Parameter
Settable values
Default values
Notes
P0 - TSP0
Boiler power selection
0 ÷ 5
1
0 = 24 kW LPG; 1 = 24 kW natural gas; 2 = 28 kW LPG;
3 = 28 kW natural gas; 4 = 32 kW LPG; 5 = 32 kW natural gas.
P3 - TSP3
Boiler type selection
1 ÷ 3
1
1 = combined instantaneous; 2 = heating only;
3 = with water heater
P6 - TSP6
Ignition power setting
0 ÷ 100 %
(min-max)
0 %
With P6=0 ignition with ramp
With P6≠0 ignition at the set power
(P6=1 minimum power ÷ P6=100 maximum power)
P7 - TSP7
Heating power maximum setting
10 ÷ 100%
100%
P10 - TSP10
Heating output curves
0 ÷ 3
1,5
resolution 0.05
P11 - TSP11
Heating thermostat timing
0 ÷ 10 min.
4
P12 - TSP12
CH power rising ramp timer
0 ÷ 10 min.
1
P13 - TSP13
Timing of post-circulation, heating, anti-freeze, flue clean-
ing
30 ÷ 180 sec.
30
P14 - TSP14
Setting of "solar" DHW thermostats
0 ÷ 1
0
0 = normal
1 = solar
P15 - TSP15
Anti water hammer delay
0 ÷ 3 sec.
0
P16 - TSP16
Ambient thermostat reading delay / Remote Control
0 ÷ 199 sec.
0
P17 - TSP17
Multifunction relay setting
0 ÷ 3
0
0 = shut-down and fault;
1 = requested by the ambient thermostat 1/Remote Control;
2 = solar; 3 = request by the ambient thermostat 2
S
olar par
. (with P17=2 or with supplementar
y boar
d)
P18 - TSP18
Solar system selection
0 ÷ 1
0
0 = solar valve; 1 = solar pump
P19 - TSP19
Water heater set-point setting
10 ÷ 90 °C
60 °C
only with P18 = 1
P20 - TSP20
ΔT ON (diff. solar pump ignition)
1 ÷ 30 °C
6 °C
P21 - TSP21
ΔT OFF (diff. solar pump shut-down)
1 ÷ 30 °C
3 °C
P22 - TSP22
Maximum collector temperature
80 ÷ 140 °C
120 °C
P23 - TSP23
Minimum collector temperature
0 ÷ 95 °C
25 °C
P24 - TSP24
Solar collector anti-freeze
0 ÷ 1
0
0 = anti-freeze not enabled; 1 = anti-freeze enabled
(only with P18 = 1)
P25 - TSP25
Solar load forcing
0 ÷ 1
0
0 = automatic operation; 1 = always enabled
P26 - TSP26
Enabling of water heater cooling
0 ÷ 1
0
0 = disabled; 1 = enabled
(only with P18 = 1)
P27 - TSP27
Heating timer reset temperature
35 ÷ 78 °C
40 °C
P28 - TSP28
Hydraulic selection for deviating valve relay control
0 ÷ 1
0
0 = recirculating pump + deviating valve; 1 = double pump.
P29 - TSP29
Default parameter setting (except P00, P01, P02, P17, P28)
0 ÷ 1
0
0 = user's parameters
1 = default parameters
Displa
y only
P30
External temperature
only with external probe connected
P31
Flow temperature
P32
Nominal calculated flow temperature
only with external probe connected
P33
Set point of zone 2 flow temperature
only with at least one zone board connected
P34
Current zone 2 flow temperature
only with at least one zone board connected