31
0x0416
1046
Channel 23 current value
short
Unit 10mA, default 0
0x0417
1047
Channel 24 current value
short
Unit 10mA, default 0
0x0418
1048
Total reverse current
short
Unit 100mA, default 0
0x0419
1049
Total current
short
Unit 100mA, default 0
0x041A
1050
Average current
short
Unit 10mA, default 0
0x041B
1051
Total power
short
Unit 1000W, default 0
0x041C
1052
Average power
short
Unit 10W, default 0
0x041D
~
0x0434
1053
~
1076
Channel 1 ~ 24 power
short
Unit 10W, default 0
FR-DCMG-HS4Q Hall special register Large-scale energy information
(0x0500-0x0540)
0x0500
1280
The higher 16bit of the total
generated energy
Unsigned
short
Unit 10Wh, default 0
0x0501
1281
The lower 16bit of the total
generated energy
Unsigned
short
Unit 10Wh, default 0
0x0502
1282
The higher 16bit of the
generated energy of
channel1
Unsigned
short
Unit 10Wh, default 0
0x0503
1283
The lower 16bit of the
generated energy of
channel1
Unsigned
short
Unit 10Wh, default 0
.......
......
......
......
....
0x0539
1343
The higher 16bit of the
generated energy of
channel24
Unsigned
short
Unit 10Wh,default 0
0x0540
1344
The lower 16bit of the
generated energy of
channel24
Unsigned
short
Unit 10Wh,default 0
System information configuration (0x0B00-0x0B24)
0x0B00
2816
Alarm release
Unsigned
Short
The percentage of the alarm threshold is
used as the alarm release threshold.
Unit %, default 2, setting range 0 to 100
W/R
0x0B01
2817
Bus voltage alarm low
threshold
Unsigned
short
Unit V, default 300
W/R
0x0B02
2818
Bus voltage alarm high
threshold
Unsigned
short
Unit V, default 1000
W/R
0x0B03
2819
Temperature sensor 1
short
Unit 0.1 ° C, default 800, setting range is
W/R