KC 24 - KRB 24 - KR 24
Minimum permissible length of air intake pipe is 1 meter.
Minimum permissible length of flue gas venting pipe is 1 meter.
Maximum permissible length of air intake/flue gas venting pipes is 84 meters (combined length of air intake and flue gas venting pipe).
For each additional 1 meter of straight pipe maximum permissible length is to be reduced by 1 meter.
For each additional 90° elbow, maximum permissible length is to be reduced by 1 meter.
For each additional 45° elbow, maximum permissible length is to be reduced by 0.5 meter.
The roof terminal reduces maximum permissible length by 5.5 meters.
The wall terminal reduces maximum permissible length by 5 meters.
KC 28 - KRB 28 - KR 28
Minimum permissible length of air intake pipe is 1 meter.
Minimum permissible length of flue gas venting pipe is 1 meter.
Maximum permissible length of air intake/flue gas venting pipes is 91 meters (combined length of air intake and flue gas venting pipe).
For each additional 1 meter of straight pipe maximum permissible length is to be reduced by 1 meter.
For each additional 90° elbow, maximum permissible length is to be reduced by 1 meter.
For each additional 45° elbow, maximum permissible length is to be reduced by 0.5 meter.
The roof terminal reduces maximum permissible length by 5.5 meters.
The wall terminal reduces maximum permissible length by 5.5 meters.
KC 32 - KRB 32 - KR 32
Minimum permissible length of air intake pipe is 1 meter.
Minimum permissible length of flue gas venting pipe is 1 meter.
Maximum permissible length of air intake/flue gas venting pipes is 78 meters (combined length of air intake and flue gas venting pipe).
For each additional 1 meter of straight pipe maximum permissible length is to be reduced by 1 meter.
For each additional 90° elbow, maximum permissible length is to be reduced by 1 meter.
For each additional 45° elbow, maximum permissible length is to be reduced by 0.5 meter.
The roof terminal reduces maximum permissible length by 6 meters.
The wall terminal reduces maximum permissible length by 5.5 meters.
3.2.6.4. Air intake and flue gas venting via 60 mm split pipes
The information given above is with reference to air intake/flue gas venting ducts made from smooth, rigid pipes approved and
supplied by the manufacturer.
Installation types C43 - C53 - C83
KC / KRB / KR 12 - KC / KRB / KR 24 - KC / KRB / KR 28 - KC / KRB / KR 32
Minimum permissible length of air intake pipe is 1 meter.
Minimum permissible length of flue gas venting pipe is 1 meter.
Maximum permissible length of air intake/flue gas venting pipes is 39 meters for the KC / KRB / KR 12, 23 meters for the KC / KRB / KR 24 and KC /
KRB / KR 28 models and of 20 meters for the KC / KRB / KR 32 model (combined length of air intake and flue gas venting pipe).
For each additional 1 meter of straight pipe maximum permissible length is to be reduced by 1 meter.
For each additional 90° elbow, maximum permissible length is to be reduced by 1 meter.
For each additional 45° elbow, maximum permissible length is to be reduced by 0.5 meter.
The air intake/flue gas venting terminal reduces maximum permissible length by 4.5 meters.