6. Specifications
* Derate capacity to 60% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 208VAC.
Charge the UPS for at least 5 hours before storing the unit. Cover the UPS, and place it upright in a cool, dry location.
During storage, recharge the battery in accordance with the following table:
Storage
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient
temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer or
service center.
5. Storage and maintenance
Batteries must not be discarded as regular household waste! As part of the
company’s eco-friendly approach, we encourage you to follow all applicable local
waste regulations to dispose of your used devices and batteries properly.
MPN
FDC-1000T
General
Input
Output
Battery
Alarms/Indicators
Physical appearance
Additional information
Capacity
1000VA/800W
Double conversion
100-127VAC
40Hz-70Hz
NEMA 5-15P
100-127VAC
47Hz-53Hz or 57Hz-63Hz
>88%
Pure sine wave
3 NEMA 5-15R
0ms
4ms
12V/9Ah (2)
14 min at full load
4 hours to 90% capacity
22lb
3.75ft
Battery mode:
Sounds every 4 seconds
Low battery:
Sounds every second
Overload:
Sounds every 0.5 second
Fault: Continuous sound
Graphical LCD with blue
backlight
11.1x5.7x8.7in
Two years for UPS,
One year for battery
50Hz ± 0.25Hz or
60Hz ± 0.3Hz
0.99 at 100% load
Topology
Nominal voltage
Frequency
Power factor
AC plug style
Nominal voltage
Frequency (synchronized)
Frequency (battery)
Efficiency (AC mode)
Waveform
Battery type and quantity
Backup time
Recharge time
Visual indicators
Audible
Cord length
Product dimensions
Product weight
Warranty
Communication ports
Included
FDC-2000T
3.75ft
15.6x 5.7x8.7in
38lb
Two years for UPS,
One year for battery
2000VA/1600W
Double conversion
100-127VAC
40Hz-70Hz
0.99 at 100% load
NEMA 5-15P
100-127VAC
47Hz-53Hz or 57Hz-63Hz
>88%
Pure sine wave
4 NEMA 5-15R
0ms
4ms
12V/9Ah (4)
14 min at full load
4 hours to 90% capacity
Battery mode:
Sounds every 4 seconds
Low battery:
Sounds every second
Overload:
Sounds every 0.5 second
Fault: Continuous sound
Graphical LCD with blue
backlight
50Hz ± 0.25Hz or
60Hz ± 0.3Hz
Included
FDC-1002T
3.75ft
11.1x5.7x8.7in
22lb
Two years for UPS,
One year for battery
1000VA/800W
Double conversion
220VAC
40Hz-70Hz
0.99 at 100% load
NEMA 5-15P
220VAC
50/60Hz (60/50Hz)
± 0.5%
>88%
Pure sine wave
3 NEMA 5-15R
0ms
4ms
12V/9Ah (2)
14 min at full load
4 hours to 90% capacity
RS-232, USB,
SNMP card (optional)
RS-232, USB,
SNMP card (optional)
RS-232, USB,
SNMP card (optional)
Battery mode:
Sounds every 4 seconds
Low battery:
Sounds every second
Overload:
Sounds every 0.5 second
Fault: Continuous sound
Graphical LCD with blue
backlight
ForzaTracker
ForzaTracker
ForzaTracker
50Hz (60Hz) ± 0.5%
Included
FDC-2002T
3.75ft
15.6x 5.7x8.7in
38lb
Two years for UPS,
One year for battery
2000VA/1600W
Double conversion
220VAC
40Hz-70Hz
0.99 at 100% load
NEMA 5-15P
220VAC
50/60Hz (60/50Hz)
± 0.5%
>88%
Pure sine wave
4 NEMA 5-15R
0ms
4ms
12V/9Ah (4)
14 min at full load
4 hours to 90% capacity
RS-232, USB,
SNMP card (optional)
Battery mode:
Sounds every 4 seconds
Low battery:
Sounds every second
Overload:
Sounds every 0.5 second
Fault: Continuous sound
Graphical LCD with blue
backlight
ForzaTracker
50Hz (60Hz) ± 0.5%
Included
USB management
Transfer time (inverter to bypass)
Total outlets
Transfer time (line to battery)
Power management
software
Содержание FDC-1000T