Hardware installation
Shutting down and removing a FortiGate-5001D board
FortiGate-5001D Security System Guide
01-500-0242101-20151109
19
http://docs.fortinet.com/
9
Once the board is inserted correctly, fully tighten the retention screws to lock the
FortiGate-5001D board into position in the chassis slot.
Shutting down and removing a FortiGate-5001D board
The following procedure describes how to correctly use the FortiGate-5001D mounting
components described in
“FortiGate-5001D mounting components” on page 16
to
remove a FortiGate-5001D board from an ATCA chassis slot.
FortiGate-5001D boards are hot swappable. The procedure for removing
a FortiGate-5001D board from a chassis slot is the same whether or not the chassis is
powered on.
To remove a FortiGate-5001D board from a chassis slot
To complete this procedure, you need:
•
An ATCA chassis with a FortiGate-5001D board installed
•
An electrostatic discharge (ESD) preventive wrist strap with connection cord
1
Shut down the operating system running on the FortiGate-5001D board. For example:
• From the web-based manager, go to
System > Status
and from the
Unit Operation
widget, select
Shutdown
and then select
OK
.
• From the CLI enter
execute shutdown
2
Attach the ESD wrist strap to your wrist and to an available ESD socket or wrist strap
terminal.
3
Disconnect all cables from the FortiGate-5001D board, including all network cables,
the console cable, and any USB cables or keys.
Tighten
Retention
S
crew
To avoid potential hardware problems, always shut down the FortiGate-5001D operating
system (FortiOS) properly before power cycling the FortiGate-5001D board.
Do not carry the FortiGate-5001D board by holding the handles or retention screws.
When inserting or removing the FortiGate-5001D board from a chassis slot, handle the
board by the front panel. The handles are not designed for carrying the board. If the
handles become bent or damaged the FortiGate-5001D board may not align correctly in
the chassis slot.
FortiGate-5001D boards must be protected from static discharge and physical shock.
Only handle or work with FortiGate-5001D boards at a static-free workstation. Always
wear a grounded electrostatic discharge (ESD) preventive wrist strap when handling
FortiGate-5001D boards.