150VAC
Nominal input frequency
60Hz / 50Hz (autosensing)
Low-loss frequency
40±1Hz
Low-loss return frequency
42±1Hz
High-loss frequency
65±1Hz
High-loss return frequency
63±1Hz
Power factor
1
Output short-circuit protection
Line mode: circuit breaker
Battery mode: electronic circuits
Efficiency (line mode)
>95% (rated R load, battery fully charged)
Transfer time
10ms typical (UPS
20ms typical (appliances)
Output power derating:
When AC input voltage drops to 95V,
the output power will be derated
Output power
Rated power
50% power
65V
95V
140V
Input Voltage
Содержание FIO-P11K12
Страница 1: ...1KW User Manual 2 y ear w arran ty Off grid hybrid solar inverter and charger FIO P11K12...
Страница 34: ...NOTES...
Страница 35: ...NOTES...
Страница 36: ......