background image

 

________________________________________________________________________________ 

 

25 

      

AST 14 C 152/00

 

 

7.3  POSITIONING OF TERMINALS 

 

For the wall positioning of the discharge terminals of the boiler, in the cases provided for in 
DPR n° 551 dated 29/12/99, observe the distances indicated in the following table: 

 

POSITIONING OF THE TERMINALS – FORCED DRAUGHT 

(extract from  standard UNI  7129)

 

POSITION OF THE TERMINAL 

 

 

Under window 

600 

Under ventilation opening  

600 

Under gutter 

300 

Under balcony (1) 

300 

From an adjacent window  

400 

From an adjacent ventilation opening 

600 

From vertical pipes or discharges (2) 

300 

From the corner of a building   

300 

From the concave part of the building 

300 

At ground level  

2500 

Between two terminals, vertically 

1500 

Between two terminals, horizontally 

1000 

From a frontal surface without openings or terminals within a radius 
of 3 metres from the smoke outlet 

2000 

The same, but with openings or terminals within a radius of 3 metres 
from the smoke outlet 

3000 

 

Note: 
(1) T erminals under a balcony in use must be positioned in such a position that the total distance of the exhaust fumes, from the exit point of the same from 
the terminal to the outlet from the external perimeter of the balcony, including the height of any protective railing, is not less than 2000 mm. 
(2) In the positioning of the terminals, distances no shorter than 500 mm must be adopted from materials which are at risk from the action of the combustion 
products  (for  example,  gutters  made  of  plastic  materials,  wooden  structures,  etc.)  without  adopting  adequate shielding  precautions  in  relation  to  said 
materials. 

 

 

POSITIONING OF THE TERMINALS

 

Содержание Libra Dual BTFS 24

Страница 1: ...UAL FAMILY Wall hung boilers GROUP Aqua Premium compact with excludable water tank MODELS Nias Dual BTFS Libra Dual BTFS CODE AST 14 C152 00 ______________________________________________ 1 st Edition...

Страница 2: ...Gas valve SIT 845 4 2 Gas conversions 4 3 Gas valve regulation 4 4 Chimney sweep function ___________________Page 16 CHAPTER 05 HYDRAULIC GROUP 5 1 Complete hydraulic group 5 2 Secondary plate heat ex...

Страница 3: ...itre water tank excludable by the user Fondital version Model with reduced depth placed inside a metal casing to be built into the external wall Output 24 28 and 32 kW LIBRA DUAL BTFS ENCASED Instanta...

Страница 4: ..._________________________________________________________________ 4 AST 14 C 152 00 1 2 DIMENSIONS Nias and Libra Dual BTFS indoor ELECTRIC PROTECTION IP44 Nias and Libra Dual BTFS in wall ELECTRIC PR...

Страница 5: ...HW plate heat exchanger Hydraulic group DHW plate Control board Electronic board Flow pressare switch CH pump Flow meter Safety valve DHW pump Two way valve Ignition transformer CH expansion vessel DH...

Страница 6: ...time when the aqua premium turns on The system keeps the water in the tank at 10 C higher than the set DHW temperature WATER TANK TIMES 24 kW about 6 minutes and 30 seconds 28 kW about 5 minutes and...

Страница 7: ..._____ 7 AST 14 C 152 00 When the water tank switch is off the DHW pump and the two way interception valve are not active in this situation the boiler operates as a standard instantaneous boiler HEATIN...

Страница 8: ...s a quantity of DHW less than the quantity permitted by a flow regulator placed after the plate heat exchanger 8l min for 24kW 10l min for 28 Kw and 12l min for the model with 32 Kw output Example if...

Страница 9: ...d by the plate heat exchanger of the appliance the user is in a position to make use of a significant quantity of hot water in a determined space of time until the stratified water tank has been compl...

Страница 10: ...se of normal operation of the boiler or warn in the case ofmalfunctioning or shut down of the boiler INDICATION LIGHTS DURING NORMAL OPERATION OF THE BOILER 2 3 4 5 6 7 Condition Red Red Red Red Red R...

Страница 11: ...N L OFF OFF Smoke ther mostat press shut down X OFF OFF ON L OFF OFF OFF OFF Flow probe malfunction X ON L OFF OFF OFF OFF OFF ON L DHW probe malfunction X ON L OFF OFF OFF OFF OFF OFF Water tankprobe...

Страница 12: ...east 15 minutes have elapsed ATTENTION The anti freeze function only protects the boiler it does not protect the entire heating system To protect the heating system with the boiler in the anti freeze...

Страница 13: ...trol panel Electronic safety board and integrated modulation Electronic ignition with separate transformer Flue gas pressure switch Gas valve with double shutter 3 2 OPERATING CHARACTERISTICS DHW prio...

Страница 14: ...diameter mm min max Methane Gas G20 30 5 28 4 10 0 20 1 35 1 3 11 5 Butane Gas G30 30 5 28 4 10 0 29 0 80 3 5 28 5 Propane Gas G31 30 5 28 4 10 0 37 0 80 4 5 33 0 Instantaneous DHW supply t 30 C 13 li...

Страница 15: ...aximum DHW working temperature C 62 62 62 Total capacity of expansion vessel L 8 10 10 Maximum recommended CH system capacity L 160 200 200 Value rel ated to 15 C 1013 mbar condition Maxi mum temperat...

Страница 16: ...GAS VALVE SIT 845 MAX MIN RESISTANCE VALUES OF THE COILS EV1 880 Ohm at 220 Vac EV2 6900 Ohm at 220 Vac RESISTANCE VALUES OF THE REGULATION COIL 78 2 Ohm Gas inlet pressure check Gas outlet pressure c...

Страница 17: ...c board and position the MET LPG jumper to the LPG position see the photo below Now proceed with the adjustment of the gas valve next page CONVERSION FROM LPG TO NATURAL GAS Check that the boiler is d...

Страница 18: ...gas while holding still the external screw check correct operation of the burner verifying that the ignition is proper and quiet act on PACC trimmer of the electronic board when necessary in order to...

Страница 19: ...THE HYDRAULIC GROUP OF NIAS LIBRA DUAL BOILER WAS DESIGNED COMPLETLEY BY FONDITAL ENGINEERS AS WITH ALL OF THE OTHER HYDRAULIC GROUPS OF OUR BOILERS DHW and CH probe parameters 10Kohm at 25 C with 343...

Страница 20: ...ONDARY PLATE HEAT EXCHANGER ALFA LAVAL 24 kW 22 plates 28 kW 26 plates 32 kW 26 plates 5 3 THREE WAY VALVE 5 4 2 WAY INTERCEPTION VALVE Maximum working temperature 88 C Maximum working pressure 3 Bar...

Страница 21: ...h micro water tank In position F6MAC reserved for future developments F2PIA F3RIS F4BOI F5MIC F6MAC Nias and Libra Dual boilers must have the Jumper positioned in the position F2PIA like an instantane...

Страница 22: ..._______________________________________________________________________________ 22 AST 14 C 152 00 6 3 ELECTRONIC BOARD DIAGRAM Indoor only boiler Standard for ENCASED boiler Optional for INDOOR boile...

Страница 23: ...r temperature and the programmed in door temperature the correction depends on the setting of the thermoregulation coefficient KT by means of the trimmer Vmin The boiler electronics recognize the pres...

Страница 24: ...h the exception of B22 Discharge BTFS 24 each 90 wide radius bend equals 1 5 m in length each 90 narrow radius bend equals 3 5 m in length Discharge BTFS 28 each 90 wide radius bend equals 2 m in leng...

Страница 25: ...two terminals vertically M 1500 Between two terminals horizontally N 1000 From a frontal surface without openings or terminals within a radius of 3 metres from the smoke outlet O 2000 The same but wi...

Страница 26: ...y leakage gas supply pressure to boiler minimum and maximum gas pressures to boiler nozzles boiler ignition boiler combustion parameters by analysis of flue this is to be performed once every tw o yea...

Страница 27: ...ce if necessar y Silicone pipes are disconnected or faulty Reconnect or repl ace silicone pipes Insufficient air intake or flue gas discharge Checkair flue gas ducts unclog or replace as needed Fan is...

Отзывы: