7
5.1.
Details of bathroom installation
The appliance must be installed according to current regulations and laws in force in the country of use.
The radiator is class I and has IPX4 electrical protection. In bathrooms, it can be installed in areas 2 and 3 (see figure 1) provided that the control
device is not within reach of people using the shower or bathtub.
The radiator must not be connected to the earth lead.
In the bathroom, protect the power line with a 30 mA high sensitivity differential device.
Install a multi-pole circuit breaker. The distance between the contacts must be at least 3 mm.
2,25 m
fig. 1
AREA 0
AREA 0
AREA 1
AREA 2
AREA 3
5.
ELECTRICAL CONNECTIONS
Important: When installing, or cleaning your Vantage Electric Radiator, it must be disconnected from the power supply.
The Vantage Electric Radiator must be connected only to a 230/240v AC power supply.
A multi-pole circuit breaker must be installed. The distance between the contacts must be at least 3 mm. The appliance’s power circuit must be
protected by a high sensitivity differential protection device.
The radiator is supplied with a 3-pin plug and allows phase, neutral and ground connections.
The electrical equipment must be provided with grounding.
Never insert metal objects into or attempt to pierce the side of the radiator containing the regulation system (right side).If the power cord is
damaged, it must be replaced by a qualified electrician only.