• Burden 0.005VA per phase Max at 11Amps
• 5mA Pickup Current
• Pass through wire gauge dimension: 0.177" / 4.5mm
• Continuous current withstand: 20 amps for screw terminated or pass through
current connections
2.3 Isolation
All Inputs and Outputs are galvanically isolated to 2500 Volts AC.
2.4 Environmental Rating
Storage: (-25 to +70)° C
Operating: (-10 to +65)° C
Humidity: to 75% RH Non-Condensing
Faceplate Rating: NEMA12 (Water Resistant)
Environment : IP54 standard, IP65 optional
Mounting Gasket Included
2.5 Sensing Method
• RMS
• Sampling at 120+ Samples per Cycle on all channels measured readings
simultaneously
• Harmonic %THD (% of Total Harmonic Distortion)
2.6 Update Rate
• Watts, VAr and VA-100msec
• All other parameters-1second
2.7 Power Supply
Option D2:
• (65 to 275) Volts AC and (90 to 380) Volts DC. Universal AC/DC Supply
Option D:
• 18-60VDC Burden: 10VA max.
2.8 Communication Format
• 2 Com Ports (Back and Face Plate)
• RS485 Port (Through Back Plate)
• Com Port Baud Rate: (1200 to 115200)
• Com Port Address: 0-247
• 8 Bit, No parity
• Modbus RTU Protocols