Malfunctions, possible causes and solutions
BOILER STATUS
MALFUNCTION
PROBABLE CAUSE
USER'S TASKS
QUALIFIED PERSONNEL'S
TASKS
E41**
No communication between
board and peripheral devices
(panel interface and/or zone/
solar boards).
Interface display is
disconnected.
Contact qualified personnel
Reconnect it.
Zone/solar boards are
disconnected.
Contact qualified personnel
Reconnect them.
Interface display and/or zone/
solar boards are faulty.
Contact qualified personnel
Replace them.
E42
Solar system setting error.
Wrong boiler board or solar
board setting parameters.
Contact qualified personnel
Check that the P03 and P18
parameter set values match
with those specified on the
reference tables.
E43
Zone configuration error.
Wrong setting of P61
parameter.
Wrong boiler board setting
parameters.
Contact qualified personnel
Check that the P61 parameter
set values match with those
specified on the reference
tables.
E44**
Ambient probe 1 failure.
Ambient probe is
disconnected.
Contact qualified personnel
Reconnect it.
Ambient probe is faulty.
Contact qualified personnel
Replace it.
E45**
Ambient probe 2 failure.
Ambient probe is
disconnected.
Contact qualified personnel
Reconnect it.
Ambient probe is faulty.
Contact qualified personnel
Replace it.
E46
Pressure transducer failure.
Pressure transducer is
disconnected.
Contact qualified personnel
Reconnect it.
Pressure transducer is faulty.
Contact qualified personnel
Replace it.
E47
External probe with connected
ambient probe error.
External probe is disconnected.
Contact qualified personnel
Reconnect it.
External probe is faulty.
Contact qualified personnel
Replace it.
E49
The interface does not work.
The interface does not
communicate with the boiler
board.
Contact qualified personnel
Replace it.
E80*
The ∆T between flow and
return is not within the limits.
Flow and/or return probes are
faulty.
Contact qualified personnel
Replace them.
Obstructed bypass pipe
Contact qualified personnel
Remove any obstructions, or
replace the pipe.
The bypass valve is not
assembled or wrongly
assembled.
Contact qualified personnel
Restore bypass valve correct
assembling.
Heat exchanger primary circuit
is obstructed.
Contact qualified personnel
Clean or replace the exchanger.
E86*
Flow temperature increases
too quickly.
Pump is seized.
Contact qualified personnel
Unseize the pump.
Pump is faulty.
Contact qualified personnel
Replace it.
Air present inside heating
system.
Contact qualified personnel
Bleed the air from the boiler
by opening the jollies on the
exchanger and pump.