TECHNICAL DATA AND INSTRUCTIONS 

CE 0051

GB

CLASSIC

G 009 - 04

G a s   r a d i a t o r s

Содержание gazelle techno classic

Страница 1: ...TECHNICAL DATA AND INSTRUCTIONS CE 0051 GB CLASSIC G 009 04 G a s r a d i a t o r s ...

Страница 2: ...book contains instructions for the fitter and user on how to install use and service these appliances Gas appliances must be installed by an approved company in compliance with current legislation Gas radiators must only be serviced by properly qualified personnel possessing the requisites prescribed by law IMPORTANT ...

Страница 3: ...ard The radiator must be installed by a professionally qualified person in compliance with legal requirements and following the manufacturer s instructions A professionally qualified person means anyone having specific technical skills in the area of component parts for domestic heating systems and being qualified under the current regulations For the radiator to work correctly andefficiently itmu...

Страница 4: ...__________________________ page 8 3 Instructions for the installer___________________________________________________ page 9 3 1 Choosing a location___________________________________________________________ page 9 3 2 Installation___________________________________________________________________ page 10 3 2 1 Straight wall flue system___________________________________________________ page 10 3 ...

Страница 5: ...tor switches off due to a malfunction press to reset and resume operation see 1 3 2 If the radiator locks out again both red lights on do not reattempt to start it up Contact a Service Centre for assistance 1 INSTRUCTIONS FOR THE USER Always ensure to have first ingnition performed by professional personnel only WARNING 1 1 CONTROL PANEL AND SETTINGS A on off main switch B timer clock C temperatur...

Страница 6: ...et button L If the radiator still does not start up after the second attempt contact a Service Centre for assistance In the event of a shutdown due to overheating with light H on contact a Service Centre for assistance Always check that the grilles and the air intake and flue terminal are free from obstructions such as foreign bodies material or the like Also make sure that the radiator is not cov...

Страница 7: ...ng moving curtain before switching on the radiator pull the curtain about 30 cm away from it fixed curtain the lower edge must be at least 30 cm from the radiator Do not place containers of water on the radiator This is because any spillage would damage the appliance and cause the risk of electrocution Never touch the hot air grilles when the radiator is on This is to avoid getting burnt If the ro...

Страница 8: ...ation in case of overheating Temperature probe on the heat exchanger 5000 and 7000 models only able to stop the radiator operation in case of overheating Main features of the GAZELLE TECHNO CLASSIC radiator High efficiency finned heat exchanger made of die cast aluminium Two channel heat recuperator made of die cast aluminium Separate and extendable air intake and flue gas outlet pipes Combustion ...

Страница 9: ...round see fig 7 Remove the foam polystyrene protection and remove the painted casing taking care not to damage it To do this remove the two screws one on either side at the bottom Remember to replace them afterwards Use the specific hexagonal spanner provided see the picture below If the wall is made partly or entirely of flammable material insulate the flue gas pipe with rock wool at least 1 cm t...

Страница 10: ...d with a supporting bracket Alternatively air intake flue gas pipes can also be installed directly to the gas radiator In this case please follow this procedure Mount gasket D on adaptor F fig 14 Fit adaptor F into stub pipe C fig 9 and fix it to the base of the appliance using the screw Y provided pic 14 C Fit the Ø 35 mm pipe or the 90 elbow onto the adaptor inserting gasket G between the adapto...

Страница 11: ...special counter frame provided as an optional figs 8 and 17 Important keep the flue gas terminal above the air intake flue terminal When using the split pipe adaptor KIT the gas radiator can be positioned at a later time than the air intake flue gas pipes the kit contains a leaflet with instructions for installation Please refer to the following pictures for split pipe adaptor KIT application samp...

Страница 12: ...ameter of the pipes used 35 or 60 mm Compulsory with air intake pipes if the total load loss air intake flue gas outlet is less than or equal to 4 Pa Compulsory with air intake pipes if the load loss on the air intake pipe is less than or equal to 4 Pa GAZELLE TECHNO CLASSIC 3000 5000 Maximum load loss Pa 8 12 Outside diameter of the pipe mm 35 60 35 60 Starting 90 elbow for twin pipe adaptor Pa 2...

Страница 13: ... 12 Pa Air intake Pipe diameter 35 mm length 30 cm 2 x 0 30 0 6 Pa Air intake terminal 0 5 Pa The load loss on the air intake pipe is 1 1 Pa which is less than 4 Pa therefore the diaphragm must be mounted on the air intake pipe as specified in a note to table 2 Load loss with the diaphragm 2 Pa Flue gas outlet 1 pipe diameter 35 mm length 35 cm 2 x 0 35 0 7 Pa 90 elbow diameter 35 mm 2 Pa 35 60 ad...

Страница 14: ...at or the telephone dialler to the free terminal fig 21 N B To control the radiator efficiently using the external room thermostat turn temperature regulator C fig 1A fully clockwise to the maximum setting If an external programmer is connected set the timer clock to on I constant see sub section 1 3 4 fig 5 To control more than one radiator using a single timer thermostat connect terminal 3 of th...

Страница 15: ...al gas paragraph Natural gas To adjust maximum pressure undo the screw and insert the measuring instrument in pressure check point A Then unscrew the plug of pressure regulator B and with the radiator on maximum power turn the screw below to regulate the pressure at the injector which must not exceed the values shown in the table of technical data page 17 To adjust minimum pressure undo the screw ...

Страница 16: ...Wash and dry with a blast of air The Venturi tube is blocked Clean it Wrong phase neutral connection Check that the connection sequence is as specified in fig 22 The main burner ignites but goes out immediately and the radiator shuts down The flame detector cable is disconnected Reconnect it The detection electrode has short circuited Replace it Excess air in the burner Bleed the gas system comple...

Страница 17: ...90 90 Gas supply pressure mbar 20 29 37 Maximum gas pressure at the injector mbar 13 4 29 37 Minimum gas pressure at the injector mbar 7 5 15 2 19 P at maximum output Pa 54 56 54 56 54 56 Ø of air intake pipe diaphragm for straight flue gas duct up to 59 cm mm 18 18 18 Ø of air intake pipe diaphragm for split pipe system see table 2 mm 25 25 25 Standard consumption of natural gas m3 h 0 317 Standa...

Страница 18: ...s pressure at the injector mbar 7 5 16 8 21 P at maximum output Pa 58 62 58 62 58 62 Ø of air intake pipe diaphragm for straight flue gas duct up to 59 cm mm 22 5 oval 22 5 oval 22 5 oval Ø of air intake pipe diaphragm for split pipe system see table 2 mm 25 25 25 Standard consumption of natural gas m3 h 0 719 Standard consumption of LPG kg h 0 537 0 526 CO2 at maximum output 8 7 10 8 10 9 10 5 10...

Страница 19: ...19 6 DECLARATION OF CONFORMITY ...

Страница 20: ...20 Installation sequence for flue gas discharge from the wall ...

Страница 21: ...00 B mod 3000 5000 7000 mod 2200 mod 7000 mod 5000 mod 3000 GAS mod 2200 GAS mod 3000 5000 7000 3 Make holes in the wall following the correct model instructions on the template as the position of the holes vary from model to model WARNING THE HOLE FOR AIR INTAKE FLUE GAS PIPES MUST BE SLIGHTLY SLOPING TOWARDS THE GROUND IN ORDER TO ALLOW ANY CONDENSATE TO FLOW AWAY A B INSTRUÇÕES PARA A MONTAGEM ...

Страница 22: ...22 4 Measure the depth of the air intake and flue gas holes made in the wall and cut the pipes 5 cm longer than this depth ...

Страница 23: ...23 5 Fit the supplied seals to the air intake and flue gas pipes 6 Using a lubricant compound if necessary push the two pipes into the machine ...

Страница 24: ...N ONLY In installations with Standard pipes IT IS MANDATORY TO INSTALL on the terminal section of the air intake pipe THE AIR DIAPHRAGM PROVIDED in order for the appliance to operate correctly The air intake and flue gas pipes must project from the outside wall by approximately 2 cm CLASSIC 3000 air diaphragm CLASSIC 5000 and 7000 air diaphragm How to take the casing off ...

Страница 25: ...nal onto the pipe At the end of the operation the termina should look like the figure on the bottom right FLUE AIR AIR AIR AIR SOLUTION B Fix the ring plate to the wall using wall plugs F provided The terminal must then be fixed to the ring plate using the two V screws provided SOLUTION A Fix the ring plate and terminal into place at the same time using F wall plugs provided Air intake Air intake ...

Страница 26: ...earth lead to the green connector use the fast on provided in the installation kit fig 1 Seefig 2forinstructionsonhowtoconnectseveralappliances to a single room thermostat IMPORTANT please follow phase neutral connection sequence as shown in figs 1 and 2 CN6 CN6 FUSE F1A 250V FUSE F1A 250V CN6 FUSE F1A 250V fig 1 fig 2 ...

Страница 27: ...27 ...

Страница 28: ... 0365 878 31 Fax 39 0365 878 576 e mail info fondital it www fondital com The Manufacture reserves the right to make minor modifications to the products as required without affecting the basic features Uff Pub Fondital IST 03 G 009 04 Luglio 2014 07 2014 0YMANUIS12 ...