14: Charger boost voltage setting

Interface

Setting

Parameter 2:

 Use this setting to configure the boost voltage 

level. 

2.25-2.40:

 Sets the charger boost voltage from 2.25 to 2.40 

V/cell.  (Default is set  at 2.36V/cell) 

15: Charger float voltage setting

Interface

Setting

Parameter 2:

 Use this setting to determine the float voltage 

level. 

2.20-2.33: 

Sets the charger float voltage from 2.20 to 2.33V/cell 

(Default is 2.28V/cell)

16: EPO relay setting

Interface

Setting

Parameter 2:

 Use this setting to configure the EPO circuit 

control. 

AO:

 Active Open (Default). When AO is selected as the normal 

configuration, it will enable the EPO function when Pin 1 and 

Pin 2 are opened. 

AC:

 Active Close. When AC is selected as the normal configu-

ration, it will enable the EPO function when Pin 1 and Pin 2 are 

closed.

17: External output isolation transformer 

Interface

Setting

Parameter 2:

 Allow or disallow the connection of an external 

output isolation transformer 

ENA:

 If selected, the UPS will be allowed to connect to an 

external output isolation transformer.

DIS:

 If selected, the UPS will be denied to connect to external 

output isolation transformer. (Default)

18: Runtime setting display

Interface

Setting

Parameter 2:

 Use this setting to configure the runtime on the 

display. 

EAT:

 If EAT is selected, it will show the estimated runtime on 

the screen (Default)

RAT:

 If RAT is selected, it will show the runtime accumulated up 

to this point. 

19: Acceptable input voltage range setting 

Interface

Setting

Parameter 2:

 Use this menu to set the acceptable high voltage 

point and acceptable low voltage point for the input voltage by 

pressing the 

Down

 or 

Up

 key.

HLS:

 Input high-voltage point

For 200/208/220/230/240 VAC models:

280/290/300:

 sets the high-voltage point in parameter 2. 

(Default: 300VAC)

LLS:

 Bypass low-voltage point

For 200/208/220/230/240 VAC models:

110/120/130/140/150/160:

 sets the low-voltage point in

parameter 2. (Default: 110VAC)

00: Exit setting

Interface

Setting

Exits the configuration mode.

Содержание FDC-2012R-I

Страница 1: ...2 y e a r w a r r a n t y Ajustes 05_19_2017 User Manual Uninterruptible Power Supply System FDC 2012R I FDC 3012R I ...

Страница 2: ...ertified electrical cables for input and output connections During the installation of this equipment make sure that the sum of the leakage currents of the UPS and the connected loads shall not exceed 3 5 mA CAUTION The unit is heavy Lifting the unit requires a minimum of two people 1 4 Important safety instructions Do not disconnect the mains cable on the UPS system or the building wiring outlet ...

Страница 3: ...e of damage be found or if some parts are missing do not turn the UPS on you must immediately notify the carrier or dealer where you purchased the unit 2 2 UPS diagram Front view Rear view FDC 2012R I FDC 3012R I 1 Programmable outlets for non critical loads 2 Dedicated outlets for critical loads 3 AC input 4 Modem phone network surge protection 5 USB communication port 6 RS 232 communication port...

Страница 4: ...tep 3 Verify that the UPS is stable and firmly attached to the base Intelligent slot RS 232 port USB port To allow for unattended UPS shutdown start up and status monitoring connect one end of the communication cable to the USB RS 232 port and the other end to the communication port of your PC With the monitoring software installed you can schedule UPS shutdown start up and monitor its status thro...

Страница 5: ...nter button Select button ON Mute Select button Turn on the UPS Press and hold the ON Mute button for at least 2 seconds to turn on the UPS Mute the alarm When the UPS is on battery mode press and hold this button for at least 3 seconds to disable or enable the alarm system This command would not apply when warnings or errors occur Up key Press this button to display previous selection in the UPS ...

Страница 6: ...oltage output voltage and output frequency V voltage Hz frequency Indicates that the programmable management outlets are working Indicates that the UPS is connected to utility power Indicates that the battery is working Indicates the charging status Indicates the UPS is working in bypass mode Indicates the UPS is working in ECO mode Indicates the UPS is working in converter mode Battery level indi...

Страница 7: ... 50 The output frequency is set to 50Hz CF 60 The output frequency is set to 60Hz Parameter 2 Activates or cancels the ECO mode Two options are available ENA ECO mode enable DIS ECO mode disable Default Parameter 2 Use this menu to set the acceptable high voltage point and low voltage point for ECO mode by pressing Down key or Up key HLS High loss voltage in ECO mode For 200 208 220 230 240 VAC mo...

Страница 8: ...feature ENA Programmable outlets enabled DIS Programmable outlets disabled Default 10 Backup time setting for programmable outlets Interface Setting Parameter 2 Sets the backup time limits for the programmable outlets 0 999 Use this setting to define the programmable outlets backup time in minutes from 0 999 in order to connect non critical devices on battery mode Default 999 12 Battery total Ah s...

Страница 9: ...he connection of an external output isolation transformer ENA If selected the UPS will be allowed to connect to an external output isolation transformer DIS If selected the UPS will be denied to connect to external output isolation transformer Default 18 Runtime setting display Interface Setting Parameter 2 Use this setting to configure the runtime on the display EAT If EAT is selected it will sho...

Страница 10: ...in acceptable range the UPS will supply pure and stable AC power to connected loads The UPS will also charge the battery while in online mode ECO mode Efficiency Corrective Optimizer Frequency converter mode Energy saving mode When the input voltage is within the voltage regulation range the UPS will bypass voltage to loads for energy saving The UPS will also charge the battery while in ECO mode W...

Страница 11: ... beeping every second Fault code 49 becomes illuminated and the alarm starts beeping continuously Fault code 43 becomes illuminated along with the icon on the LCD display and the alarm starts beeping continuously Battery backup time is shorter than its nominal value Charge the batteries for at least 5 hours and then check their capacity If the problem persists consult your dealer Batteries are not...

Страница 12: ...gement software Environment Operating temperature Storage temperature Relative humidity Operating altitude Audible noise Physical appearance Dimensions Weight Cord length Additional information Warranty 2000VA 2000W 3000VA 3000W Double conversion 200 240VAC 175VAC 155VAC 135VAC 125VAC 3 based on load percentage 100 80 80 70 70 60 60 0 Low line transfer voltage 10V 300VAC 3 High line transfer volta...

Страница 13: ......

Отзывы: