44
Technical features and dimensions
Description
um
Max. output
Min. output
30% load
Casing heat loss with burner on
%
0.61
6.52
-
Casing heat loss with burner off
%
0.21
Flue system heat loss with burner on
%
2.69
2.08
-
Flue system mass capacity
g/s
12.43
1.33
-
Flue temp. – air temp.
°C
61
33
-
Heat output efficiency rating (60/80°C)
%
96.7
91.4
-
Heat output efficiency rating (30/50°C)
%
105.1
104.9
-
30% heat output efficiency rating
%
-
-
106.5
Efficiency rating (according to 92/42/EC)
-
NOx emission class
-
5
Tab. 5 Combustion specifications KBS 24
Description
um
Max. output
Min. output
30% load
Casing heat loss with burner on
%
0.87
5.10
-
Casing heat loss with burner off
%
0.19
Flue system heat loss with burner on
%
2.33
2.00
-
Flue system mass capacity
g/s
15.81
1.87
-
Flue temp. – air temp.
°C
60
40.5
-
Heat output efficiency rating (60/80°C)
%
96.8
92.9
-
Heat output efficiency rating (30/50°C)
%
106.2
104.8
-
30% heat output efficiency rating
%
-
-
108.3
Efficiency rating (according to 92/42/EC)
-
NOx emission class
-
5
Tab. 6 Combustion specifications KBS 32